Time constants ( s ) Resistance. Other data - Class H /6600 V kva. Efficiencies ( % )(3 phase - Classe H V kva)

Size: px
Start display at page:

Download "Time constants ( s ) Resistance. Other data - Class H /6600 V kva. Efficiencies ( % )(3 phase - Classe H V kva)"

Transcription

1 Alternators: LSA 5, XL8 Ratings 5 Hz 5 rpm kva 66 V 4 poles kva / kwe - Cos φ =,8 3 phase Duty / Ambient Continuous duty (BR) / 4 C PR* / 4 C PR* / 7 C Temperature Rise Class.H/5 K Class.F/5 K 5 K 63 K Tension (*) 63 V - 66 V 63 V - 66 V 63 V - 66 V 63 V - 66 V kva 84 kwe (*) Y connection * PR= Peak rating Reactances (%) - class H / 66 V - kva Short-circuit ratio Direct axis synchronous reactance Quadrature axis synchronous reactance Direct axis transient reactance Quadrature axis transient reactance Direct axis subtransient reactance Quadrature axis subtransient reactance Negative sequence reactance Zero sequence reactance Stator leakage reactance Rotor leakage reactance unsaturated saturated Kcc,53 Xd,5,887 Xq,3,3 X'd,8,94 X'q,3,3 X''d,6,7 X''q,58,34 X,4, X Xs or Xl Xr,9,63,8 Time constants ( s ) Open circuit direct axis transient time constant Open circuit quadrature axis transient time constant Short-circuit direct axis transient time constant Short circuit quadrature axis transient time constant Open circuit direct axis subtransient time constant Open circuit quadrature axis subtransient time constant Subtransient direct axis time constant Subtransient quadrature axis time constant Armature time constant T'do,88 T'qo NA T'd,9 T'q NA T''do,36 T''qo,4 T''d, T''q,8 Ta,4 Resistance Armature resistance X/R ratio Zero sequence resistance Negative sequence resistance Ra,3 X/R 9,478 R 3,67 R,84 Other data - Class H /66 V - kva no load excitation current full load excitation current full load excitation voltage Air flow Harmonic rate (**) total harmonic content line to line, at no load or with linear and balanced load. io ( A),7 ic (A) 4,7 uc (V) 5 M3/s,5 % NA Efficiencies ( % )(3 phase - Classe H - 66 V - kva) COS Ø =,8 COS Ø = 5% 5% 75% % % 5% 5% 75% % % 9,9 95,4 95,9 95,9 95,9 93,4 96, 96,8 97, 97,

2 Alternators: LSA 5, XL8 5 Hz 5 rpm kva 66 V 4 poles Efficiencies P.F. / P.F.,8 PF 98 PF,8 97 Efficiency - Rendement en % % 5% 75% % Load - Charge - % of rated electrical kw Transient voltage variation : 66 V - 5 Hz Transient voltage dip curve versus load impact 3% 5% Voltage dip - (% of rated voltage) % 5% % 5% PF = % PF =,8,,4,8,,6, Inrush - Appel de charge - % of rated kva Transient voltage rise curve versus load rejection % Voltage rise - (% of rated voltage) 5% % 5% PF =,8 %,,5,5,75,,5,5 kva shedding at P.F. - % of rated kva

3 Alternators: LSA 5, XL8 5 Hz 5 rpm kva 66 V 4 poles 3 phase short-circuit curves at no load and rated speed ( Y connection ) 4 Isc (Per unit - rms) Heat damage curve Symmetrical phase to neutral short circuit Symmetrical two phase short circuit Symmetrical three phase short circuit short circuit at generator terminals 8 6 4,,, Time (sec) Capability curve ( PQ diagram ),7 p.f.,8 p.f.,9 p.f. kwe / rated kva,944 p.f.,9 p.f.,875 p.f.,8 p.f.,7 p.f.,9,6 p.f.,8,7,6 p.f.,5 p.f.,6,5 p.f.,4 p.f.,5,4,4 p.f.,3 p.f.,3,3 p.f., p.f.,, p.f., p.f.,, p.f. - -,8 -,6 -,4 -,,,4,6,8 kvar / rated kva

4 SPECIALLY ADAPTED FOR GENSET APPLICATIONS The alternator is designed to be suitable for typical generator set applications,such as: backup, base production, cogeneration, marine applications, rental, telecommunications, etc. COMPLIANT WITH INTERNATIONAL STANDARDS The alternator conforms to the main international standars and regulations IEC 634, NEMA MG., ISO 853/3, CSA UL 446, UL 4B on request, marine regulations, etc. It can be integrated into a CE marked generator The alternator is designed, manufactured and marketed in an ISO 9 and ISO 4 environment. TOP OF THE RANGE ELECTRICAL PERFORMANCE - Class H insulation. - Standard 6-wire winding, /3 pitch for Low Voltage, and 5/6 pitch for Medium & High Voltage - Other voltages are possible with optional adapted windings. - High efficiency and motor starting capacity. EXCITATION AND REGULATION SYSTEM SUITED TO THE APPLICATION The alternator can be supplied with 'AREP+PMI' or PGM excitation system, according to the alternator specification. standard excitation system is AREP with R449 A.V.R. Excitation system regulator AREP+PMI PMG C.T. R76 R73 mains // mains // 3 phase sensing external Pot. R 449 std D 5 included included voltage regulation accuracy ±,5% PROTECTION SYSTEM SUITED TO THE ENVIRONMENT The alternator is IP 3 in standard. - Standard winding protection for clean environments with relative humidity 95%, including indoor marine environments. s : IP43 - IP44 : filters on air inlet and air outlet, water mist separator Winding protections for Harsh environments and relative humidity greater than 95% Space heaters. Thermal protection for winding.(pt) REINFORCED MECHANICAL STRUCTURE USING FINITE ELEMENT MODELLING -Compact and rigid assembly to better withstand genset or engine vibrations. - Steel frame. - Cast iron flanges and shields. -Twin-bearing and single-bearing versions designed to be suitable for most engines on the market. -Half-key balancing. -Regreasable bearings. ACCESSIBLE TERMINAL BOX PROPORTIONED FOR OPTIONAL EQUIPMENT - Easy access to the voltage regulator and to the connections. - Possible incorporation of accessories for parralleling, protection and measurement. Regulation options COMMON DATA insulation class winding pitch terminals drip proof altitude overspeed H /3 (n 6S) 6 IP 3 m 5 min- excitation system regulation accuracy (*) sustained short-circuit current Total harmonic (**) TGH / THC waveform : NEMA= TIF - (**) Waveform : C.E.I. = FHT - (**) (*) steady state duty. (**) total harmonic content line to line, at no load or full rated linear and balanced load. AREP+PMI ou PMG ±,5 % 3% (3 IN) : S < 3,5% < 5 < % Products and materials shown in this catalog may, at any time, be modified in order to follow the latest technological developments, improve the design or change conditions of utilization. Their description cannot, in any case, engage LEROY-SOMER liability. The values indicated are typical values.

5 Thermal damage curve Stator current (per rated current) 3,5,5 Negative phase sequence current (per rated current) 3 Maximum duration (seconds) Unbalanced load curve Maximum duration of fault (seconds) Stator Earth Fault Current Fault Current (A) A B C C : Extensive damage B : Considerable damage A : Acceptable damage Maximum duration of fault (seconds)

LSA Pole. R 726 Mains paralleling

LSA Pole. R 726 Mains paralleling 498 en-.27 / a Alternators LSA.2-4 Pole Electrical and mechanical data LSA.2-4 Pole SPECIALLY ADAPTED FOR APPLICATIONS The LSA.2 alternator is designed to be suitable for typical generator set applications,

More information

PARTNER ALTERNATORS LSA Pole

PARTNER ALTERNATORS LSA Pole 90 16 kva - 0 Hz 1 6 kva - 60 Hz 38 en - 11.04 / g PARTNER ALTERNATORS LSA 44.2-4 Pole Electrical and mechanical data SPECIALLY ADAPTED FOR APPLICATIONS The LSA 44.2 alternator is designed to be suitable

More information

Low Voltage alternators - 4 pole LSA 47.2

Low Voltage alternators - 4 pole LSA 47.2 Low Voltage alternators - 4 pole 36 to 6 kva - Hz / 46 to 7 kva - 6 Hz Electrical and mechanical data 3782 en - 214.1 / h 36 to 6 kva - Hz / 46 to 7 kva - 6 Hz SPECIALLY ADAPTED TO APPLICATIONS The alternator

More information

Low Voltage alternators - 4 pole LSA 46.2

Low Voltage alternators - 4 pole LSA 46.2 Low Voltage alternators - 4 pole 18 to 31 kva - Hz / 228 to 381 kva - 6 Hz Electrical and mechanical data 379 en - 212.11 /h 1-8-POWER-8 18 to 31 kva - Hz / 228 to 381 kva - 6 Hz SPECIALLY ADAPTED TO APPLICATIONS

More information

PARTNER ALTERNATORS LSA 40-4 Pole

PARTNER ALTERNATORS LSA 40-4 Pole 23 kva - 50 Hz 12,5 28 kva - 60 Hz 4250 en - 2011.03 / c PARTNER ALTERNATORS LSA 40-4 Pole Electrical and mechanical data SPECIALLY ADAPTED TO APPLICATIONS The LSA 40 alternator is designed to be suitable

More information

LSA R & LSA H 49.1 Low Voltage Alternators - 4 pole

LSA R & LSA H 49.1 Low Voltage Alternators - 4 pole LSA R & LSA H 49.1 Low Voltage Alternators - 4 pole 30 to 30 kva - 0 Hz / 420 to 63 kva - 60 Hz Electrical and mechanical data Adapted to applications LSA R and LSA H alternators are enclosed alternators

More information

ALTERNATOR TECHNICAL DESCRIPTION 1. LSA 53.2 XL13 / 4p. Chargé d'affaire : Karthikeyan GN 1 Moteurs Leroy-Somer +33 (0) xx

ALTERNATOR TECHNICAL DESCRIPTION 1. LSA 53.2 XL13 / 4p. Chargé d'affaire : Karthikeyan GN 1 Moteurs Leroy-Somer +33 (0) xx ALTERNATOR TECHNICAL DESCRIPTION LSA 53.2 XL3 / 4p LS Reference: 3_66 Date: 426 V4.5G 9/26 Chargé d'affaire : Karthikeyan GN Moteurs LeroySomer +33 ()2 38 6 42 xx Electric Power Generation Orleans prenom.nom@leroysomer.com

More information

TAL 049 Low Voltage Alternator - 4 pole

TAL 049 Low Voltage Alternator - 4 pole TAL 049 Low Voltage Alternator - 4 pole 730 to 1000 kva - 50 Hz / 915 to 1250 kva - 60 Hz Electrical and mechanical data Adapted to needs The TAL alternator range is designed to meet the needs of general

More information

TAL 047 Low Voltage Alternator - 4 pole

TAL 047 Low Voltage Alternator - 4 pole TAL 047 Low Voltage Alternator - 4 pole 4 to 660 kva - 50 Hz / 5 to 825 kva - 60 Hz Electrical and mechanical data Adapted to needs The TAL alternator range is designed to meet the needs of general applications

More information

TAL 044 Low Voltage Alternator - 4 pole

TAL 044 Low Voltage Alternator - 4 pole TAL 044 Low Voltage Alternator - 4 pole Three-phase 70 to 65 kva - 50 Hz / 88 to 206 kva - 60 Hz Dedicated single-phase 57 to 82 kva - 50 Hz / 80 to 25 kva - 60 Hz Electrical and mechanical data TAL 044

More information

WDG 51 - Technical Data Sheet

WDG 51 - Technical Data Sheet MV 804 S WDG 51 - Technical Data Sheet FRAME MV 804 S SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 W WDG 12 - Technical Data Sheet FRAME LV 804 W SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 R WDG 12 - Technical Data Sheet FRAME LV 804 R SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

S0L1-J1 - Technical Data Sheet

S0L1-J1 - Technical Data Sheet S0L1-J1 - Technical Data Sheet Standards Stamford industrial alternators meet the requirements of the relevant parts of the IEC EN 60034 and the relevant section of other international standards such as

More information

WDG 61 - Technical Data Sheet

WDG 61 - Technical Data Sheet HV 804 W WDG 61 - Technical Data Sheet FRAME HV 804 W SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

S4L1S-D4 Wdg.17 - Technical Data Sheet

S4L1S-D4 Wdg.17 - Technical Data Sheet - Technical Data Sheet Standards STAMFORD industrial alternators meet the requirements of the relevant parts of the BS EN 60034 and the relevant section of other international standards such as BS5000,

More information

WDG 71 - Technical Data Sheet

WDG 71 - Technical Data Sheet HV 804 R WDG 71 - Technical Data Sheet FRAME HV 804 R SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

WDG 83 - Technical Data Sheet

WDG 83 - Technical Data Sheet HV 804 R WDG 83 - Technical Data Sheet FRAME HV 804 R SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

WDG 07 - Technical Data Sheet

WDG 07 - Technical Data Sheet LV 804 S WDG 07 - Technical Data Sheet FRAME LV 804 S SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 T WDG 12 - Technical Data Sheet FRAME LV 804 T SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

S4L1D-G41 Wdg Technical Data Sheet

S4L1D-G41 Wdg Technical Data Sheet - Technical Data Sheet Standards Stamford industrial alternators meet the requirements of the relevant parts of the BS EN 60034 and the relevant section of other international standards such as BS5000,

More information

WDG 13 - Technical Data Sheet

WDG 13 - Technical Data Sheet LV 804 T WDG 13 - Technical Data Sheet FRAME LV 804 T SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 S WDG 12 - Technical Data Sheet FRAME LV 804 S SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

PI734F - Winding 07. Technical Data Sheet APPROVED DOCUMENT

PI734F - Winding 07. Technical Data Sheet APPROVED DOCUMENT - Winding 07 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 34 and the relevant sections of other national and international standards

More information

PI734F - Winding 28. Technical Data Sheet APPROVED DOCUMENT

PI734F - Winding 28. Technical Data Sheet APPROVED DOCUMENT - Winding 28 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information

PI734E - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734E - Winding 312. Technical Data Sheet APPROVED DOCUMENT - Winding 312 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information

PI734C - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734C - Winding 312. Technical Data Sheet APPROVED DOCUMENT - Winding 312 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information

PI734B - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734B - Winding 312. Technical Data Sheet APPROVED DOCUMENT - Winding 312 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information

PI734C - Technical Data Sheet

PI734C - Technical Data Sheet PI734C - Technical Data Sheet PI734C SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

PI734A - Technical Data Sheet

PI734A - Technical Data Sheet PI734A - Technical Data Sheet PI734A SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

PM734D - Winding 312. Technical Data Sheet APPROVED DOCUMENT. Generator Solutions AS

PM734D - Winding 312. Technical Data Sheet APPROVED DOCUMENT. Generator Solutions AS PM734D - Winding 312 Technical Data Sheet PM734D SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and

More information

PM734F - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PM734F - Winding 312. Technical Data Sheet APPROVED DOCUMENT PM734F - Winding 312 Technical Data Sheet PM734F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and

More information

4939 en / a PARTNER ALTERNATORS LSA 54. General features and ratings

4939 en / a PARTNER ALTERNATORS LSA 54. General features and ratings 99 en - 00 / a PRTNR LTRNTORS LS eneral features and ratings LTRNTOR : LS M / 0kV - 00V - 0z - 00rpm - P (*) Y connection * PR= Peak rating Reactances (%) - class - 0 kv - 00 V unsaturated Short-circuit

More information

440 (12) 416 (12) 416 (12) 440 (12)

440 (12) 416 (12) 416 (12) 440 (12) ALTERNATOR DATA SHEET Frame Size LVSI804X CHARACTERISTICS No of Bearings 2 WEIGHTS: Stator Assembly: 10141 lb 4 kg Rotor Assembly: 4184 lb 1898 kg Complete Assembly: 18289 lb 8296 kg MAXIMUM SPEED: 2250

More information

PM734B - Technical Data Sheet. Generator Solutions AS

PM734B - Technical Data Sheet. Generator Solutions AS - Technical Data Sheet STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and certifications can be considered on request. DESCRIPTION

More information

Spec Information. Reactances Per Unit Ohms

Spec Information. Reactances Per Unit Ohms GENERATOR DATA Spec Information Generator Specification Frame: 1647 Type: SR5 No. of Bearings: 1 Winding Type: RANDOM WOUND Flywheel: 21.0 Connection: SERIES STAR Housing: 00 Phases: 3 No. of Leads: 6

More information

GENERATOR DATA JANUARY 30, 2015

GENERATOR DATA JANUARY 30, 2015 GENERATOR DATA JANUARY 30, 2015 For Help Desk Phone Numbers Click here Generator Specification Frame: 1822 Type: SR5 No. of Bearings: 2 Winding Type: FORM WOUND Flywheel: 21.0 Connection: SERIES STAR Housing:

More information

AGN 034 Alternator Reactance

AGN 034 Alternator Reactance Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 034 Alternator Reactance DEFINITION Reactance Periods Inherent to the design of an alternator are certain internal

More information

Spec Information. Reactances Per Unit Ohms

Spec Information. Reactances Per Unit Ohms GENERATOR DATA Spec Information Generator Specification Frame: LC6134K Type: LC No. of Bearings: 1 Winding Type: RANDOM WOUND Flywheel: 18.0 Connection: - STAR Housing: 0 Phases: 3 No. of Leads: 6 Poles:

More information

4938 en / a PARTNER ALTERNATORS LSA General features and rating4

4938 en / a PARTNER ALTERNATORS LSA General features and rating4 9 en - 00 / a PRTNR LTRNTORS LS eneral features and rating LTRNTOR : LS M0 / 000kV - 00V - 0z - 00rpm - P (*) Y connection * PR= Peak rating Reactances (%) - class - 000 kv - 00 V unsaturated Short-circuit

More information

Packaged Generators: New Kato Engineering Packaged Generator Line: Over 75 Years of Experience: Conformity: Service: Quality Standards:

Packaged Generators: New Kato Engineering Packaged Generator Line: Over 75 Years of Experience: Conformity: Service: Quality Standards: Packaged Generators: New Kato Engineering Packaged Generator Line: The new Kato Engineering line of generators is a group of commercial and industrial quality generators that can meet the broadest range

More information

Generation Interconnection Study Data Sheet Synchronous Machines

Generation Interconnection Study Data Sheet Synchronous Machines FOR INTERNAL USE ONLY GTC Project Number: Queue Date: Generation Interconnection Study Data Sheet Synchronous Machines Customers must provide the following information in its entirety. GTC will not proceed

More information

APPENDIX 1 to LGIP INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY

APPENDIX 1 to LGIP INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY APPENDIX 1 to LGIP INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY 1. The undersigned Interconnection Customer submits this request to interconnect its Large Generating Facility with Transmission

More information

PI144H - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI144H - Winding 311 APPROVED DOCUMENT. Technical Data Sheet PI144H - Winding 311 Technical Data Sheet PI144H SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY

INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY Internal Use Only Date Received Time Received Received By: 1. The undersigned Interconnection Customer submits this request to interconnect its Large

More information

Low Voltage Alternators - 4 pole

Low Voltage Alternators - 4 pole TAL - A40 - A42 - A44 Electrical and mechanical data Advanced Production Technology Automated winding process to ensure maximum lifespan and reduce human error VPI (vacuum pressure impregnation) insulation

More information

Low Voltage Alternators

Low Voltage Alternators Low Voltage Alternators Excitation and regulation systems SHUNT - PMG - AREP Low Volta SHUNT excitation for basic applications - The AVR power supply voltage is shunted on the alternator output terminals.

More information

Technical Data Sheet for AvK-Alternators

Technical Data Sheet for AvK-Alternators Technical Data Sheet for AvK-Alternators FM 7.3-5 Date: 8/1/14 Customer: GENERIC DATASHEET only Project No.: AvK Reference: dsg114l1_6_5_69_a48m988 Object data: Site: Prime Mover: Application: Stationary

More information

Technical Data Sheet for AvK-Alternators

Technical Data Sheet for AvK-Alternators Technical Data Sheet for AvK-Alternators FM 7.3-5 Date: 9/1/13 Customer: GENERIC DATASHEET only Project No.: AvK Reference: dig156l_6_6_138 Object data: Site: Prime Mover: Application: Stationary Power

More information

Technical Data Sheet for AvK-Alternators

Technical Data Sheet for AvK-Alternators Technical Data Sheet for AvK-Alternators FM 7.3-5 Date: 9/1/13 Customer: GENERIC DATASHEET only Project No.: AvK Reference: dig13k_4_5_33 Object data: Site: Prime Mover: Application: Stationary Power Plant

More information

Technical Data Sheet for AvK-Alternators

Technical Data Sheet for AvK-Alternators Technical Data Sheet for AvK-Alternators FM 7.3-5 Date: 3/9/13 Customer: Bitte Interessent eingeben! Project No.: AvK Reference: 1-67-83-1 Object data: Site: Prime Mover: Application: Stationary Power

More information

Application Guidance Notes: Technical Information from Cummins Generator Technologies

Application Guidance Notes: Technical Information from Cummins Generator Technologies Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 007 - Testing POLICY The following is offered as an eplanation of the policy and procedures followed by Cummins

More information

AGN 005 Fault Currents and Short Circuit Decrement Curves

AGN 005 Fault Currents and Short Circuit Decrement Curves Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 005 Fault Currents and Short Circuit Decrement Curves DESCRIPTION To facilitate the correct design of an electrical

More information

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW Electric Utility Contact Information DTE Energy Interconnection Coordinator One Energy Plaza, SB

More information

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS 2-1. General but less than locked-rotor amperes and flows only Electrical power systems must be designed to serve in the normal circuit path. a variety of

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

HCM634G - Technical Data Sheet

HCM634G - Technical Data Sheet HCM634 - Technical Da Sheet HCM634 SPECIFICATIONS & OPTIONS TERMINALS & TERMINAL BOX Marine gs may be ctified to Lloyds, DnV, Bureau Vitas, ABS, manisch-lloyd RINA. Oth standards and ctificio can be coided

More information

R448 & R448 V50 A.V.R. Installation and maintenance R 448 ST5 ST3 ST10. Armature + 6- Field X2 Z1 X1 Z2 E+ E- 0V Slow fuse 250V 10 A

R448 & R448 V50 A.V.R. Installation and maintenance R 448 ST5 ST3 ST10. Armature + 6- Field X2 Z1 X1 Z2 E+ E- 0V Slow fuse 250V 10 A Armature + 6- Field Thismanualistobegivento theenduser F1 ST5 Slow fuse 250V 10 A with LAM without LAM 10 Yellow 11 Red 12 Black 9 Green X2 Z1 X1 Z2 E+ E- 0V 110 22 ST3 requency 50Hz 60Hz ST10 R 448 This

More information

ECP3 4. Rev. 1. Powered by TCPDF (www.tcpdf.org)

ECP3 4. Rev. 1. Powered by TCPDF (www.tcpdf.org) Rev. 1 Powered by TCPDF (www.tcpdf.org) General Data Standards Alternators are designed and produced within an ISO 9001 environment. The entire series is manufactured according to, and complies with,

More information

NPE32 4. Rev. 1. Powered by TCPDF (

NPE32 4. Rev. 1. Powered by TCPDF ( Rev. 1 Powered by TCPDF (www.tcpdf.org) General Data Standards Alternators are designed and produced within an ISO 9001 environment. The entire series is manufactured according to, and complies with,

More information

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy

More information

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System WHO SHOULD FILE THIS SUBMITTAL: Anyone in the final stages of interconnecting a Generation System with Nodak Electric Cooperative, Inc. This submittal shall be completed and provided to Nodak Electric

More information

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company Engineering data submittal Page 1 WHO SHOULD FILE THIS SUBMITTAL : Anyone in the final stages of in terconnecting a Generation System with Otter Tail Power. This submittal shall be completed and provided

More information

R448 & R448 V50 A.V.R.

R448 & R448 V50 A.V.R. Armature + 6- This manual is to be given to the end user F1 ST5 Field Slow fuse 250V 10 A with LAM without LAM 10 Yellow 11 Red 12 Black 9 Green X2 Z1 X1 Z2 E+ E- 0V 110 22 ST3 requency 50Hz 60Hz LAM 13

More information

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number:  Address: NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information

More information

Cooling Fans G-17. Cooling Fans G-17. AC Input/Low-Power Consumption EMU Series. AC Input/Compact Size MU Series

Cooling Fans G-17. Cooling Fans G-17. AC Input/Low-Power Consumption EMU Series. AC Input/Compact Size MU Series Cooling G-17 Cooling / E / / / S / / V / E / P E S V E P D D Page Introduction G-18 E G-22 G-26 G-36 G-52 S G-56 Low Speed G-76 V G-80 E G-82 P G-84 G-17 G-18 Technical reference

More information

ILA2E572PC1A0 integrated drive ILA with servo motor V - EtherCAT - indus connector

ILA2E572PC1A0 integrated drive ILA with servo motor V - EtherCAT - indus connector Characteristics integrated drive ILA with servo motor - 24..48 V - EtherCAT - indus connector Main Range of product Product or component type Device short name Motor type Number of motor poles 6 Network

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

r 450 Installation and maintenance This manual is to be given to the end user R 450 VOLT. STAB. I EXC STAT. AREP PMG FUSIBLES / FUSES

r 450 Installation and maintenance This manual is to be given to the end user R 450 VOLT. STAB. I EXC STAT. AREP PMG FUSIBLES / FUSES 8 7 9 6 5 4 C 45 en -. / a R 45 DETECT. PH PH. SENSING 5 Hz EXT FREQ 6 Hz SETTING This manual is to be given to the end user VOLT. STAB. I EXC FUSIBLES / FUSES EXT.FREQ. SET. ON ONLY FOR SPECIAL CONFIG.

More information

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW Electric Utility Contact Information Detroit Edison Company Interconnection

More information

APPENDIX B: Generation Interconnection Application Form

APPENDIX B: Generation Interconnection Application Form 2 APPENDIX B: Generation Interconnection Application Form WHO SHOULD FILE THIS APPLICATION: Anyone expressing interest to install generation which will interconnect with Xcel Energy (Local electric utility)

More information

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H018F1 variable speed drive ATV kW hp V - 1ph Characteristics variable speed drive ATV12-0.18kW - 0.25hp - 100..120V - 1ph Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application

More information

R 450. AVRs. Installation and maintenance. This manual is to be given to. the end user R 450 VOLT. STAB. I EXC STAT. LEDS PMG

R 450. AVRs. Installation and maintenance. This manual is to be given to. the end user R 450 VOLT. STAB. I EXC STAT. LEDS PMG 6 5 4 7 8 9 C US 45 en -. / e 5 Hz EXT FREQ 6 Hz SETTING This manual is to be given to the end user VOLT. STAB. I EXC FUSIBLES / FUSES EXT.FREQ. SET. ON ONLY FOR SPECIAL CONFIG. KNEE 5Hz 65Hz 6Hz PHASE

More information

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol Product datasheet Characteristics ATV12HU22M2 Complementary Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component name Variable

More information

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink Characteristics variable speed drive ATV12-4kW - 5hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

Sizing Generators for Leading Power Factor

Sizing Generators for Leading Power Factor Sizing Generators for Leading Power Factor Allen Windhorn Kato Engineering 24 February, 2014 Generator Operation with a Leading Power Factor Generators operating with a leading power factor may experience

More information

Short-circuit behavior - Xd ; s-s, transient, subtransient. Chapter 4 - Series Resistance of Transmission Lines

Short-circuit behavior - Xd ; s-s, transient, subtransient. Chapter 4 - Series Resistance of Transmission Lines EE 5200 - Lecture 15 Fri Oct 6, 2017 Announcements SYNCH homework posted, due latest Mon 9am Office hrs: EERC 123 4:05-5:55pm W,F (online connect via Zoom) Office: EERC 614. Phone: 906.487.2857 Recommended

More information

R438 A.V.R. Installation and maintenance. This manual is to be given to. the end user CALL US TODAY POWER-58. SHOP ONLINE

R438 A.V.R. Installation and maintenance. This manual is to be given to. the end user CALL US TODAY POWER-58. SHOP ONLINE T1 T7 T2 T8 This manual is to be given to the end user T4 T10 140 mm T5 T11 X2 Z1X1 Z2 E+ E- 0V 110 220 380 200 mm z P1 ST9 AREP PMG This manual concerns the alternator which you have just purchased. We

More information

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY WN U-60 Attachment C to Schedule 152, Page 1 SCHEDULE 152 APPLICATION FOR INTERCONNECTING A GENERATING FACILITY TIER 2 OR TIER 3 This Application is considered complete when it provides all applicable

More information

Incremental encoders Redundant sensing, isolated blind hollow shaft ø mm, cone shaft ø17 mm pulses per revolution

Incremental encoders Redundant sensing, isolated blind hollow shaft ø mm, cone shaft ø17 mm pulses per revolution Features Robust, compact housing Two bearings with large distance, one at each end High shaft load up to 450 N Shock resistant up to 250 g Shaft insulation up to 2.8 kv Highest operating speed 10000 rpm

More information

SAMSUNG ELECTRO-MECHANICS CO., LTD

SAMSUNG ELECTRO-MECHANICS CO., LTD Model Name : Features : ㅡ Suitable for LED lighting application ㅡ UL8750, UL1310 Class 2 ㅡ For use in Dry and Damp Location ㅡ Full-protection provided: OCP/OVP/OTP/SCP ㅡ 0-10V Dimming Control ㅡ IP67 ㅡ

More information

PART 1 OWNER/APPLICANT INFORMATION

PART 1 OWNER/APPLICANT INFORMATION CALHOUN COUNTY ELECTRIC COOP. ASSN. Application for Operation of Customer-Owned Generation This application should be completed as soon as possible and returned to the Cooperative in order to begin processing

More information

Conventional Paper-II-2013

Conventional Paper-II-2013 1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine

More information

K Factor Power Transformers

K Factor Power Transformers Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business

More information

CLP0112 Open Frame Power Supply Vac input; 12Vdc output; 150W Output Power

CLP0112 Open Frame Power Supply Vac input; 12Vdc output; 150W Output Power Applications Telecommunications equipment Embedded Computing Storage Systems Industrial equipment Features Compact size 50.8 mm x 101.6 mm x 36.1 mm (2 in x 4 in x 1.4 in) with density of 13.4W/in 3 Universal

More information

DATAMAX GENERATORS DATA C E NT E R A P P L I C AT I O N S, TO K W LOW A N D H I G H VO LTAG E, 6 0 A N D 5 0 H Z

DATAMAX GENERATORS DATA C E NT E R A P P L I C AT I O N S, TO K W LOW A N D H I G H VO LTAG E, 6 0 A N D 5 0 H Z DATAMAX GENERATORS DATA C E NT E R A P P L I C AT I O N S, 110 0 TO 3 5 0 0 K W LOW A N D H I G H VO LTAG E, 6 0 A N D 5 0 H Z DATAMAX TM GENERATORS When mission critical loads are on the line data centers

More information

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication: Application : RISH Master 3490 SS is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy having auto-resetting 8 digit seven segment LED counter. The unit

More information

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems This application should be completed as soon as possible and returned to the Cooperative in order to

More information

Code No: R Set No. 1

Code No: R Set No. 1 Code No: R05310204 Set No. 1 III B.Tech I Semester Regular Examinations, November 2007 ELECTRICAL MACHINES-III (Electrical & Electronic Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Product availability : Stock - Normally stocked in distribution facility Price* : 191.76 USD Main Range of

More information

Standard & Optional Items, Certifications and RFQ

Standard & Optional Items, Certifications and RFQ Standard & Optional Items, Certifications and RFQ Standard & Optional Items, Certifications and RFQ Standard Items Optional Items Hazardous Certifications Marine Certifications API-546 Request for Quote

More information

OBICON. Perfect Harmony. Short overview. ROBICON Perfect Harmony. System Overview. The Topology. The System. ProToPS. Motors.

OBICON. Perfect Harmony. Short overview. ROBICON Perfect Harmony. System Overview. The Topology. The System. ProToPS. Motors. and Drives Control R Interface OBICON Perfect Harmony Short overview 14.03.2007 1 System overview Product features Truly Scaleable Technology 300 kw to 30 MW (Single Channel) Large Number of Framesizes

More information

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation This application is to be completed and returned to the Cooperative member service representative in order to begin

More information

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %

More information

1 INTRODUCTION ORDER CODE / INFORMATION

1 INTRODUCTION ORDER CODE / INFORMATION INTRODUCTION ORDER CODE / INFORMATION 269/269Plus * * * * * * 269/269Plus SV D/O.4 ORDER CODE / INFORMATION Motor management relay Standard version Drawout version Phase CT Ground CT (required for D/O

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

Orbital GFI Inverter Series

Orbital GFI Inverter Series Orbital GFI Inverter Series Datasheet Key Features One, split or three phases and up to 25 kva Superior efficiency of 95% CAN Bus control and DAQ Power quality and EMC compliance in accordance with European

More information