SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD GROUNDING RESISTANCE MEASUREMENTS AND IMPROVEMENT

Size: px
Start display at page:

Download "SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD GROUNDING RESISTANCE MEASUREMENTS AND IMPROVEMENT"

Transcription

1 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-III) REV-01 GROUNDING RESISTANCE MEASUREMENTS AND IMPROVEMENT This specification is property of SEC and subject to change or modification without any notice

2 TABLE OF CONTENTS Clause Description Page Number 1.0 General General Requirements Ground Resistance Measurement Ground Resistance design and Improvement 10 Figures 1 to Page 2 of 24

3 1.0 GENERAL: 1.1 Scope: This Grounding Standard describes factors affecting the ground resistance and the method of measuring ground resistance of Distribution System Network installations. It also describes the methods for improving soil resistivity. 1.2 Objective: Objectives of this Grounding Standard are as follows; a) To verify the adequacy of a new grounding system. b) Specify corrective steps, if any, for lowering the grounding resistance. c) Detect changes in the existing grounding system. 1.3 Factors Effecting Ground Resistance: The ground resistance at a given location is dependent on a number of factors, some of which are as follows: Soil Resistivity The ground resistance of a single rod type electrode is dependent upon the resistivity of the soil immediately surrounding the electrode. The soil which is far from the electrode has little effect on the ground resistance. The soil resistivity depends on the nature of soil, its chemical composition, amount of moisture in it and soil temperature. Compact soil has lower resistance than non compact soil of the same type. Soils having high content of salts like magnesium sulphate, copper sulphate, etc. have low resistivity. Increasing moisture content in the soil decrease the ground resistance considerably. However beyond approximately 20 % the moisture has less effect on reducing the ground resistance. Decreasing soil temperature increases ground resistance Arrangement of Grounding System As the ground rod resistance: R = ρl/a Where: ρ is the resistivity of material, L is the length of the rod, A is the area cross-section. Page 3 of 24

4 Therefore ground resistance can be reduced by: - Use of large diameter of rod - Use of longer rod length - Use of parallel rods - Use of Low Resistance Material ( LRM) LRM are described further in para 4. As such grounding resistance at a location can be reduced by proper arrangement of ground rods. Two (2) ground rods when spaced one meter apart and interconnected have combined ground resistance approximately 40 % more than the combined resistance of the same rods when spaced 4 meters apart. Depth of ground rod has a significant effect on the ground resistance. Usually the ground resistance decreases as the ground rod depth increases. This is so because the surface layers of soil have less moisture content than the deep layers. 2.0 GENERAL REQUIREMENTS FOR MEASUREMENT 2.1 Ensure that the equipment whose ground resistance is to be measured is deenergized. 2.2 Isolate the ground under test from all other grounds like cable screens, cable neutrals, primary neutrals, equipment body, etc. 2.3 The limits for the values of resistance for respective installations shall be as per SDCS-03 part-1 and part GROUND RESISTANCE MEASUREMENTS Below mentioned methods shall be adopted for measurement of grounding resistance: i) Measurement through Fall of Potential method. ii) iii) Measurement through Clamp On Meter Method. Measurement through Attached Rod Technique Method. Page 4 of 24

5 The description of each method is given as under: 3.1 Fall of Potential Method General The fall of potential method, also known as three terminal method, used to measure ground resistance is illustrated in Fig. 1. This method involves passing a current through the ground under test (G), and noting the influence of this current in terms of voltage between (G) and a test potential electrode (P). A test current electrode (C) is used to permit the passing of current into G, which for convenience, is measured at zero potential. The ground resistance is given as ratio of measured voltage to the imposed current. The null balance type earth tester shall normally be used for measuring ground resistance in this method. The instrument is supplied with 3 test leads and 2 electrodes (C & P) Measuring Procedures Ensure that the equipment whose ground resistance is to be measured is deenergized. During testing the test personnel must wear the required safety gears like shoes, hat, gloves, etc. Isolate the ground under test from all other grounds like cable screens, cable neutrals, primary neutrals, equipment body, etc. Refer to Fig. 1. Here C1, P1, P2, and C2 are four terminals on the instrument. i) Connect C1 and P1 together with a copper jumper wire. Connect C1 to the ground under test G. This connection should be as short as possible. ii) Drive current electrode C into the soil at a distance of approximately 30 meters from G. Let this distance be called as ' D'. Connect C to C2. iii) Drive potential electrode P at a distance of 0.62 D from G and along a straight line between G and C. Connect P to P2. iv) Obtain null point on the instrument and read off the corresponding resistance. v) Similarly take readings at a distance of (0.62D +2) meters and (0.62D -2) meters from G by driving P at these locations without changing the location of C. If the three reading are very close to each other then the resistance reading obtained at 0.62D is the true ground resistance and is so recorded. Page 5 of 24

6 In some cases the three readings mentioned above may not be close to each other. In such cases proceed to take more readings at equal increments of two meters on either side of 0.62D distance and plot a curve of distance versus resistance readings as indicated in Fig.2. Read the true ground resistance, in such cases, as the one corresponding to the flat portion of the curve and record it so, if the flat portion on the curve is not obtained, then move the current electrode 'C' further away from 'G' in a different direction and repeat the procedure stated above. If reasonable care is exercised in initial locations of C and P, then in general, it will not be necessary to plot the curve or move the location of C. The following precaution should be taken in choosing the location of C & P and installation of these electrodes. i) Locate C as for away from G as possible. ii) Locate C and P away from any known buried bare metallic objects. iii) G, C and P should be located in a fairly uniform soil. iv) C and P should be driven firmly into the soil so that there is no tendency for them to sway. The measured ground resistance and other related information shall be recorded. 3.2 Clamp On Meter method General This method is based on passing a current in the grounding conductor encircled by a current transformer using a voltage source with a constant value. The probe head or jaw of the clamp on meter is the key component in the current measurement. Typically grounded distribution system may be simulated by the basic circuit shown in Fig. 3. If the voltage (V) is applied to any measured grounding electrode with resistance Rx through a special current transformer, current (I) flows through the circuit thereby establishing the following equation: V/I= Rx + 1/ Σ n i=1 1/R Where usually Rx >> 1/ Σ n i=1 1/R Page 6 of 24

7 Therefore V/I= Rx is established. If I is detected and measured with V kept constant, the measured grounding electrode resistance Rx can be obtained. A signal is fed to a special transformer via a power amplifier from a constant voltage oscillator. The resulting current is then sensed by a detection CT. An active filter is used to dampen earth current at commercial frequency and high frequency noise. If case we clamp on the meter around any grounding electrode in a multi grounded system, the measured value of the electrode under test will be the resistance of that particular rod in series with the equivalent parallel resistance value that the rest of multi grounded system represents. As an example, if the number of grounding rods in a distribution feeder reaches hundred and if each has a resistance value of 25 ohms, in case we clamp around any electrode in the system, the measured value would be 25 ohms in series with the equivalent parallel resistance with negligible value say 0.25 ohms. The displayed value would be ohms (i.e V/I = 25 Ω Ω) Typical illustrations of measurement of the ground resistance for a pole, transformer and service box is given in Figures 4 to 6. For measurement, select the current range 'A'. Clamp on the meter to the ground conductor and measure the ground current. Note that if ground current is above 5 Amp or noise exceeds 50 V, grounding resistance measurements shall not be possible. Note the location for maintenance and move to another location for measurement. After noting the ground current, select the ground resistance range and measure the resistance directly. The reading measured as such indicates not just the resistance of the rod itself but of the connected system neutral and all bonded connections between the neutral and the rod Attached Rod Technique Method Fall-of-Potential testing is extremely reliable, highly accurate, conforms to IEEE 81 and gives the operator complete control over the set-up. However it is exceedingly time consuming and labor intensive and requires that the individual grounding electrodes be disconnected from the system. Clamp-on testing is quick and easy but has many limitations. This method requires a good return path, is susceptible to noise, has reduced accuracies and can not be used on isolated grounds. It is not applicable for installation checks or commissioning new checks or commissioning new sites and has no built in proof. Page 7 of 24

8 The Attached Rod technique (ART) provides some of the advantages on clamp-on testing (not having to disconnect the ground electrode) while remaining true to the theory and methodology of fall-of-potential testing. To understand the method, it is necessary to understand the theory and math behind it. In theory a fall of potential measurement could be made without disconnecting the ground electrode if additional measurements were made with an earth leakage clamp meter (milliamp meter). Figures 7 and 8 show the three measurements that would be made. The first step is to measure the resistance (R T ) of the entire system using a typical fall-of-potential configuration. In this example, the reading for R T is 1.9 Ω. Step two involves measuring the total current (I T ) being injected into the system from C1.From this example, I T is 9.00 ma. The next step is to measure the amount of current (Iu) following to the service. In this case Iu is 5.00 ma. With these measurements the voltage drop from the selected volume of soil to the point of P2 can be determined as follows: V = I T x R T V = A x 1.9 Ω V = V The current through the ground electrode (I G ) can also be determined. I G = I T Iu I G = 9.00 ma-5.00 ma I G = 4.00 ma Using the voltage drop and the current through the ground electrode, the resistance of the ground electrode (R G ) can be determined. R G = V I G R G = 0.017V A R G = 4.25 Ω As noted, this is a theoretical approach that requires perfect conditions. Any additional current flowing from the service through the ground electrode would reduce the accuracy of the measurement. The earth leakage clamp meter would have to filter out all but the current generated by the instrument through C1 to ensure the Page 8 of 24

9 accuracy. Additionally, this approach requires that a number of mathematical, calculations be made. The Attached Rod Technique is based on the theory outlined above. Figure 9 shows an ART test being made. Ground testers that are designed to make ART measurements include a special builtin current clamp that is placed between the C1 connection and the earth. This type of instrument includes noise protection and digitally filters out all currents other than that generated by the instruments. The instruments microprocessor automatically performs all the calculations necessary to generate a resistance measurement for the ground electrode. The test is a fall-of-potential test, meaning that all the "rules" still apply. Ideally, the operator would take ten measurements and plot the results to determine true resistance. Proper probe spacing remains critical, and fall-of- potential procedure and methodology must be followed. As with a traditional fall-of- potential test, the results can be proved by increasing the probe spacing. The advantage of the ART method over traditional fall-of-potential testing is that the ground electrode under test does not have to be disconnected from the system 4.0 GROUNDING SYSTEM DESIGN AND IMPROVEMENT Common minimum values of grounding resistance required for various network installations lie in the range of 5 to 25 Ω. as discussed in grounding procedures part1 and part-11. For large transmission and distribution substations, resistance of about 1 Ω is required. Such cases will certainly need grounding grids. For other cases, grounding rods or wires may be used. The recommended grounding rod is 16 mm diameter copper clad steel rod of 2.4 m length for use in normal soil and 1.2 m length for use in hard areas. In the areas with resistivity up to 100 Ohm-meters grounding shall be carried out using additional rods. Tables below describe the earth resistance values achieved versus approximate no. of ground rods required. In the areas with resistivity value higher than 100 ohm-meter Low Resistivity Materials (LRM) shall be used to improve the resistivity. Table 1 and 2 show the variation of resistance and resistivity and number of rods for rods, 2.4 m and 1.2 m lengths, respectively. Page 9 of 24

10 Table 1: Variation of grounding resistance with number of rod and soil resistivity on 2.4 m long, rod depth, rod diameter = 16 mm. ρ (Ω.m) Grounding Resistance (Ω) 1 rod 2 rods 3 rods 4 rods 8 rods 12 rods Table 2: Variation of grounding resistance with number of rod and soil resistivity at 1.2 m rod depth, rod diameter = 16 mm. ρ (Ω.m) Grounding Resistance (Ω) 1 rod 2 rods 3 rods 4 rods 8 rods 12 rods Page 10 of 24

11 Using these tables, it is possible to decide how many grounding rods are required to achieve a selected or specified value of ground resistance. Table 3 gives the required number of rods of two sizes, in soils of different resistivity values. In this table NP = Not Practicable is assigned to cases where too many rods are required. It is clear from this table that for medium to high soil resistivity, it is difficult to get less than 25 Ω grounding resistance by using rods only. Therefore, in such cases, soil resistivity has to be modified by using LRM Table 3: Number of rods required to obtain different grounding resistance values for various soil resistivity values. Grounding 5 Ω 10 Ω 15 Ω 25 Ω ρ (Ω.m) No. of 2.4 m rods No. of 1.2 m rods No. of 2.4 m rods No. of 1.2 m rods No. of 2.4 m rods No. of 1.2 m rods No. of 2.4 m rods No. of 1.2 m rods NP NP NP 23 NP 14 NP NP NP NP NP 27 NP 13 NP 1000 NP NP NP NP NP NP NP NP The specific grounding system design is usually based on the space available for installation and the desired specific value of grounding resistance. Installation of vertical ground rods is not always practical at certain locations. A horizontal electrode provides an effective alternative for narrow paths or shallow rock substructures. It might be a rod or more typically, a length of bare copper wire buried in the earth. Horizontal electrodes are often used to interconnect a system of multiple vertical electrodes for further reduction of overall system ground resistance. A horizontal electrode configuration can be either a straight line, a ring, or perimeter (square, circular, or triangular) or a star radiating from a single point. There is reduction in resistance with the increase in depth, but 0.5 m depth is found to be adequate for applications in the Kingdom. The resistance value of ring formation exhibits ~10% higher Rg value than straight horizontal wire of the same length. Page 11 of 24

12 Star configuration (radially extending out) presents almost the same resistance as the equal length of straight wire. The perimeter of ring can be changed to square or rectangular formation without changing appreciably the value of earth resistance. 4.1 APLICATION OF LRM Systematic investigations lead to the conclusion that the best choice for high resistivity soils are the vertical ground rods placed in LRM filled augered holes. Table 4 summarizes earth resistance values that can be obtained with the number of LRM treated 2.4 m long rod electrodes when used either alone or arranged in parallel, spaced at least 2.4 m apart of each other and placed in a straight line. Table 5 presents the required number of LRM treated vertical rod electrodes for each specific value of soil resistivity. Table 4: Variation of ground resistance of 2.4 m rod in augered holes of 0.1m diameter and filled with LRM Native Soil Number of Rods ρ (Ω.m) Table 5: Number of LRM treated rods in augered holes required for specific ground resistance in soil with ρ 100 Ω.m. Soil Resistivity ρ (Ω.m) Earth Resistance 5 Ω 10 Ω 15 Ω 25 Ω No. of 2.4 m long rods No. of 2.4 m long rods No. of 2.4 m long rods No. of 2.4 m long rods Page 12 of 24

13 For rocky and arid sandy terrains where the required specific resistance values cannot be obtained with 2.4 m long rods, then longer rods of either 3.6 m or 4.8 m length can be opted. Table 6 summarizes the values of resistances that can be obtained with these rods when placed in 10 cm diameter augered holes filled with LRM. Yet, another alternative is the use of horizontal buried wire with LRM. The use of LRM on these buried grounding systems will also reduce their surge impedance by increasing the effective contact area of electrode to soil. The horizontal wire shall be buried at a depth of 0.5 m and embedded in 5 cm 5 cm trench filled with LRM as shown in figure 11. The design engineer can select a specific electrode configuration as per the geodetic terrain, the prevailing soil resistivity, the importance of the intended site, the costs of copper rod /horizontal buried conductor and LRM. Table 6: Number of electrodes embedded in 10 cm diameter LRM filled augered holes for specific ground resistance. Spacing between rods should be equal to length of rod. Earth Resistance Resistivity (ρ) 5 Ω 10 Ω 15 Ω 25 Ω Rod Length Rod Length Rod Length Rod Length 3.6 m 4.8 m 3.6 m 4.8 m 3.6 m 4.8 m 3.6 m 4.8 m PREPARATION OF LRMs The LRM for application in augered holes (Fig.10) or in trenches prepared for horizontal layout of ground wire formations (Fig.11) shall be prepared as under LRM for Augered Hole (Type H b ) To fill a 2.4 long and 10 cm diameter hole, around 20 liters of LRM is required. For longer holes, multiples can be used. To get 20 liters, the ingredients have to be prepared in two steps (X and Y). In case of X, take 2.5 liters of bentonite clay and mix it with 10 liters of clean water (non salty) and then add and churn 53 ml of sodium carbonate (this salt is commercially Page 13 of 24

14 known as Soda Ash). Please do not use sodium chloride (the common kitchen salt) as it will spoil the bentonite. For part Y, take 160 ml of SAP and soak it in 6.7 liters of clean water (non salty). In about one hour SAP s granules will absorb all of this water and swell into the form of small ice cubes. For areas where the ambient temperatures are below 20 C, it may take a bit longer than one hour. Now mix well both (X+Y) and when done, the LRM is ready for pouring in the augered hole. The rod should be placed in the middle of the hole. Inserting the rod prior to filling of hole with LRM is the better way for such cases LRM for Trenches (Type P b ) To embed the copper wire in LRM in a 5cm x 5 cm trench, an LRM layer thickness of 5 cm is recommended. To prepare 100 liters of LRM of type P b, the ingredients have to be prepared in two steps (X and Y). For step X, take 15.2 liters of bentonite clay and mix it with 40 liters of clean water (non salty) to make a soft dough. Now add 320 ml of sodium carbonate and mix it well. For step Y, take 905 ml of SAP and soak it in 40 liters of clean water (non salty) for about one hour till it fully absorbs all of this water. Now mix well both (X+Y). LRM type P b is ready for pouring in the trench. Cover the layer of LRM with a polyethylene sheet of at least 1-2 mm thickness, before refilling with the native soil. To prepare a different quantity of LRM, the same ratio of ingredients of step X and Y must be maintained. For laying earth wire embedded with LRM, prepare the trench as shown in Figure 11. Spread out enough LRM uniformly in the bottom of the trench up to a thickness of 2.5 cm (1.0") and then place the horizontal wire conductor on the top of LRM. Spread more LRM to completely cover conductor about 2.5 cm thick. Preferably use ground staples to maintain wire conductor in the center of the LRM filling. Pour some soil in the trench at the top of the LRM and gently tamp it down. Now fill the rest of the trench. Important Notes: (a) Do not use salty water as it will spoil the bentonite clay for producing LRM. Clean water with conductivity < 500 µs/cm (micro Siemens/centimeter) is recommended. (b) For preparation of smaller quantities of LRM, plastic mixing tubs or wheel borrow, and for larger quantities cement mixer can be used. (c) Never indigest the granules of SAP. Page 14 of 24

15 Page 15 of 24

16 Page 16 of 24

17 Page 17 of 24

18 Page 18 of 24

19 Page 19 of 24

20 Page 20 of 24

21 Figure-7: Ground Resistance measurements Figure-8: Leakage Current Meaurement Page 21 of 24

22 Figure-9: Attached Rod Technique measurement. Page 22 of 24

23 Reduction in Rg using LRM <5 Ω m r- Radius of the ground rod L- Length of the ground rod D- Bore diameter FIGURE 10: LRM for Augered Hole (Type H b ) Page 23 of 24

24 Native Soil Backfill 50 cm LRM 5 cm 2.5 cm Wire conductor 5 cm Figure-11: Preparation of trench for LRM embedded horizontal wire conductor Page 24 of 24

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING Rev. 01 This specification is property of SEC and subject to change or modification without any notice

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

Industrial and Commercial Power Systems Topic 7 EARTHING

Industrial and Commercial Power Systems Topic 7 EARTHING The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 7 EARTHING 1 INTRODUCTION Advantages of earthing (grounding): Limitation

More information

Grounding and Lightning arrestors

Grounding and Lightning arrestors CHAPTER - Four Grounding and Lightning arrestors 4.1. Introduction Electrical connection of neutral point of a supply system or the non current carrying part of electrical equipments to the general mass

More information

FAQ ON EARTHING STANDARDS 16/08/2018

FAQ ON EARTHING STANDARDS 16/08/2018 FAQ ON EARTHING STANDARDS 16/08/2018 This document has been updated to include changes made to substation earthing layouts that have been made necessary due to copper theft. The main changes to be aware

More information

HV Substation Earthing Design for Mines

HV Substation Earthing Design for Mines International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 4, Issue 6 (October 2012), PP. 100-107 HV Substation Earthing Design for Mines M.

More information

ANALOG RESISTANCE METER USER S MANUAL

ANALOG RESISTANCE METER USER S MANUAL Page 1 of 14 MILLER 400A ANALOG RESISTANCE METER USER S MANUAL Page 2 of 14 CONTENTS Page Description.. 3 Operating Instructions 4 Applications 5 4-Electrode Applications.. 5 Earth Resistivity Measurement...

More information

ANALOG RESISTANCE METER

ANALOG RESISTANCE METER 1 P a g e M A N 1 6 0 MILLER 400A ANALOG RESISTANCE METER USER S MANUAL Revised Aug 22, 2018 2 P a g e M A N 1 6 0 CONTENTS Page Description.. 3 Operating Instructions 4 Applications 5 4-Electrode Applications..

More information

High Voltage Pylon Earth Measurements

High Voltage Pylon Earth Measurements High Voltage Pylon Earth Measurements Speaker: Gavin van Rooy Authors: Frank Barnes and Gavin van Rooy Tycom (Pty) Ltd PO Box 3546, Randburg, 2125, South Africa E-mail: frank@tycom.co.za Phone: 011 787

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

UNDERSTANDING. Ground Resistance Testing. Soil Resistivity. Ground Resistance. 3-Point Measurements. 4-Point Measurements. Clamp-On Measurements

UNDERSTANDING. Ground Resistance Testing. Soil Resistivity. Ground Resistance. 3-Point Measurements. 4-Point Measurements. Clamp-On Measurements UNDERSTANDING Ground Resistance Testing Current supply E Ammeter (I) I Voltmeter (E) Ground electrode under test X Auxiliary potential electrode Y Auxiliary current electrode Z R Rx R1 R2 Rn-1 Rn EARTH

More information

Grounding for Power Quality

Grounding for Power Quality Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states

More information

Importance of Grounding in Power System. Presented by Mr. H Jayakumar Ex- Joint Director CPRI

Importance of Grounding in Power System. Presented by Mr. H Jayakumar Ex- Joint Director CPRI Importance of Grounding in Power System Presented by Mr. H Jayakumar Ex- Joint Director CPRI OBJECT OF EARTHING Prime Object of Earthing is to Provide a Zero Potential Surface in and around and under the

More information

K e e l i n g C o m p a n y

K e e l i n g C o m p a n y e e l i n g C o m p a n y GOLF IRRIGATION WIRE Page 87 GOLF IRRIGATION WIRE e e l i n g C o m p a n y Page 88 e e l i n g C o m p a n y It is the responsibility of the installer to connect all electronic

More information

EXCAVATION AND BACKFILL

EXCAVATION AND BACKFILL Standard Specification 2565.3, 2451, and 1805 A basic understanding of specifications is needed to properly replace the disturbed soil and restore the condition of the excavated area. The size of the disturbed

More information

Evaluation of Soil Resistivity Characteristics forsubstation Grounding: a Case Study of a University Campus in South-West Zone, Nigeria

Evaluation of Soil Resistivity Characteristics forsubstation Grounding: a Case Study of a University Campus in South-West Zone, Nigeria Evaluation of Soil Resistivity Characteristics forsubstation Grounding: a Case Study of a University Campus in South-West Zone, Nigeria Adegboyega Gabriel A Bells University of Technology, Ota, Nigeria

More information

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor Safety earthing Sector Energy PTI NC Theodor Connor Copyright Siemens AG 2008. All rights reserved. Content Introduction Theoretical background Soil Analysis Design of earthing system Measurements on earthing

More information

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4 SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: 16.10 Document Number: KUCSH0039 Rev: 4 16.10.1 INTRODUCTION 16.10.1.1 The intent of this standard is to ensure that continuity

More information

Device Interconnection

Device Interconnection Device Interconnection An important, if less than glamorous, aspect of audio signal handling is the connection of one device to another. Of course, a primary concern is the matching of signal levels and

More information

Attendee Announcements

Attendee Announcements Attendee Announcements Seminar Raffle Be sure to drop your raffle ticket in the drum at today s Keynote located in the Mile High Ballroom. You have a chance to win a $250 American Express Gift Card. One

More information

Outdoor Installation 2: Lightning Protection and Grounding

Outdoor Installation 2: Lightning Protection and Grounding Outdoor Installation 2: Lightning Protection and Grounding Training materials for wireless trainers This one hour talk covers lightning protection, grounding techniques and problems, and electrolytic incompatibility.

More information

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002 National Radio Astronomy Observatory Socorro, NM 87801 EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable T. Baldwin June 05, 2002 Summary Double-armor triple-sheath fiber optic cable will be

More information

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING 1 PRACTICAL PROBLEMS WITH SUBSTATION EARTHING Dr Hendri Geldenhuys Craig Clark Eskom Distribution Technology This paper considers the issues around substation sites where the soil resistivity is of particularly

More information

Appendix. Appendix. Getting Down to Earth. AVO, International NJATC 07

Appendix. Appendix. Getting Down to Earth. AVO, International NJATC 07 IBEW NECA Appendix ATTITUDE SKILL KNOWLEDGE FOR APPRENTICESHIP & TRAINING THE ELECTRICAL INDUSTRY Appendix Getting Down to Earth AVO, International Appendix IBEW NECA ATTITUDE SKILL KNOWLEDGE FOR APPRENTICESHIP

More information

EARTH-POTENTIAL ELECTRODES PERMAFROST AND TUNDRA

EARTH-POTENTIAL ELECTRODES PERMAFROST AND TUNDRA EARTH-POTENTAL ELECTRODES PERMAFROST AND TUNDRA N V. P. Hessler and A. R. Franzke* ntroduction URNG the past two years the authors installed a number of electrodes D in the permafrost and tundra area of

More information

Understand the importance of Ground Resistance Testing & much more! (800) (508)

Understand the importance of Ground Resistance Testing & much more! (800) (508) Soil Resistivity Ground Resistance 3-Point Measurements 4-Point Measurements Clamp-On Measurements Understand the importance of Ground Resistance Testing & much more! (800) 343-1391 (508) 698-2115 www.aemc.com

More information

Stake-less earth / ground testing

Stake-less earth / ground testing APPLICATION NOTE Stake-less earth / ground testing NEW DET14C and DET24C CLAMPS GETTING-AROUND ANY CHALLENGE What is stake-less testing? How does it work? Where and how can it be used? What are the potential

More information

Article 250 Grounding & Bonding

Article 250 Grounding & Bonding Article 250 Grounding & Bonding AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Dr. Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER NOTE: This course is APPROVED for continuing education

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard NSW Category Electrical Title Reference Number PDS 05 (RIC Standard: EP 12 10 00 11 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

Instruction Manual. TT1000 Tower Earth Tester. Rev 01

Instruction Manual. TT1000 Tower Earth Tester. Rev 01 Instruction Manual TT1000 Tower Earth Tester Rev 01 Contents 1 Introduction... 3 2 Features... 3 3 Operation... 4 3.1 Test Lead Configuration... 5 3.2 Probe Integrity Test... 6 3.3 Impedance measurement...

More information

PERFORMANCE ASSESSMENT OF SUBSTATION SITE EARTHING USING FLUKE 1625 GROUND TESTER

PERFORMANCE ASSESSMENT OF SUBSTATION SITE EARTHING USING FLUKE 1625 GROUND TESTER Nigerian Journal of Technology (NIJOTECH) Vol. 32, No. 1, March, 2013, pp. 49 53. Copyright 2013 Faculty of Engineering, University of Nigeria. ISSN 1115-8443 PERFORMANCE ASSESSMENT OF SUBSTATION SITE

More information

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit Current will always try to return to its source In order for there to be current, there must be a complete circuit Current will take as many paths or circuits available to it to return to the source The

More information

American Electrical Institute

American Electrical Institute American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article

More information

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:15 No:03 39 Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models Shen-Wen Hsiao, Shen-Jen

More information

UNDERSTANDING. Ground Resistance Testing. I Voltmeter (E) Grounding. electrode. under test. Ground rod and clamp

UNDERSTANDING. Ground Resistance Testing. I Voltmeter (E) Grounding. electrode. under test. Ground rod and clamp UNDERSTANDING Ground Resistance Testing Current supply E Ammeter (I) I Voltmeter (E) Grounding electrode under test X Auxiliary potential electrode Y Auxiliary current electrode Z R Rx R1 R2 Rn-1 Rn EARTH

More information

Asset Protection Cathodic Protection Soil Resistivity Measurement. Work Instruction No.:

Asset Protection Cathodic Protection Soil Resistivity Measurement. Work Instruction No.: Asset Protection Cathodic Protection Soil Resistivity Measurement Approved by: Manager Pipeline Standards 1 PURPOSE This work instruction describes the processes to be followed when measuring soil resistivity.

More information

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS 2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS Contents Section Brief Description... 1 Where and why it is used... 1.1 Induced Measureable Parameters... 1.2 Hardware

More information

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object U. S. Gudmundsdottir, C. F. Mieritz Abstract-- When a lightning discharge strikes a tall object, the lightning current

More information

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy High Voltage Pylon earth Measurements Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy Abstract The earth connection of high voltage electrical power line pylons is obviously

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

EPG. by Chris C. Kleronomos

EPG. by Chris C. Kleronomos April 1994 EFFECTIVE EQUIPMENT GROUNDING ECOS Electronics Corporation by Chris C. Kleronomos The quality of the electrical wiring and grounding in a facility containing sensitive electronic equipment is

More information

LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE

LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE International Lightning Protection Association 1 st Symposium Valencia Spain 24th 25th of November, 2011 LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE Alain Rousseau SEFTIM (France) ABSTRACT To make a

More information

Examples of Design for Cathodic Protection Systems

Examples of Design for Cathodic Protection Systems Examples of Design for Cathodic Protection Systems CURRENT REQUIREMENTS From Estimated Exposed Surface Area Estimating current requirements from expected exposed surface is always subject to error. There

More information

Back to the Basics Current Transformer (CT) Testing

Back to the Basics Current Transformer (CT) Testing Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of

More information

CONTINUOUS COUNTERPOISE ON POLES

CONTINUOUS COUNTERPOISE ON POLES Project Procedure CONTINUOUS COUNTERPOISE ON POLES 07/25/2011 PAGE 1 OF 5 1.0 PURPOSE The purpose of this procedure is to provide guidance and direction for the installation of continuous counterpoise

More information

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS Section 1 Definitions 2 Scope of Work 3 Extent of Work 4 Inspection and Performance of Work 5 Trenching 6 Duct Installation

More information

Foundation Specifications

Foundation Specifications Installation Instructions Bulletin 237746 Foundation Specifications for High-Wind 4.5-Meter Earth Station Antennas Revision C 1.0 INTRODUCTION 1.1 This document specifies typical foundation characteristics,

More information

Current Probes. User Manual

Current Probes. User Manual Current Probes User Manual ETS-Lindgren Inc. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall

More information

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments Thomas Szollossy Senior Technical Support Engineer Power Quality Thailand PQSynergy 2017, Chiang Mai, Thailand Introduction

More information

Instruction Manual for Digital Grounding Resistance Meter. Table of Contents

Instruction Manual for Digital Grounding Resistance Meter. Table of Contents I. Overview...2 II. Open-case Inspection...3 III. Safety Precautions...4 IV. Work Principle...7 V. Appearance Description...9 VI. Technical Characteristics 10 VII. Resistance Measurement Method..12 VIII.Battery

More information

Instruction Manual for Digital Grounding Resistance Meter

Instruction Manual for Digital Grounding Resistance Meter Instruction Manual for Digital Grounding Resistance Meter Instruction Manual for Digital Grounding Resistance Meter Table of Contents I. Overview...2 II. Open-case Inspection...3 III. Safety Precautions...4

More information

Customer Requirements RF Antenna Installations

Customer Requirements RF Antenna Installations Application Terms Attachment requirements and clearances on the Pole for Radio Frequency (RF) antenna equipment installations. This standard is intended to allow electrical workers to perform their normal

More information

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU Technology solutions and innovations for developing economies Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT

More information

SELF-ALIGNING PLASTIC INCLINOMETER CASING IN BOREHOLES. Model GEO-LOK. Roctest Limited, All rights reserved.

SELF-ALIGNING PLASTIC INCLINOMETER CASING IN BOREHOLES. Model GEO-LOK. Roctest Limited, All rights reserved. INSTRUCTION MANUAL SELF-ALIGNING PLASTIC INCLINOMETER CASING IN BOREHOLES Model Roctest Limited, 2013. All rights reserved. This product should be installed and operated only by qualified personnel. Its

More information

ABSTRACT 1 INTRODUCTION

ABSTRACT 1 INTRODUCTION ELECTROMAGNETIC ANALYSIS OF WIND TURBINE GROUNDING SYSTEMS Maria Lorentzou*, Ian Cotton**, Nikos Hatziargyriou*, Nick Jenkins** * National Technical University of Athens, 42 Patission Street, 1682 Athens,

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

Toro OSMAC RDR Field Satellite Electric Actuation Models Installation Instructions

Toro OSMAC RDR Field Satellite Electric Actuation Models Installation Instructions Toro OSMAC RDR Field Satellite Electric Actuation Models Installation Instructions Introduction The OSMAC RDR Satellite Controller is designed for installation on a substantial concrete foundation with

More information

Basic Wire Antennas. Part II: Loops and Verticals

Basic Wire Antennas. Part II: Loops and Verticals Basic Wire Antennas Part II: Loops and Verticals A loop antenna is composed of a single loop of wire, greater than a half wavelength long. The loop does not have to be any particular shape. RF power can

More information

Best Practices for Power and Transient Protection on Rosemount Radar Transmitters

Best Practices for Power and Transient Protection on Rosemount Radar Transmitters Technical Note Rosemount Radar Transmitters Best Practices for Power and Transient Protection on Rosemount Radar Transmitters BACKGROUND INTRODUCTION This document describes best practices for power and

More information

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA Rajat Verma Project Engineer BHEL EDN, BANGALURU, MYSORE ROAD, KARNATAKA 560024, India ABSTRACT

More information

Reference Number PDS 04 (RIC Standard: EP SP)

Reference Number PDS 04 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Reference Number PDS 04 (RIC Standard: EP 12 10 00 10 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

4 Antennas as an essential part of any radio station

4 Antennas as an essential part of any radio station 4 Antennas as an essential part of any radio station 4.1 Choosing an antenna Communicators quickly learn two antenna truths: Any antenna is better than no antenna. Time, effort and money invested in the

More information

AN Far field antenna design. Document information. UCODE EPC G2, G2XM, G2XL, Antenna design

AN Far field antenna design. Document information. UCODE EPC G2, G2XM, G2XL, Antenna design AN 0971 Far field antenna design Rev 1.4 4 March 2008 Application note Document information Info Keywords Abstract Content UCODE EPC G2, G2XM, G2XL, Antenna design This application note provides general

More information

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of

More information

INDEX. Micro-ohmmeter MH-10 Page 3. MI (5, 10, 15, 20 kv) Page 4 Mega-ohmmeter MD (5 kv) Page 4

INDEX. Micro-ohmmeter MH-10 Page 3. MI (5, 10, 15, 20 kv) Page 4 Mega-ohmmeter MD (5 kv) Page 4 Micro-ohmmeter MH-10 Page 3 MI (5, 10, 15, 20 kv) Page 4 Mega-ohmmeter MD (5 kv) Page 4 Earth resistance meter TL-5 Page 5 Indirect earth contact simulator MPC (5, 20, 50 A) Page 6 Trip time tester CR

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING Y. Rajotte J. Fortin G. Lessard Hydro-Québec, Canada Hydro-Québec, Canada Hydro-Québec, Canada e-mails: rajotte.yves@ireq.ca fortin.jacques@ireq.ca

More information

ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment)

ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment) ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment) 1. In an A.C. circuit A ; the current leads the voltage by 30 0 and in circuit B, the current lags behind the voltage by 30 0. What is the

More information

Semi-permanent sediment pore water sampling systems.

Semi-permanent sediment pore water sampling systems. Semi-permanent sediment pore water sampling systems. These are based on the simple and extremely effective MHEproducts TubeWells which are constructed of ¼ polyethylene tubing and fitted with a 10 cm polypropylene

More information

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation Marcos Telló Department of Electrical Engineering Pontifical Catholic University of Rio Grande

More information

AC Voltage- Pipeline Safety and Corrosion MEA 2015

AC Voltage- Pipeline Safety and Corrosion MEA 2015 AC Voltage- Pipeline Safety and Corrosion MEA 2015 WHAT ARE THE CONCERNS ASSOCIATED WITH AC VOLTAGES ON PIPELINES? AC concerns Induced AC Faults Lightning Capacitive coupling Safety Code Induced AC Corrosion

More information

Stray Voltage and Swimming Pools

Stray Voltage and Swimming Pools Stray Voltage and Swimming Pools Marty L. Page, P.E. Southern Company malpage@southernco.com October 19 th 2009 2009 Jodie Lane National Conference for Stray Voltage Detection, Mitigation & Prevention

More information

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 422 MAY 1993 CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS 422.01 SCOPE 422.02 REFERENCES 422.03 DEFINITIONS

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

ENGINEERING REPORT PHASES I & II MITIGATOR PERFORMANCE TESTS

ENGINEERING REPORT PHASES I & II MITIGATOR PERFORMANCE TESTS ENGINEERING REPORT PHASES I & II MITIGATOR PERFORMANCE TESTS INDUCED AC MITIGATION PERFORMANCE ON A STEEL GAS TRANSMISSION PIPELINE REPORT OF JANUARY 29, 2014 Copyright MATCOR, Inc. 2014 MITIGATOR TM VS.

More information

Soil Resistivity Ground Resistance 3-Point Measurements 4-Point Measurements Clamp-On Measurements

Soil Resistivity Ground Resistance 3-Point Measurements 4-Point Measurements Clamp-On Measurements Soil Resistivity Ground Resistance 3-Point Measurements 4-Point Measurements Clamp-On Measurements 200 Foxborough Blvd. Foxborough, MA 02035 (800) 343-1391 (508) 698-2115 FAX (508) 698-2118 sales@aemc.com

More information

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN): Single Earthed Neutral and Multi Earthed Neutral. SEPTEMBER 6, 2011 5 COMMENTS Single Earthed Neutral and Multi Earthed Neutral: In Distribution System Three Phase load is unbalance and non linear so The

More information

Outline. Grounding Washer, Electrical Equipment Bond (WEEB) Acme Cable Clips Acme Conduit Entry (ACE) Questions

Outline. Grounding Washer, Electrical Equipment Bond (WEEB) Acme Cable Clips Acme Conduit Entry (ACE) Questions www.we-llc.com Outline Grounding Washer, Electrical Equipment Bond (WEEB) Acme Cable Clips Acme Conduit Entry (ACE) Questions Bonding & Grounding Grounding Terms Equipment Grounding: The National Electrical

More information

INSTRUCTION MANUAL. Model 18AVQII Five Band Vertical Antenna 10, 15, 20, 40, 80 Meter. General Description. Theory of Operation

INSTRUCTION MANUAL. Model 18AVQII Five Band Vertical Antenna 10, 15, 20, 40, 80 Meter. General Description. Theory of Operation Model 18AVQII Five Band Vertical Antenna 10, 15, 20, 40, 80 Meter 308 Industrial Park Road Starkville, MS 39759 (662) 323-9538 Fax: (662) 323-5803 INSTRUCTION MANUAL General Description The Hy-Gain 18AVQII

More information

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design IEEE PES Transmission and Distribution Conference 2008 Panel Session Large Wind Plant Collector Design Wind Farm Collector System Grounding by Steven W. Saylors, P.E. Chief Electrical Engineer Vestas Americas

More information

American Institute of Timber Construction 7012 South Revere Parkway Suite 140 Centennial, CO Phone: 303/ Fax: 303/

American Institute of Timber Construction 7012 South Revere Parkway Suite 140 Centennial, CO Phone: 303/ Fax: 303/ American Institute of Timber Construction 7012 South Revere Parkway Suite 140 Centennial, CO 80112 Phone: 303/792-9559 Fax: 303/792-0669 404.1. SCOPE STANDARD FOR RADIALLY REINFORCING CURVED GLUED LAMINATED

More information

GROUND TESTERS For all of your Ground Testing needs...

GROUND TESTERS For all of your Ground Testing needs... GROUND TESTERS For all of your Ground Testing needs... An array of Ground Testers to choose from Whether you are doing a simplified 2-Point, a more complete 3- or 4-Point Fall-of-Potential test, a soil

More information

Electrical TP-18 February 2017 ELECTRICAL TECHNICAL PAPER 18 FREQUENTLY ASKED QUESTIONS ABOUT CATHODIC PROTECTION SYSTEM EQUIPMENT TESTING

Electrical TP-18 February 2017 ELECTRICAL TECHNICAL PAPER 18 FREQUENTLY ASKED QUESTIONS ABOUT CATHODIC PROTECTION SYSTEM EQUIPMENT TESTING ELECTRICAL TECHNICAL PAPER 18 FREQUENTLY ASKED QUESTIONS ABOUT CATHODIC PROTECTION SYSTEM EQUIPMENT TESTING CATHODIC PROTECTION SYSTEM EQUIPMENT TESTING Question No. 1 What should I (the contractor) check

More information

Lightning Strikes. Presented to the Greater Norwalk Amateur Radio Corporation Inc. February 8, 2017 Steven M. Simons W1SMS

Lightning Strikes. Presented to the Greater Norwalk Amateur Radio Corporation Inc. February 8, 2017 Steven M. Simons W1SMS Lightning Strikes Presented to the Greater Norwalk Amateur Radio Corporation Inc. February 8, 2017 Steven M. Simons W1SMS ARRL CT State Technical Coordinator The Power of Lightning What is a Ground? Design

More information

There are a wide variety of ground resistance testers available on the

There are a wide variety of ground resistance testers available on the Featured Products: Choosing the Right Ground Resistance Tester There are a wide variety of ground resistance testers available on the market today. These vary in design, features, and complexity, and include

More information

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER GROUNDED ELECTRICAL POWER DISTRIBUTION Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER .0 Conductors for Electrical Power Distribution For single-phase transmission of AC power or

More information

Generation of Sub-nanosecond Pulses

Generation of Sub-nanosecond Pulses Chapter - 6 Generation of Sub-nanosecond Pulses 6.1 Introduction principle of peaking circuit In certain applications like high power microwaves (HPM), pulsed laser drivers, etc., very fast rise times

More information

White Paper Security Cameras, CATV, GPS and Satellite Protection

White Paper Security Cameras, CATV, GPS and Satellite Protection White Paper Security Cameras, CATV, GPS and Satellite Protection 1485-042 White Paper Security Cameras, CATV, GPS and Satellite Protection Security Cameras, CATV, GPS & Satellite Protection Outdoor Closed

More information

AMERICAN NATIONAL STANDARD

AMERICAN NATIONAL STANDARD ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 81 2007 Surge Withstand Test Procedure NOTICE The Society of Cable Telecommunications Engineers (SCTE) Standards

More information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS 1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8

More information

Conduit measured transfer impedance and shielding effectiveness (typically achieved in the RS103 and CS114 tests)

Conduit measured transfer impedance and shielding effectiveness (typically achieved in the RS103 and CS114 tests) Conduit measured transfer impedance and shielding effectiveness (typically achieved in the RS3 and CS4 tests) D. A. Weston K. McDougall conduitse.doc 5-2-27 The data and information contained within this

More information

Calculate the maximum amount of energy this battery can deliver.

Calculate the maximum amount of energy this battery can deliver. 1 A battery in a laptop computer has an electromotive force (emf) of 14.8 V and can store a maximum charge of 15. 5 10 3 C. The battery has negligible internal resistance. Calculate the maximum amount

More information

Tools of Algebra. Chapter 1:

Tools of Algebra. Chapter 1: Chapter 1: Tools of Algebra Using algebraic formulas requires skill with all types of numbers (negatives, fractions and decimals), an understanding of measurements for lengths and angles, familiarity with

More information

ACompactN-Way Wilkinson Power Divider Using a Novel Coaxial Cable Implementation for VHF Band

ACompactN-Way Wilkinson Power Divider Using a Novel Coaxial Cable Implementation for VHF Band Progress In Electromagnetics Research Letters, Vol. 62, 49 55, 2016 ACompactN-Way Wilkinson Power Divider Using a Novel Coaxial Cable Implementation for VHF Band S. S. Kakatkar *,PrafullIrpache,andK.P.Ray

More information

Pre-Laboratory Assignment

Pre-Laboratory Assignment Measurement of Electrical Resistance and Ohm's Law PreLaboratory Assignment Read carefully the entire description of the laboratory and answer the following questions based upon the material contained

More information

60Hz Ratings. Typical Applications. Features & Characteristics. Ratings

60Hz Ratings. Typical Applications. Features & Characteristics. Ratings The PCR is a solid-state device designed to simultaneously provide DC isolation and AC continuity/grounding when used with cathodically protected structures, such as pipelines, tanks, grounding systems,

More information

Chapter 6 Antenna Basics. Dipoles, Ground-planes, and Wires Directional Antennas Feed Lines

Chapter 6 Antenna Basics. Dipoles, Ground-planes, and Wires Directional Antennas Feed Lines Chapter 6 Antenna Basics Dipoles, Ground-planes, and Wires Directional Antennas Feed Lines Some General Rules Bigger is better. (Most of the time) Higher is better. (Most of the time) Lower SWR is better.

More information

The influence of environment on condition of location damage in screen of the coaxial cable. 1. Introduction

The influence of environment on condition of location damage in screen of the coaxial cable. 1. Introduction Computer Applications in Electrical Engineering The influence of environment on condition of location damage in screen of the coaxial cable Wiesław Tarczyński Opole University of Technology 45-233 Opole,

More information

Rec. ITU-R F RECOMMENDATION ITU-R F *

Rec. ITU-R F RECOMMENDATION ITU-R F * Rec. ITU-R F.162-3 1 RECOMMENDATION ITU-R F.162-3 * Rec. ITU-R F.162-3 USE OF DIRECTIONAL TRANSMITTING ANTENNAS IN THE FIXED SERVICE OPERATING IN BANDS BELOW ABOUT 30 MHz (Question 150/9) (1953-1956-1966-1970-1992)

More information

LC31L-BAT Link Coupler

LC31L-BAT Link Coupler Instruction Manual For the LC31L-BAT Link Coupler 09 March 2018 2012-2018 by Ralph Hartwell Spectrotek Services All rights reserved 2 RADIO FREQUENCY WARNING NOTICE If the LC31L-BAT is installed incorrectly

More information