1 QUARTINO, WHITE PAPER Evaluation of transformer-free UPS design vs transformer-based by Carlo Kufahl, Product Manager, 3-phase UPS 1/1

2 Evaluation of transformer-free UPS design vs transformer-based The real function of the transformer in a UPS The first double-conversion UPS where born in the 1970s and at that time the semiconductors available, on top of being bigger and less performing; they were not compatible with the voltage levels as today. Consequently, the UPS system at that time needed a transformer to step-up the voltage of the UPS output in order to provide to the critical load the same voltage rating of the input (mains). This is the original and only reason why there was the need of having a transformer integrated in the UPS. Evolution of double-conversion UPS UPS are subject to technology evolution on a 3-5 year rate, which is the same rate for the electronics and power-electronics evolution. Among many others, there has been one very important step of technology, which is worth explaining in this context because 1) its customer benefits are significant as we will cover in a moment and 2) it permitted to change from transformer-based design into transformer-free. It is the topology change of the power converters (rectifier and inverter), which started to happen at the very beginning of this century, from thyristor-based design first 6-pluse and later 12-pulse thyristor bridges into the today topology based on IGBT (Insulated Gate Bipolar Transistor). Today virtually all doubleconversion UPS have the power converters based on IGBT and are transformer-free. Differences between transformer-free and transformer-based design and its effect on the customer benefits Before we look into the design differences and its consequences/impact, let us briefly explain how the two topologies work, by means of single line diagrams (Figure 1 and Figure 2). Transformer-based UPS The UPS has two AC inputs, the rectifier and bypass inputs, one AC output and a DC connection for the battery. The rectifier and bypass inputs can be connected together (inside the UPS) in order to have one common input. During the normal working conditions, when mains is available, the normal power flow goes through the rectifier, inverter and transformer to the output and supplies the critical load. This working-mode is called double-conversion mode. In double-conversion mode, the battery is constantly kept at full charge (floating). During long or short power outages (mains at input side is not available) the battery feeds the inverter which, supplies power the critical load trough the transformer with no interruption. 2

3 The static bypass path acts as emergency path, coming in the game when there is a problem on the double-conversion path such as overload, over temperature or short circuit at the output side of the UPS. In some cases, the static bypass path becomes the primary power path. This working mode is commonly known as eco-mode; despite the fact that each UPS manufacturer is implementing small differences and is calling it differently, it is practically identical for all: the load is still protected in case of power outages but there is an interruption of typically 5-8ms during which the UPS has to transfer from static bypass to inverter. Finally, there is a maintenance bypass switch, can be UPS integrated or external when having a parallel UPS system. Its function is to bypass the unit connecting input to output directly and thanks to the other switches the unit can be isolated and serviced. Figure 1: single line diagram of a transformer-based UPS Transformer-free UPS The working principle of transformer-free UPS is the same as for the transformer-based, with the main difference that there is no transformer integrated; the newer IGBT technology allows working with higher voltages, hence there is no need of stepping up the voltage after the inverter. This has enormous effect on the energy efficiency improving it from 90% to 96%, which is industry-standard today. Furthermore, as it is easy to imagine transformer-free UPS are much lighter and occupy less footprint; less space means less investment cost and less weight means easier handling, which also ends up with a cost difference for the installation work. 3

4 Figure 2: single line diagram of a transformer-free UPS Also, because of working with higher voltage, an additional converter between the DC bus and the battery was introduced. It allows to keeping precise control over the batteries constantly and providing clean DC voltage, with no ripple, which maximizes the battery lifetime. But the advantages do not stop here. The total harmonic distortion gets dramatically low and the input power factor is resistive thanks to the active control of the input currents. This means that the devices which are upstream the of the UPS (e.g. generators) must not be oversized by a factor 1.5 or even more as it usually is/was with transformerbased UPS. Finally, some other differences can be identified at the output stage: the output impedance and the dynamic response in case of unbalanced load are better on the transformer-free UPS thanks to the direct control of the output sinus and the fact that each phase is controlled independently. On the contrary, the output short circuit capability on inverter results to be stronger on the transformer-based UPS. The same cannot be confirmed for the short circuit capability on bypass: the two designs achieve the same levels having similar if not equal circuitry for the bypass. Bear in mind that the fact that designers take into account also the short circuit of the inverter is because of power-supply design rules. In reality, it is more likely that a short circuit happens when mains is available which means that the short circuit gets cleared by the bypass hence the capability on the bypass is what counts. 4

5 Major technical specifications differences (typical) Let us summarize the major technical differences between the two topologies. Table 1: summary of the major technical differences between the two topologies. # transformer-based transformer-free 1 Efficiency on double conversion mode 90-92% 95-96% 2 Efficiency on eco-mode 99% 99% 3 Current Total Harmonic Distortion (THDi) 30% (6-pluse thyristor-based rectifier) 12% (12-pluse thyristor-based rectifier) 3-4% (IGBT rectifier) 3-4% 4 Input Power Factor low on partial load at full and partial load 5 AC ripple on Battery without battery charger more than 5% with battery charger 0.2% 0.2% 6 Allowed number of battery blocks in series (12V) fix (typically 40) variable from 30 to 50 7 Output impedance high (worse) low (better) 8 Output fault clearing capability on inverter up to 5 x In (better) up to 3 x In (worse) 9 Output fault clearing capability on bypass up to 10 x In up to 10 x In 10 Dynamic response poor, unbalanced loads affect output voltages ideal, direct control of the output sinus, each phase is controlled independently, thus unbalanced loads are not affecting the output voltages 11 Weight (one 500kVA unit) tons 1 ton 12 Footprint (one 500kVA unit) sqm sqm Major differences for the customers (effect on the customer benefits) Table 2: summary of the major differences between the two topologies for the customers. # transformer-based transformer-free 1 Investment cost 2 Operational cost $$$ due to higher UPS cost, higher installation cost (oversize of system upstream the UPS) and larger footprint. $$$ due to lower efficiency means higher energy costs for both UPS and cooling. $$ $ Higher efficiency reduced power losses and less cooling. During many years, the saving is significant. 3 Environmental impact for producing the product and transport to final location Higher than transformer-free due to more components (transformer) and bigger mechanical size for the unit Lower than transformer-based thanks to the same arguments 4 Environmental impact for operating the product Lower efficiency means higher power losses and more energy needed for cooling. Higher efficiency means less power losses and less energy needed for cooling 5

6 5 Battery life (Lead-Acid) may be dramatically reduced due to AC ripple up to 12 years From the above comparisons, it clearly results that the transformer-free UPS design has more advantages on his part and those that count today. This is somewhat obvious, otherwise we would not see that the IGBT based and transformer-free UPS design market has replaced the old designs. However, it is correct to reminding that both designs provide the fundamental functionalities of a doubleconversion UPS and both designs maintain the key characteristics such as availability, reliability and the expected life-time of the UPS is equal for the two. The non-topics for having a transformer-based UPS In addition to what was just explained, some people in the industry are still convinced that a transformer in a UPS has other functions. Isolate input from output Sometimes it is required that the UPS input and/or output are completely isolated from the rest of the electrical installation. At first, a transformer-based UPS seems to be ideal solution for that, having the isolation transformer inbuilt at the output of the rectifier and before the output terminals. Is this really so? In reality the isolation isn t there, looking back at Figure 1, we immediately see that when the UPS is in static-bypass mode or maintenance bypass mode the isolation between input and output is not there. Moreover, the Neutral-line is always not isolated, also in double-conversion mode. As the figure 3 shows, Neutral-line goes through from input to output without isolation. This is valid for virtually all UPS systems. Figure 3: 4-wire diagram of a transformer-based UPS. In order to have a complete and true isolation from the input of the UPS to the output, the best way would be to add external isolation transformers as showed in the example in Figure 4. It becomes clear that when there is the need of isolate input from output, the best choice results to 6

7 be a transformer-less UPS (higher efficiency, smaller footprint and lower weight) plus external isolation transformers. Figure 4: 4-wire diagram of a transformer-based UPS. Better filtering As the UPS itself is a device which works with switching frequency and PWM (rectification and creation of the output sinus by means of switching ON and OFF semiconductors), there are unwelcome phenomena, like harmonic distortion, which need to be filtered out and the input Power Factor. The main indicators of the quality of the power are: 1. Total Harmonic Distortion of the input current (THDi) 2. Total Harmonic Distortion of the output voltage (THDU) 3. Input Power Factor (input PF) Now, the full explanation and theory related to these three UPS characteristics could be topic for a separate paper. Regarding our topic of transformer-based vs transformer-less UPS design it is important to understand whether there are significant differences between the two designs, for what concerns the quality of the power. 1. THDi, the lower, the better. As already summarized in Table 1 at item #3, the THDi depends on the topology of the rectifier. If the rectifier is IGBT based and the UPS has proper passive LC filtering, then the THDi will be around 3-4%, regardless if the UPS is transformer-based or not. However, it is worth mentioning that old thyristor-based UPS, which generate high THDi, are also transformer-based and are still present in the portfolio of some manufacturers. In other words, choosing a transformer-less UPS means excluding automatically thyristor based rectifier UPS. 2. THDU, like the THDi, the lower, the better. Let s analyze the transformer-less design first; as the switching frequency of the transformer-less UPSs is usually around or above 15 khz, the output voltage includes few low-order harmonics (the low-order are the ones 7

8 with higher amplitude, hence the one generating more total harmonic content) and the passive LC filtering is more than enough to keep THDU low. 2% is today the TDHU value of transformer-less UPS and such value is more than OK, meaning that there is no effect on the load side. On the contrary, transformer based UPS are generating more low-order harmonic content as their switching frequency ranges from 1 khz to 3kHz; so the transformer is used as a filter for those low-order harmonics and the THDU at the output results to be also around 2%. As a conclusion, we can say that the output THDU of UPS is today practically equal among the most manufacturers and it isn t worth to have an output transformer (maybe external) whose sole purpose is to lower the THDU further down, if the UPS already guarantees 2%. 3. Input PF, the closer to 1.0 (restive) the better. Like for the THDi, the responsible device for the input Power Factor is the rectifier (and the input filters). As already mentioned in Table 1 at item #4, on the transformer-based UPS the PF typically varies with the amount of load (aggravates with the decreasing of the load) due to passive filtering numb rectifiers (without active PF correction). As UPS systems are practically never fully loaded, but typically loaded between 25% and 75%, the input PF results to be capacitive and this is a big disadvantage as anyone in the UPS industry knows. transformer-less UPS typically have rectifiers with active PF correction, thus have the PF very close to resistive (0.99) at all load levels. Fault tolerant Some people in the market are still claiming that when having a transformer in the UPS it will be better able to handle internal and external faults or short circuits. This may have been true two decades ago, but today s this is not the case anymore. Transformerless UPSs have internal circuitry, fast fusing and fast digital controls that allow the machine to effectively handle internal shorts such as e.g. a short on the inverter bridge. Like many UPS manufacturers, ABB has on every UPS series the necessary circuitry and fuses to protect the power converters including the battery charger. 8

9 Conclusions When designing medium to large power supply systems, there are numerous factors to be taken into account, which can be grouped into the following categories: safety, availability, flexibility, impact on environment and cost. Now, if in theory, all is nice and easy and we want to have all the above mentioned categories matching 100%, in practical life the best solution is the best compromise. This is valid for all applications. It may be type of application, or the criticality of the business connected to that power supply, or the business-model of the end-user, etc. that determine which is the best compromise for each installation. Now that the pro and cons of the two UPS designs have been explained in this paper, we can conclude that the use of transformer-free UPS allow to achieve the best compromise by fulfilling by far the majority of the power supply design factors. For the customers it means that the modern transformer-free UPS design matches today s customer requirements much more widely than the transformer-based. 9

GESS Industrial UPS System. Overview

GESS Industrial UPS System. Overview GESS Industrial UPS System Overview Industrial UPS System Rectifier with Isolation Transformer Inverter with Isolation Transformer By-pass line Voltage Stabilizer with Isolation Transformer > Individual

More information

Strategies for design 600V large modular UPS for critical power applications

Strategies for design 600V large modular UPS for critical power applications White Paper Markets Served Data centers Strategies for design 600V large modular UPS for critical power applications Executive summary Today s transformerless UPS systems are significantly smaller and

More information

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing. 1.0 Scope This document describes the specification for Toshiba 1000 Series On-Line Uninterruptible Power System (UPS). The UPS will supply a computer grade AC output sine wave which is unaffected by the

More information

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS MERLIN GERIN KNOW HOW THM filtering and the management of harmonics upstream of UPS THM filtering and the control of harmonics upstream of UPSs Authors : S. BERNARD - J.N. FIORINA - B GROS - G. TROCHAIN

More information

B9000 FXS kVA B9600 FXS kVA

B9000 FXS kVA B9600 FXS kVA OF CONTINUOUS SERVICE YEARS WARRANTY B9000 FXS 60-300kVA B9600 FXS 400-800kVA BORRI B9000 FXS B9600 FXS With disturbances to the electrical supply being one of the major causes of IT downtime, the UPS

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION 1.1 Introduction Power semiconductor devices constitute the heart of the modern power electronics, and are being extensively used in power electronic converters in the form of a

More information

SHUNT ACTIVE POWER FILTER

SHUNT ACTIVE POWER FILTER 75 CHAPTER 4 SHUNT ACTIVE POWER FILTER Abstract A synchronous logic based Phase angle control method pulse width modulation (PWM) algorithm is proposed for three phase Shunt Active Power Filter (SAPF)

More information

Est Static Frequency Converter. SFX 10kVA - 10MVA

Est Static Frequency Converter. SFX 10kVA - 10MVA Est.1968 Static Frequency Converter SFX 10kVA - 10MVA Static Frequency Converter SFX 10kVA - 10MVA A Concept Thycon Static Frequency Converters (SFX) convert supply frequency to load requirement frequency.

More information

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis By ALL-TEST Pro, LLC & EMA Inc. Industry s use of Motor Drives for AC motors continues to grow and the Pulse-Width

More information

High Voltage DC Transmission 2

High Voltage DC Transmission 2 High Voltage DC Transmission 2 1.0 Introduction Interconnecting HVDC within an AC system requires conversion from AC to DC and inversion from DC to AC. We refer to the circuits which provide conversion

More information

MGETM EPSTM /625/750/800 kva. Three phase UPS

MGETM EPSTM /625/750/800 kva. Three phase UPS MGETM EPSTM 8000 Three phase UPS 555/625/750/800 kva > Performance 3 phase Power Protection with high active power density and adaptability to meet the unique requirements of very large datacenters, buildings

More information

The Turtle, The Hare and UPS Performance (This Time the Rabbit Wins!)

The Turtle, The Hare and UPS Performance (This Time the Rabbit Wins!) The Turtle, The Hare and UPS Performance (This Time the Rabbit Wins!) By Thomas E. Wilson, P.E. Wilson Engineered Systems, Inc. 11497 Columbia Park Drive West, Suite #2 Jacksonville, FL 32258 UPS systems

More information

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN UNINTERRUPTIBLE POWER SYSTEMS PF >0.98 G8000MM Series 100 to 750 KVA UPS IGBT DESIGN 94% Efficiency Main Features State-of-the-Art Modular Design Provides Maximum Flexibility The Toshiba G8000MM Uninterruptible

More information

Switches And Antiparallel Diodes

Switches And Antiparallel Diodes H-bridge Inverter Circuit With Transistor Switches And Antiparallel Diodes In these H-bridges we have implemented MOSFET transistor for switching. sub-block contains an ideal IGBT, Gto or MOSFET and antiparallel

More information

Harmonic Filtering in Variable Speed Drives

Harmonic Filtering in Variable Speed Drives Harmonic Filtering in Variable Speed Drives Luca Dalessandro, Xiaoya Tan, Andrzej Pietkiewicz, Martin Wüthrich, Norbert Häberle Schaffner EMV AG, Nordstrasse 11, 4542 Luterbach, Switzerland luca.dalessandro@schaffner.com

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

A New Concept of Power Quality Monitoring

A New Concept of Power Quality Monitoring A New Concept of Power Quality Monitoring Victor Anunciada 1, Hugo Ribeiro 2 1 Instituto de Telecomunicações, Instituto Superior Técnico, Lisboa, Portugal, avaa@lx.it.pt 2 Instituto de Telecomunicações,

More information

TECHNICAL DATA SHEET B9600FXS kva

TECHNICAL DATA SHEET B9600FXS kva GENERAL INFORMATION TECHNICAL DATA SHEET B9600FXS 400-500-600-800 kva UPS Type ON LINE - Double Conversion Nominal output power (Cos 0.9) kva 400 500 600 800 Nominal output power (Cos 1.0) kw 360 450 540

More information

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India Abstract: The objective of this research is to develop a novel voltage control scheme that

More information

A NEW SINGLE STAGE THREE LEVEL ISOLATED PFC CONVERTER FOR LOW POWER APPLICATIONS

A NEW SINGLE STAGE THREE LEVEL ISOLATED PFC CONVERTER FOR LOW POWER APPLICATIONS A NEW SINGLE STAGE THREE LEVEL ISOLATED PFC CONVERTER FOR LOW POWER APPLICATIONS S.R.Venupriya 1, Nithyananthan.K 2, Ranjidharan.G 3, Santhosh.M 4,Sathiyadevan.A 5 1 Assistant professor, 2,3,4,5 Students

More information

Open-Delta Systems Affect Variable Frequency Drives

Open-Delta Systems Affect Variable Frequency Drives Open-Delta Systems Affect Variable Frequency Drives To avoid premature drive failure, proper precautions must be taken when installing VFDs on open-delta supplies. Written by: Dan Peters, Yaskawa America,

More information

Improving Passive Filter Compensation Performance With Active Techniques

Improving Passive Filter Compensation Performance With Active Techniques IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 1, FEBRUARY 2003 161 Improving Passive Filter Compensation Performance With Active Techniques Darwin Rivas, Luis Morán, Senior Member, IEEE, Juan

More information

How adjustable speed drives affect power distribution

How adjustable speed drives affect power distribution How adjustable speed drives affect power distribution Application Note Adjustable speed drives (ASDs) can be both a source and a victim of poor power quality. ASDs as victim loads Although ASDs are usually

More information

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter 1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560

More information

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS Copyright Mitsubishi Electric Power Products TABLE OF CONTENTS 1. SCOPE... 1 1.1 The System... 1 2. SYSTEM DESCRIPTION... 1 2.1 Components... 1 2.2 Modes

More information

Module 4. AC to AC Voltage Converters. Version 2 EE IIT, Kharagpur 1

Module 4. AC to AC Voltage Converters. Version 2 EE IIT, Kharagpur 1 Module 4 AC to AC Voltage Converters Version EE IIT, Kharagpur 1 Lesson 9 Introduction to Cycloconverters Version EE IIT, Kharagpur Instructional Objectives Study of the following: The cyclo-converter

More information

AN003. Basic Terms Used for DC Power Supplies. Elaborated by: Marco Geri (R&D Manager - NEXTYS SA.)

AN003. Basic Terms Used for DC Power Supplies. Elaborated by: Marco Geri (R&D Manager - NEXTYS SA.) AN003 Elaborated by: Marco Geri (R&D Manager - NEXTYS SA.) Rev.1.0 Page 1/5 1 Introduction DC (Direct Current) power supplies are used in various applications related to automation, telecom, industry,

More information

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation Slide 1 Excerpt from the BoA BoA: Book of Acronyms MSC/MSR: Mechanically

More information

Development of a Single-Phase PWM AC Controller

Development of a Single-Phase PWM AC Controller Pertanika J. Sci. & Technol. 16 (2): 119-127 (2008) ISSN: 0128-7680 Universiti Putra Malaysia Press Development of a Single-Phase PWM AC Controller S.M. Bashi*, N.F. Mailah and W.B. Cheng Department of

More information

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS Chapter 1 : Power Electronics Devices, Drivers, Applications, and Passive theinnatdunvilla.com - Google D Download Power Electronics: Devices, Drivers and Applications By B.W. Williams - Provides a wide

More information

These true online inverters integrate pulse width modulation (PWM) control combined with high frequency IGBT power transistors.

These true online inverters integrate pulse width modulation (PWM) control combined with high frequency IGBT power transistors. Three-phase Industrial Inverter OND4 SERIES The new OND4 SERIES inverter provides safe, pure sine wave, single-phase or three-phase reliable power to critical control equipment. These inverters are of

More information

A New Multilevel Inverter Topology with Reduced Number of Power Switches

A New Multilevel Inverter Topology with Reduced Number of Power Switches A New Multilevel Inverter Topology with Reduced Number of Power Switches L. M. A.Beigi 1, N. A. Azli 2, F. Khosravi 3, E. Najafi 4, and A. Kaykhosravi 5 Faculty of Electrical Engineering, Universiti Teknologi

More information

POWER- SWITCHING CONVERTERS Medium and High Power

POWER- SWITCHING CONVERTERS Medium and High Power POWER- SWITCHING CONVERTERS Medium and High Power By Dorin O. Neacsu Taylor &. Francis Taylor & Francis Group Boca Raton London New York CRC is an imprint of the Taylor & Francis Group, an informa business

More information

Introduction to Rectifiers and their Performance Parameters

Introduction to Rectifiers and their Performance Parameters Electrical Engineering Division Page 1 of 10 Rectification is the process of conversion of alternating input voltage to direct output voltage. Rectifier is a circuit that convert AC voltage to a DC voltage

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SG Series 80 100 120 kva 400 Vac CE Series 0 Date of issue: 01.11.2007 SGSE_080_UPS_GE_01a SGSE_100-120_UPS_GE_01a

More information

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors. Industrial Inverter The Gentec inverter systems, OND2 SERIES, provide safe, pure sine wave, reliable power to critical control equipment. These inverters are online type, usually the load is fed by the

More information

Est Static Frequency Converter. SFX 10kVA - 10MVA

Est Static Frequency Converter. SFX 10kVA - 10MVA Est.1968 Static Converter SFX 10kVA - 10MVA Concept Thycon Static Converters (SFX) convert supply frequency to load requirement frequency. Typical applications are 50 to 60Hz conversion for naval and 50

More information

Caution - leakage currents! Leakage currents in fault-current protected environments

Caution - leakage currents! Leakage currents in fault-current protected environments Caution - leakage currents! Leakage currents in fault-current protected environments Herbert Blum Product Manager EMC > General situation > Leakage current vs. fault current > Leakage currents from frequency

More information

Introduction to HVDC VSC HVDC

Introduction to HVDC VSC HVDC Introduction to HVDC VSC HVDC Dr Radnya A Mukhedkar Group Leader, Senior Principal Engineer System Design GRID August 2010 The Voltage Sourced Converter Single Phase Alternating Voltage Output Steady DC

More information

INVESTIGATION OF GATE DRIVERS FOR SNUBBERLESS OVERVOLTAGE SUPPRESSION OF POWER IGBTS

INVESTIGATION OF GATE DRIVERS FOR SNUBBERLESS OVERVOLTAGE SUPPRESSION OF POWER IGBTS INVESTIGATION OF GATE DRIVERS FOR SNUBBERLESS OVERVOLTAGE SUPPRESSION OF POWER IGBTS Alvis Sokolovs, Iļja Galkins Riga Technical University, Department of Power and Electrical Engineering Kronvalda blvd.

More information

A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems

A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems K Siva Shankar, J SambasivaRao Abstract- Power converters for mobile devices and consumer electronics have become extremely lightweight

More information

CHAPTER 4 4-PHASE INTERLEAVED BOOST CONVERTER FOR RIPPLE REDUCTION IN THE HPS

CHAPTER 4 4-PHASE INTERLEAVED BOOST CONVERTER FOR RIPPLE REDUCTION IN THE HPS 71 CHAPTER 4 4-PHASE INTERLEAVED BOOST CONVERTER FOR RIPPLE REDUCTION IN THE HPS 4.1 INTROUCTION The power level of a power electronic converter is limited due to several factors. An increase in current

More information

Liebert Hipulse-U. Fully Digital Dual DSP Controlled Transformer Based UPS

Liebert Hipulse-U. Fully Digital Dual DSP Controlled Transformer Based UPS Liebert Hipulse-U Fully Digital Dual DSP Controlled Transformer Based UPS Addressing a Variety of Needs The Liebert Hipulse-U offers a reliable, scalable and user-friendly solution to ensure availability

More information

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL Saravanan.R 1, Hariharan.M 2 1 PG Scholar, Department OF ECE, 2 PG Scholar, Department of ECE 1, 2 Sri Krishna College

More information

Operation of a Three-Phase PWM Rectifier/Inverter

Operation of a Three-Phase PWM Rectifier/Inverter Exercise 1 Operation of a Three-Phase PWM Rectifier/Inverter EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the block diagram of the three-phase PWM rectifier/inverter.

More information

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION 1 Arsha.S.Chandran, 2 Priya Lenin 1 PG Scholar, 2 Assistant Professor 1 Electrical & Electronics Engineering 1 Mohandas College of Engineering

More information

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY Journal of Electrical Engineering & Technology (JEET) (JEET) ISSN 2347-422X (Print), ISSN JEET I A E M E ISSN 2347-422X (Print) ISSN 2347-4238 (Online) Volume

More information

W o r l d C l a s s P o w e r S o l u t i o n s Internal power supply UPS mains operation UPS battery operation Bypass operation Parallel operation Manual bypass Overload Inverter failure Mains failure

More information

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs Mr. P. Biswas, ABB ABSTRACT The Indian Railways employ single phase 25 kv Traction sub-station (TSS) for supplying power

More information

Vacon Baltic Days Tallinn, Estonia

Vacon Baltic Days Tallinn, Estonia Vacon Baltic Days 22.-23.9.2011 Tallinn, Estonia Vacon Technology Yrjö Karvonen Technical Account Manager Frequency converter Why to use Applications Energy saving Easy to control (ma, V, digital I/O,

More information

Power quality as a reliability problem for electronic equipment

Power quality as a reliability problem for electronic equipment Power quality as a reliability problem for electronic equipment A. Victor A. Anunciada1,3, Hugo Ribeiro2,3 1 Department of Electrical and Computer Engineering, Instituto Superior Técnico, Universidade

More information

IMPORTANCE OF VSC IN HVDC

IMPORTANCE OF VSC IN HVDC IMPORTANCE OF VSC IN HVDC Snigdha Sharma (Electrical Department, SIT, Meerut) ABSTRACT The demand of electrical energy has been increasing day by day. To meet these high demands, reliable and stable transmission

More information

Uninterruptible Power System (UPS) 20 to 320 kva

Uninterruptible Power System (UPS) 20 to 320 kva Large-capacity Uninterruptible Power System (UPS) 20 to 320 kva All IGBT type UPS 7000F Series REC 82-5 Fuji's UPS for today's computerized On-line support for all applications Data communication devices

More information

High Frequency Inverter Design Fundamentals. Chandrashekar DR April 19, 2010

High Frequency Inverter Design Fundamentals. Chandrashekar DR April 19, 2010 High Frequency Inverter Design Fundamentals Chandrashekar DR April 19, 2010 Agenda By the End of this session we will Understand different kinds of back up systems Discuss building blocks of basic inverter

More information

Technical Data Sheet. Uninterruptible Power Supply On-line VH Series UPS. Critical Power UL / 208V

Technical Data Sheet. Uninterruptible Power Supply On-line VH Series UPS. Critical Power UL / 208V Technical Data Sheet Uninterruptible Power Supply On-line VH Series UPS 2000-3000 UL / 208V GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850

More information

A Combined Buck and Boost Converter for Single-Phase Power-Factor Correction

A Combined Buck and Boost Converter for Single-Phase Power-Factor Correction 2005 IBM Power and Cooling Technology Symposium A Combined Buck and Boost Converter for Single-Phase Power-Factor Correction Kevin Covi Introduction The AC/DC converters in IBM s high-end servers connect

More information

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Available online at   ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015 Available online at www.sciencedirect.com ScienceDirect Procedia Technology 21 (2015 ) 310 316 SMART GRID Technologies, August 6-8, 2015 A Zig-Zag Transformer and Three-leg VSC based DSTATCOM for a Diesel

More information

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL 14 CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL 2.1 INTRODUCTION Power electronics devices have many advantages over the traditional power devices in many aspects such as converting

More information

Comparison of Hybrid Asymmetric and Conventional Multilevel Inverters for Medium Voltage Drive Applications

Comparison of Hybrid Asymmetric and Conventional Multilevel Inverters for Medium Voltage Drive Applications Comparison of Hybrid Asymmetric and Conventional Multilevel Inverters for Medium Voltage Drive Applications Master of Science Thesis in the Master s programme Electric Power Engineering AMIR SAJJAD BAHMAN

More information

Literature Review. Chapter 2

Literature Review. Chapter 2 Chapter 2 Literature Review Research has been carried out in two ways one is on the track of an AC-AC converter and other is on track of an AC-DC converter. Researchers have worked in AC-AC conversion

More information

Introduction to HVDC in GB. Ian Cowan Simulation Engineer 12 March 2018

Introduction to HVDC in GB. Ian Cowan Simulation Engineer 12 March 2018 Introduction to HVDC in GB Ian Cowan Simulation Engineer 12 March 2018 Contents 1) History of Electricity Networks 2) Overview of HVDC 3) Existing Schemes 4) Future Schemes 5) Regulation and Ownership

More information

Improved H6 Transformerless Inverter for PV Grid tied power system

Improved H6 Transformerless Inverter for PV Grid tied power system Improved H6 Transformerless Inverter for PV Grid tied power system Madhuri N.Kshirsagar madhuri.n.kshirsagar@gmail.com Pragati K. Sharma pragatisharma91@gmail.com Shweta A. Deshmukh shweta4155@gmail.com

More information

APPLICATION GUIDE. Harmonics in HVAC applications

APPLICATION GUIDE. Harmonics in HVAC applications APPLICATION GUIDE Harmonics in HVAC applications Table of contents 4 Harmonics in general and why we should care 4 Introduction 4 Basics of harmonics 5 Causes of harmonic distortion 5 Problems caused

More information

A Half Bridge Inverter with Ultra-Fast IGBT Module Modeling and Experimentation

A Half Bridge Inverter with Ultra-Fast IGBT Module Modeling and Experimentation ELECTRONICS, VOL. 13, NO. 2, DECEMBER 29 51 A Half Bridge Inverter with Ultra-Fast IGBT Module Modeling and Experimentation Dinko Vukadinović, Ljubomir Kulišić, and Mateo Bašić Abstract This paper presents

More information

Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications. Series 7400 M

Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications. Series 7400 M Power Protection for Business Critical Continuity Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications Compact Three-phase UPS with Optimum Load Performance And

More information

Preventing transformer saturation in static transfer switches A Real Time Flux Control Method

Preventing transformer saturation in static transfer switches A Real Time Flux Control Method W H I T E PA P E R Preventing transformer saturation in static transfer switches A Real Time Flux Control Method TM 2 SUPERSWITCH 4 WITH REAL TIME FLUX CONTROL TM Preventing transformer saturation in static

More information

Floating Output DC-DC Converter Using Single Winding Reactor and Its Applications

Floating Output DC-DC Converter Using Single Winding Reactor and Its Applications 1 / 5 SANYO DENKI Technical Report No.6 Nov. 1998 General Theses Floating Output DC-DC Converter Using Single Winding Reactor and Its Applications Hirohisa Yamazaki 1. Introduction Networking based on

More information

M.Tech in Industrial Electronics, SJCE, Mysore, 2 Associate Professor, Dept. of ECE, SJCE, Mysore

M.Tech in Industrial Electronics, SJCE, Mysore, 2 Associate Professor, Dept. of ECE, SJCE, Mysore Implementation of Five Level Buck Converter for High Voltage Application Manu.N.R 1, V.Nattarasu 2 1 M.Tech in Industrial Electronics, SJCE, Mysore, 2 Associate Professor, Dept. of ECE, SJCE, Mysore Abstract-

More information

S11 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3- phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC. 1.1 References A. National

More information

Large-Capacity, High-Efficiency 3-Level UPS for North America 7000HX-T3U

Large-Capacity, High-Efficiency 3-Level UPS for North America 7000HX-T3U Large-Capacity, High-Efficiency 3-Level for North America 7000HX-T3U KAWASAKI, Daisuke HAMADA, Ippei SATO, Atsushi ABSTRACT Due to the development of information and communications systems in the information

More information

VF-nC1 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba VF-nC1 AC Variable Frequency Drives, 6 pulse for 100V single-phase 0.1 to 0.75kW, 200V single-phase 0.2 to 2.2kW and 200V threephase 0.1

More information

NJWA - Harmonics and Drives Proper System Design

NJWA - Harmonics and Drives Proper System Design Session Goals Larry Stanley, Sr. Regional Business Development Engineer, Water Segment Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia NJWA - Harmonics and Drives

More information

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives For your business and technology editors Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives The use of AC induction motors is essential for industry and utilities. AC induction

More information

Nonconventional Technologies Review no. 4/2009

Nonconventional Technologies Review no. 4/2009 ACTIVE POWER FILTER CONNECTED TO A PHOTOVOLTAIC ARRAY Daniel ALBU Department of Electronics, University of Oradea, Faculty of Electrical Engineering and Information Technology Abstract: The existence of

More information

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review S.N. Bhalerao 1, P.J. Bhakre, C.O.Reddy 3 1 Student, Department of Electrical Engineering, MSS Collage Of Engineering,

More information

UNINTERRUPTIBLE POWER SUPPLY SINGLE MODULE SYSTEM SPECIFICATIONS MODEL 9800AE

UNINTERRUPTIBLE POWER SUPPLY SINGLE MODULE SYSTEM SPECIFICATIONS MODEL 9800AE UNINTERRUPTIBLE POWER SUPPLY MODEL 9800AE SINGLE MODULE SYSTEM SPECIFICATIONS In no event shall MEPPI be liable for the accuracy, completeness or usefulness of the following specifications or for any modification(s)

More information

Harmonic Reduction using Thyristor 12-Pulse Converters

Harmonic Reduction using Thyristor 12-Pulse Converters Exercise 5 Harmonic Reduction using Thyristor 12-Pulse Converters EXERCISE OBJECTIVE When you have completed this exercise, you will understand what a thyristor 12- pulse converter is and how it operates.

More information

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM 64 CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM 4.1 INTRODUCTION Power electronic devices contribute an important part of harmonics in all kind of applications, such as power rectifiers, thyristor converters

More information

Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine

Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine T. Neumann, C. Feltes, I. Erlich University Duisburg-Essen Institute of Electrical Power Systems Bismarckstr. 81,

More information

E3 Adjustable Speed Drive Engineering Specification

E3 Adjustable Speed Drive Engineering Specification E3 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba E3 AC Variable Frequency Drives, 6 pulse for 230V and 460V. 1.1 References A. National

More information

Power Factor Correction of Three Phase Induction Motor

Power Factor Correction of Three Phase Induction Motor IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 08 February 2017 ISSN (online): 2349-784X Power Factor Correction of Three Phase Induction Motor Shashikanth. Matapathi

More information

Using the EVM: PFC Design Tips and Techniques

Using the EVM: PFC Design Tips and Techniques PFC Design Tips and Techniques Features: Bare die attach with epoxy Gold wire bondable Integral precision resistors Reduced size and weight High temperature operation Solder ready surfaces for flip chips

More information

The Quest for High Power Density

The Quest for High Power Density The Quest for High Power Density Welcome to the GaN Era Power Conversion Technology Drivers Key design objectives across all applications: High power density High efficiency High reliability Low cost 2

More information

Development of Multilevel Inverters for Control Applications

Development of Multilevel Inverters for Control Applications International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Volume: 3 Issue: 1 Jan-216 www.irjet.net p-issn: 2395-72 Development of Multilevel Inverters for Control Applications

More information

Reduce harmonics in HVAC&R inverters through C-Less technology

Reduce harmonics in HVAC&R inverters through C-Less technology Reduce harmonics in HVAC&R inverters through C-Less technology Karim Lamrabtine Global Product Manager VSD 14-15 SEPTEMBER 2011, MUNICH Agenda www.infoplc.net What are Harmonics? Standards Compliance How

More information

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM Liebert AF2 Next Generation Active Harmonic Filter Power Protection for Business-Critical Continuity TM LIEBERT AF2 You Need To Be Aware Of Harmonics During the last few years industries has witnessed

More information

ELEC387 Power electronics

ELEC387 Power electronics ELEC387 Power electronics Jonathan Goldwasser 1 Power electronics systems pp.3 15 Main task: process and control flow of electric energy by supplying voltage and current in a form that is optimally suited

More information

A Comparative Study of Different Topologies of Multilevel Inverters

A Comparative Study of Different Topologies of Multilevel Inverters A Comparative Study of Different Topologies of Multilevel Inverters Jainy Bhatnagar 1, Vikramaditya Dave 2 1 Department of Electrical Engineering, CTAE (India) 2 Department of Electrical Engineering, CTAE

More information

VFDs and Harmonics in HVAC Applications

VFDs and Harmonics in HVAC Applications VFDs and Harmonics in HVAC Applications Larry Gardner Product Marketing Manager Yaskawa America, Inc. Jeff Grant Senior Sales Engineer LONG Building Technologies October 20, 2016 2016 Yaskawa America,

More information

Comparative Study of Pulse Width Modulated and Phase Controlled Rectifiers

Comparative Study of Pulse Width Modulated and Phase Controlled Rectifiers Comparative Study of Pulse Width Modulated and Phase Controlled Rectifiers Dhruv Shah Naman Jadhav Keyur Mehta Setu Pankhaniya Abstract Fixed DC voltage is one of the very basic requirements of the electronics

More information

AGN 026 Harmonic Voltage Distortion

AGN 026 Harmonic Voltage Distortion Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 026 Harmonic Voltage Distortion Comment; The critical level of acceptable harmonic voltage distortion % is set

More information

ELG3336: Power Electronics Systems Objective To Realize and Design Various Power Supplies and Motor Drives!

ELG3336: Power Electronics Systems Objective To Realize and Design Various Power Supplies and Motor Drives! ELG3336: Power Electronics Systems Objective To Realize and Design arious Power Supplies and Motor Drives! Power electronics refers to control and conversion of electrical power by power semiconductor

More information

DC Link. Charge Controller/ DC-DC Converter. Gate Driver. Battery Cells. System Controller

DC Link. Charge Controller/ DC-DC Converter. Gate Driver. Battery Cells. System Controller Integrate Protection with Isolation In Home Renewable Energy Systems Whitepaper Home energy systems based on renewable sources such as solar and wind power are becoming more popular among consumers and

More information

Reducing Total Harmonic Distortion with Variable Frequency Drives

Reducing Total Harmonic Distortion with Variable Frequency Drives Reducing Total Harmonic Distortion with Variable Frequency Drives Low Harmonic Technology in Optidrive Eco Overview Overview Both AC line chokes and DC link chokes have historically been used with Variable

More information

Other Electronic Devices

Other Electronic Devices Other Electronic Devices 1 Contents Field-Effect Transistors(FETs) - JFETs - MOSFETs Insulate Gate Bipolar Transistors(IGBTs) H-bridge driver and PWM Silicon-Controlled Rectifiers(SCRs) TRIACs Device Selection

More information

CHOICE OF HIGH FREQUENCY INVERTERS AND SEMICONDUCTOR SWITCHES

CHOICE OF HIGH FREQUENCY INVERTERS AND SEMICONDUCTOR SWITCHES Chapter-3 CHOICE OF HIGH FREQUENCY INVERTERS AND SEMICONDUCTOR SWITCHES This chapter is based on the published articles, 1. Nitai Pal, Pradip Kumar Sadhu, Dola Sinha and Atanu Bandyopadhyay, Selection

More information