A Distance Based Protection Scheme for Distribution Systems with Distributed Generators

Size: px
Start display at page:

Download "A Distance Based Protection Scheme for Distribution Systems with Distributed Generators"

Transcription

1 A Distance Based Protection Scheme for Distribution Systems with Distributed Generators V. C. Nikolaidis, C. Arsenopoulos, A. S. Safigianni Department of Electrical and Computer Engineering Democritus University of Thrace (DUTH) Xanthi, Greece {vnikolai, konsarse, Costas D. Vournas School of Electrical and Computer Engineering National Technical University of Athens (NTUA) Athens, Greece Abstract This paper investigates the application of distance relays in distribution systems with distributed generators. An analysis of the parameters that influence the effectiveness of distance relaying in distribution networks is performed. Protection coordination between the distance relays and the existing protection means on the line is studied with the help of a realistic distribution network. Coordination problems are identified and a simple distance-based protection scheme is proposed. Index Terms Distance protection, distributed generation, distribution systems, protection coordination. I. INTRODUCTION Protection of a distribution network, in the vast majority of cases, is based on the overcurrent protection principle [1]. In existing distribution feeders, this principle is applied by designing protection schemes that are based on the proper coordination of fuses, reclosers and overcurrent relays. The expected result is that each fault should be cleared sufficiently fast with minimum impact on the customers, even when a protection device will fail. Obtaining this goal in a distribution feeder is a complicated task because it requires coordination studies that have to include all possible system states and operating scenarios, taking also into consideration the specific protection equipment available. The penetration of Distributed Generation (DG) in distribution systems considerably reformed the operating practices in these networks. Among others, the bi-directionality in the fault current flow due to the connection of DG units and the contribution of the DG units to the fault current level cause significant impact on the protection system. If the existing overcurrent protection philosophy is applied then this could lead to various issues like not-expected fuse blowing or other protection misoperations [2]. It is obvious that changes in the overcurrent protection design are necessary to overcome the impacts [3]. In general, there is a rising need to address many incompatibility issues, as well as to review and implement suitable protection schemes. In this context, the application of the distance relaying principle to protect distribution systems with DG seems a promising option [4], [5], [6]. This paper examines the application of distance relays in radial distribution systems with DG. The organization of this paper is as follows. Section II includes a brief introduction to distance protection applications in distribution systems. Section III describes the proposed distance-based protection scheme. Section IV presents the simulation results and the effect of some influencing parameters on the distance relay performance, while the conclusions are drawn in Section V. II. DISTANCE PROTECTION IN DISTRIBUTION SYSTEMS A. Distance Protection Principles Distance relays are used for primary and/or backup protection for phase faults and/or ground faults on transmission, subtransmission and distribution lines. In principle, a distance relay determines the fault impedance from the measured voltage and current at the relay location [1]. Then the measured fault impedance is compared with the known line impedance to determine if a trip command should be issued to the circuit breaker. The intentional time delay before releasing the trip command is beforehand decided in accordance with the fault distance from the relay location. The protected line portion and the corresponding time delay define the zone settings of the relay, determined in the protection design stage. Usually, there are more than one distance zone settings determined in order to provide selectivity between the various protection means in the network. Moreover, the phase and ground elements of the relay are set separately, thus resulting in different zone characteristics. Each distance zone corresponds to a specific characteristic on the complex impedance plane. Fig. 1 depicts the most common characteristics encountered nowadays, which are the mho and the polygonal ones. In Fig. 1, the typical load encroachment characteristic of distance relays is also illustrated on the impedance plane. As long as the impedance measured from the distance relay lies inside the load encroachment area, the trip command of the three-phase element is blocked.

2 B. Distribution Systems without DG Radial distribution systems are usually protected with overcurrent protection equipment. Overhead distribution lines are typically protected by a recloser located at the beginning of the feeder, which is coordinated with the downstream protection means (overcurrent relays, reclosers, and/or sectionalisers) on the main trunk and with the fuses on the laterals [1]. Radial cable lines are typically protected with overcurrent relays. In ring or meshed distribution networks, directional elements are used supplementary to the overcurrent relays in order to discriminate between the fault directions. Distance protection is not so commonly applied in distribution lines. Traditionally, this was because of the additional cost of the distance protection system due to the need of a voltage transformer together with the current transformer and the higher cost of the distance relay itself, which was more expensive than a simple overcurrent relay. Nowadays, distance protection begins more frequently to be applied in distribution networks, since the associated costs have been reduced and the benefits of the distance protection principle compared to the overcurrent one are obvious. Just to mention, the most pronounced benefits are its inherent directionality and the independency from the source impedance magnitude. In overhead line networks, the distance protection is in general implemented with automatic reclosing schemes [7]. In cable networks, if distance protection is applied as the main protection scheme, this is done with a permissive tripping arrangement via fiber optic communication. Since such schemes resemble the differential protection principle, this paper deals with application of distance protection in overhead line distribution networks. The simplest way to apply distance protection in radial overhead line distribution systems is to replace the recloser at the beginning of the feeder with a distance relay. Then, each relay setting corresponds to several fault locations, depending on the actual reach of the respective zone. For example, if Z set in Fig. 2 is the impedance reach of one of the zones, any fault within this zone will be sensed from the relay. Hence, it is the responsibility of the protection engineer to ensure selectivity between the distance relay (DR) and the protection equipment on the line that is included in this zone. C. Distribution Systems with DG When DG units are connected to distribution systems, the performance of the conventional overcurrent protection system is further affected by a number of critical factors. For instance, if the utility source is weak and the short-circuit capacity of the DG units approach that of the source, large variations in fault level will exist when the generation is in or out of service. This variation in fault level makes phase and ground overcurrent relay grading very difficult. The coordination of the overcurrent relays may also be distorted depending on the size and location of the DG units [2]. Furthermore, to maintain the stability of the distributed generators fault clearance times should be kept to a minimum. It should be noted that the above mentioned difficulties apply equally to radial circuits protected by non-directional relays and ring circuits protected by directional relays. Figure 1. Mho and polygonal characteristics. Figure 2. Reach of distance zone in radial feeders Distance protection in distribution networks with DG can improve the operating performance of the network as well as that of the protection system itself. However there are still some issues that should be dealt with efficiently. Special attention when designing distance protection in power systems with multiple intermediate sources should be given to the so called infeed effect [1]. The infeed effect results in an increase in the fault impedance measured by a distance relay if one or more generation sources are connected between the relay and the fault location. Then, the relay sees the fault at a greater distance and may only trip in a higher zone. Therefore, when there is at least one DG connected between the distance relay and the fault location, the additional fault current supplied by the DG unit must be taken into account for setting the relay properly. Consider, for example, the distribution line in Fig. 3, where a short-circuit occurs in the middle of the main trunk. Without the connection of the DG unit, the distance relay would measure the actual positive sequence impedance to the fault which is equal to Z A + Z B. When the intermediate current I B flows, the impedance appears to the distance relay as Z A + Z B + (I B /I A )Z B. The fraction between I B and I A is defined as the infeed constant K = I B /I A. The relay therefore sees an impedance of KZ B in addition to the impedance Z A + Z B, which implies that its reach is reduced. In other words, the fault appears to be farther away because of the current I B. A quite detailed guideline for extracting efficient setting rules for the distance protection in a radial distribution system with DG is given in [5]. The authors try to suggest generic rules in a way to resemble the traditional overcurrent protection philosophy. In many cases, the distance relay is used with its zone controlling the overcurrent element.

3 Figure 3. Infeed effect III. PROPOSED DISTANCE PROTECTION SCHEME To illustrate the setting rules for the distance-based protection scheme, the radial overhead line distribution system depicted in Fig. 2 is considered again. The fuses F1-F4 protect the main laterals, while the fuses F1.r-F.4.r protect the remotest tapped distribution transformer in each lateral. We assume fuses at the laterals because they are the most encountered protection means in overhead distribution lines and because fuses are more difficult to coordinate with the main feeder protection (recloser/distance relay) than overcurrent relays due to their non-settable characteristic. A fuse-saving philosophy is further adopted. Coordination between the main fuse and the fuses at the primary of the tapped transformers is assumed. The distance relay DR is installed at the beginning of the line replacing the conventional overcurrent relay. The radial line is divided into protection zones each of them (except of the first) covers part of the main line and the whole length of one of the laterals. Attention should be given so that none of the protection zones of the distance relay will overreach the protection zone of any of the distribution transformers that are tapped on the laterals. To complete this fulfillment the positive sequence impedance seen by the DR for a fault at the remotest end of the lateral should be compared with the smallest possible positive sequence impedance seen for a fault on the secondary winding of any of the distribution transformers at this lateral. Most distance relay manufacturers provide the availability to choose between any possible combination of phase and ground elements in terms of a mho or a quadrilateral characteristic. However there are manufacturers that restrict the use of mho (resp. quadrilateral) characteristics only to phase or ground elements. For example, one well established manufacturer provides phase elements with a mho characteristic, while quadrilateral characteristics are provided only for the ground elements. Moreover, most manufacturers provide four independent phase/ground elements, whereas there are some special cases where five independent phase/ground distance elements are provided with the relay. In this paper, it is assumed that the DR provides four independent mho and four independent quadrilateral elements, which can interchangeably be used for phase and ground protection. Finally, each phase and ground element has been set with a quadrilateral characteristic. The quadrilateral characteristic has been selected over the mho one because of its advantages, especially in regard with the fault resistance coverage. The setting procedure concerns equally the phase and ground elements and takes into account the infeed effect. This procedure is described below in a detailed manner. Figure 4. Coordination in long radial distribution networks The first zone is set to instantaneously (t 1 0) clear faults occurring within the 85% of the distance between the DR location and the first lateral. Thus, the largest expected fault currents will be interrupted instantaneously and the equipment will be exposed to the worst through-fault damage for the shortest time duration. This is especial critical for the substation transformer which should not be exposed to large through-fault currents. The second zone is set to cover the total impedance (Z 2 ) up to the end of the first lateral. Since the first lateral is protected by the main fuse F1, the second zone is coordinated to operate with a time delay t 2 that is larger than the largest of the total clearing times of this fuse. An appropriate minimum Coordination Time Interval (CTI min ) is taken for this purpose. The third zone is set to cover the total impedance (Z 3 ) up to the end of the second lateral. Again, coordination must be guaranteed between the zone 3 element and the fuse F2. Hence, an appropriate time delay t 3 for the zone 3 operation must be specified. Finally, the fourth zone is set to protect the line up to the end of the third lateral with an appropriate time delay t 4. Note again that in all cases coordination between the main fuse and the fuses on the transformers is assumed at each lateral. If there is a short line section beyond the third lateral or a fourth lateral as in Fig. 2, zone 4 can be extended to cover the main line up to its remotest end including the fourth lateral. If the distribution line has more than four laterals, a second distance relay named DR2 should be installed in the main line, in the section immediately after the third lateral (Fig. 4). Then, DR2 should be coordinated following the same setting philosophy as described previously. Since the phase and ground short-circuits have smaller magnitudes as the fault location moves away from the substation, the clearing times of the downstream fuses will become larger. Thus, although coordination between the DR2 and the fuses beyond the third lateral can easily be achieved, coordination between the DR2 and the DR1 is not so straightforward. By determining the appropriate time delays of the phase and ground elements of the DR2, the required CTI min between the DR1 and DR2 should be preserved. In some cases, this leads to an additional increase of the time delay of a zone element. For example, in Fig. 4 the time delay t 1,4 of the DR1 should be increased to the value t 1,4 in order to keep coordination. However, according to our experience based on protection coordination studies for radial overhead lines in Greece, a sufficient CTI between the protection devices can be achieved even for long lines supplied from a weak external grid. It is obvious that the first distance relay is commanded to protect up to three laterals, while any downstream distance relay, if needed, can protect at maximum four laterals each.

4 This can be used as a guide for determining the quantity of the required distance relays in extremely long lines with a large number of laterals. There is only one limitation concerning the maximum permitted time delay for a fault to be cleared. This limit is imposed from the coordination requirements with the transmission system protection and is shown in Fig. 4 with a dashed-dotted line. This time delay cannot be violated. It should be noticed also that installing DR2 implies installing a new substation with its associated CTs, VTs, and switchgear which is costly at the distribution level. However, the cost of installing a new substation at every four laterals is considerable lower than that of installing directional/differential relays (two at each line section) or from that required to implement a fast and reliable communication network, solutions that may alternatively be applied in order to protect of a distribution system with distributed generators. Most modern distance relay manufacturers provide the load encroachment function. In order to avoid any false trip of the distance relay due to a symmetrical three-phase heavy loading condition, this function has been included in this work. Furthermore, in case that no DG unit is connected to the line, a reclosing operation can be assumed for the distance relay. The reclosing operation proposed in this paper applies the instantaneous disconnection of the whole line by opening the circuit breaker at the beginning of the line if a fault is sensed anywhere on the line. Then, a subsequent time-delayed reclosing is performed assuming that every DG unit has been disconnected in the meantime. IV. SIMULATION RESULTS A. Test System Description The proposed distance protection scheme has been tested on a typical overhead distribution line configuration in Greece, which consists of one radial 20 kv, 50 Hz, 25 km long overhead line shown in Fig. 5. ACSR conductor is used with a cross-section of 95 mm 2 on the first segment, which constantly decreases to 50 mm 2 and 35 mm 2 on the subsequent segments. In most of the laterals, a 16 mm 2 ACSR conductor is used. The total line load is 3.42 MW and 1.99 MVAR. The transmission grid is represented by an equivalent source, having a maximum short-circuit power of 2000 MVA at 150 kv. The feeder is supplied from the external grid through a 150/20 kv distribution transformer. A conventional 1.5 MVA, 20 kv, 50 Hz round-rotor synchronous machine has been assumed as a DG unit, operating with a unity power factor when gridconnected. Standard models available in DigSilent Power Factory 15 have been used for representing the described system. In addition, actual fuse links have been modeled at the laterals and at the primary side of the load transformers. B. Distance Relay Setting At first, the case without DG production has been examined. Phase and ground faults with zero fault resistance have been simulated at critical locations on the line and the maximum total clearing times of the fuses have been determined. Table I summarizes the maximum clearing times of all the main fuses in the network. In general, the single-phase (1Φ) short-circuit resulted to the maximum clearing times. Figure 5. Realistic distribution feeder Figure 6. Phase/ground elements of the DR without considering DG Four zones have been set to cover the line up to its remotest end. These zones are shown with the blue quadrilateral characteristics in the complex impedance plane of Fig. 6. The phase and ground elements have been set to have the same reach, whereas they have different time delays determined from the maximum fuse clearing times plus the minimum required CTI min which is equal to 0.3 s. The positive resistive reach (+R) of the quadrilateral characteristics has been selected to cover a fault resistance that is at maximum equal to four times the positive reactance reach (). This is a quite effective assumption [6] for considering fault resistances in medium voltage distribution systems. It is obvious that both the third and fourth zone reaches far inside the load encroachment area, illustrated with the red line in Fig. 6. Having in mind that the load encroachment holds only for symmetrical three-phase conditions, only three-phase fault conditions with a large fault resistance may not be cleared effectively by the relay. However, such conditions are rare and even smaller fault resistances cannot be sensed from common overcurrent relays without a sensitive earth-fault element. Since no DG production has been assumed up to now, the reclosing element of the distance relay can be set to perform a fast reclosing operation for faults occurring everywhere on the line. This reclosing element is represented by the mho characteristic, shown with the brown circle in Fig. 6, which encircles the whole network.

5 TABLE I. MAXIMUM TOTAL CLEARING TIME (NO DG) Fuse TC time Fault type F Φ F Φ F Φ F Φ Next, the setting procedure has been repeated by considering DG units connected to the line. Three different penetration levels have been examined; 42%, 83%, and 125%, meaning respectively one, two, or three fully rated DG units simultaneous in operation. The DG units have been assumed to produce their 100% rated power because they are conventional synchronous machines, thus the power production is fully controllable and independent from the weather conditions. Moreover, it will be seen in the next subsection that the influence of the penetration level on the distance relay settings is more pronounced as the penetration level gets larger, while the DG unit connection point plays also an important role. Now, the critical factor is how the infeeds affects the reach of the zones. It should be noted that for the DG units to be considered as infeeds, the DG protection should be very thoroughly taken into account meaning that it is important to know if the DG protection will instantaneously disconnect the units or not in case of a fault. The under/over-voltage and under/over-frequency settings suggested from various standards [8], indicate that even for the worst short-circuit conditions, the DG will remain connected for a minimum of 0.1 s. Definitely, there are also other DG protection functions (interconnection relay, overcurrent relay etc) that should be taken into consideration. Since this time delay is in general comparable with the total clearing time of most of the fuses for phase faults and because of the fact that not all the DG units in a distribution system are simultaneously exposed to the worst voltage/frequency/overcurrent conditions during a fault, we consider that the DG units contribute constantly to the fault within the time frame of the distance relay operation. In other words, DG units are considered as infeeds in the protection coordination procedure. The main difference observed when considering DG production in the coordination study is that the phase and ground elements of the distance relay must be set uniquely because of the different contribution of the DG units under different fault types. Table II summarizes the time-distance settings of all the phase (P) and ground (G) elements of the relay as determined based on the three different DG penetration levels. Only the positive reactance reach () is shown, since the resistive reach (+R) is taken equal to four times the reactance one. As a graphical example, Fig. 7 depicts the characteristics of the phase and ground characteristics for the case of two DG units connected to the network simultaneously. In this figure, the blue solid characteristics correspond to the phase elements and the dashed magenta ones to the ground elements. The phase and ground elements operate with different time delays determined from the maximum total clearing times of the main fuses. Table III shows the total clearing times of the main fuses for all the examined penetration levels. TABLE II. TIME-DISTANCE ZONE SETINGS (WITH DG) No DG 1 DG unit 2 DG units 3 DG units P P P P G G G G TABLE III. MAXIMUM TOTAL CLEARING TIME (WITH DG) 1 DG unit 2 DG units 3 DG units Fuse TC TC time TC time Fault type F Φ F Φ F Φ F Φ Figure 7. Phase and ground elements of DR with 2 DG units in operation Obviously, if an active management system was available for this distribution system, different setting groups could be beforehand programmed and stored inside the distance relay. Then, based on the information retrieved from the DG units through communications about their operating status (on/off), the appropriate setting group can be uploaded to the relay. C. Effect of Influencing Quantities In order to investigate the influence of the fault resistance on the performance of the distance relay, we subsequently simulated single-phase and three-phase faults at the end of each zone assuming different values of fault resistances from zero up to R F = 40 Ω. Again, the case with two DG units connected is assumed, to easily compare with the Fig. 7. Fig. 8 (resp. Fig 9) illustrates the modification required in the positive reactance reach setting () of the zone 4 phase (resp. ground) element depending on the fault resistance magnitude and the DG connection point. The resistive reach (+R) is always taken equal to four times the reactive one.

6 Figure 8. Influence of the fault resistance on the reactance reach setting of the phase element Figure 10. Influence of the DG penetration on the reactance reach setting of the phase element Figure 9. Influence of the fault resistance on the reactance reach setting of the ground element The straight horizontal line in both figures corresponds to the reactance reach setting of the zone 4 element, determined when zero DG production and zero fault resistance is assumed. In any other case, the two DG units have been assumed to be simultaneously in operation at various locations; namely from bus B1 to bus B4. As can be seen, there is a clear need to increase the reach setting of the relay when the DG units are connected close to the substation and the fault resistance increases. For DG unit connections away from the substation the reach setting determined for zero DG production and zero fault resistance has not to be increased. Fig. 10 (resp. Fig. 11) depicts the modification required in the positive reactance reach setting () of the zone 4 phase (resp. ground) element depending on the DG penetration level and the DG connection point. Zero fault resistance is assumed now. It can be seen that the reach of the phase element should be increased as the penetration level of the DG units connected close to the beginning of the line increases. The reverse effect holds when the DG units are connected away from the substation. Figure 11. Influence of the DG penetration on the reactance reach setting of the ground element D. Investigation of the Combined Effect An interesting conclusion drawn from the analysis presented in this section is that the infeed effect and the influence of the fault resistance on the relay settings come not so uniformly up as defined in the theory. For example, the underreaching effect due to the intermediate infeeds does not appear when the DG units are connected close to remotest end of the line. A critical reason for that is that the pre-fault load transfer plays a significant role (as in the transmission lines) and this effect is especially pronounced in medium voltage overhead lines with different cross section segments. Additionally, if a considerable DG penetration level and a wide dispersion of generators are assumed, the increased fault resistance combined with the pre-fault load current contribution results to a considerable rotation of the fault impedance in the complex impedance plane. Next, we try to explain the abovementioned combined effect with a simple theoretical analysis based on the circuit shown in Fig. 12. Note that this circuit consists of segments similar with that of the distribution system examined in the previous subsection. The impedance Z seen by the distance relay installed at the location 0 for a fault at the end of the line is given by: Z Z ( 1 1 ) Z ( 1 2) Z (1)

7 where K1 and K2 are the infeed constants: 1 IL1 / IA A 2 I I / I B L1 B A By expressing the impedance of the two line segments in a polar form, we get: Z12 C t (3) Z23 D k Then, the infeed related terms of (1) can be calculated as follows: K1 Z12 A C ( t) (4) K2 Z23 B D ( k) Since the apparent impedance Z is a vector defined by (1), its angle is dominantly dependent on the sign of the angles θ+t and φ+k. In distribution systems these angles are mostly positive, thus resulting to an impedance vector tilted up, as shown in Fig. 13. If the fault resistance R F is added in the analysis, the impedance seen by the relay for a fault at end of the line is given by: Z Z01 ( 1 1) Z12 ( 1 2 ) ( Z23 RF ) (5) Now, the term Z 23 +R F is critical, which in polar form can be defined as: Z R E j (6) 23 F If the angle j has a smaller magnitude than φ, then the term K2( Z23 RF ) F ( j+ ) is a vector that when added to the vector of the apparent impedance, it tilts it down. This is shown, in Fig. 14. To conclude, it is understood that the rotation of the apparent vector is strongly dependent on the magnitude of the fault resistance R F. and on the infeed constants. V. CONCLUSIONS The application of distance relays in distribution systems with distributed generators has been examined in this paper to take advantage of the inherent directionality of the distance protection principle and its independency from the source impedance magnitude. On the other hand, the infeed effect and the influence of the fault resistance on the performance of the distance relay have been analyzed. Some interesting particularities that raised by investigating those effects on the application in distributions systems initiated a theoretical analysis of the phenomena. A simple distance-based protection scheme has been proposed for radial overhead lines. The scheme is intended to preserve the fuse-saving philosophy of the traditional protection system. The methodology has been applied effectively to a realistic distribution system with DG production. An extension of this scheme to be applied on extremely long radial lines has been further proposed. (2) Figure 12. Simple illustrative system Figure 13. Infeed effect projected on the relay characteristic Figure 14. Combined infeed anf fault resistance effect REFERENCES [1] J. M. Gers, E. J. Holmes. Protection of Electricity Distribution Networks. London: IET, 2004, p [2] M. Geidl, Protection of Power Systems with Distributed Generation - State of the Art. ETH Technical Report. [3] V. C. Nikolaidis, E. Papanikolaou, A. S. Safigianni, "A Communication-Assisted Overcurrent Protection Scheme for Radial Distribution Systems With Distributed Generation," IEEE Trans.Smart Grid, Vol. 7, Issue 1, pg , Jan [4] I. Chilvers, N. Jenkins and P. Crossley, Distance relaying of 11kV circuits to increase the installed capacity of distributed generation, IEE Proc.-Gener. Transm. Distrib., Vol. 152, No. 1, Jan [5] A. Sinclair, D. Finney, D. Martin, and P. Sharma, Distance protection in distribution systems: How it assists with integrating distributed resources, in 65th Annual Conference for Protective Relay Engineers, [6] J. Chang, L. Gara, Y. Kyosev, P. Fong, Application of a Multifunctional Distance Protective IED in a 15KV Distribution Network, 66th Annual Conference for Protective Relay Engineers, CPRE 2013, pp [7] G. Ziegler. Numerical Distance Protection. Principles and Applications. Siemens, [8] W. Hartmann. Distributed Generation Protection & Control. Including IEEE 1547, Green Energy and Microgrids. IEEE PES San Fransisco Technical Report.

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Time-current Coordination

Time-current Coordination 269 5.2.3.1 Time-current Coordination Time that is controlled by current magnitude permits discriminating faults at one location from another. There are three variables available to discriminate faults,

More information

PROTECTION of electricity distribution networks

PROTECTION of electricity distribution networks PROTECTION of electricity distribution networks Juan M. Gers and Edward J. Holmes The Institution of Electrical Engineers Contents Preface and acknowledgments x 1 Introduction 1 1.1 Basic principles of

More information

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes Transmission Line Protection Objective General knowledge and familiarity with transmission protection schemes Transmission Line Protection Topics Primary/backup protection Coordination Communication-based

More information

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS Hannu LAAKSONEN ABB Oy Finland hannu.laaksonen@fi.abb.com ABSTRACT Medium-voltage (MV) network short-circuit protection operation time delays have

More information

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June

More information

Line Protection Roy Moxley Siemens USA

Line Protection Roy Moxley Siemens USA Line Protection Roy Moxley Siemens USA Unrestricted Siemens AG 2017 siemens.com/digitalgrid What is a Railroad s Biggest Asset? Rolling Stock Share-holders Relationships Shipping Contracts Employees (Engineers)

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Transmission Protection Overview

Transmission Protection Overview Transmission Protection Overview 2017 Hands-On Relay School Daniel Henriod Schweitzer Engineering Laboratories Pullman, WA Transmission Line Protection Objective General knowledge and familiarity with

More information

Differential Protection for Microgrids with Embedded Generations

Differential Protection for Microgrids with Embedded Generations Differential Protection for Microgrids with Embedded Generations Paul Moroke Dept. of Electrical Engineering Tshwane University of Technology Pretoria, South Africa paulmoroke@gmail.com Abstract The permeation

More information

Notes 1: Introduction to Distribution Systems

Notes 1: Introduction to Distribution Systems Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission

More information

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants Martin Best and Stephanie Mercer, UC Synergetic, LLC Abstract Wind generating plants employ several

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS Abdelrahman AKILA Ahmed HELAL Hussien ELDESOUKI SDEDCO Egypt AASTMT Egypt AASTMT Egypt Abdurrahman.akela@gmail.com ahmedanas@aast.edu hdesouki@aast.edu

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

Adaptive Relaying of Radial Distribution system with Distributed Generation

Adaptive Relaying of Radial Distribution system with Distributed Generation Adaptive Relaying of Radial Distribution system with Distributed Generation K.Vijetha M,Tech (Power Systems Engineering) National Institute of Technology-Warangal Warangal, INDIA. Email: vijetha258@gmail.com

More information

Protection of Microgrids Using Differential Relays

Protection of Microgrids Using Differential Relays 1 Protection of Microgrids Using Differential Relays Manjula Dewadasa, Member, IEEE, Arindam Ghosh, Fellow, IEEE and Gerard Ledwich, Senior Member, IEEE Abstract A microgrid provides economical and reliable

More information

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 Prepared by System Planning Division Transmission Planning Department PJM 2016 Table of Contents Table of Contents Approval...6

More information

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME Donald M. MACGREGOR Electrocon Int l, Inc. USA eii@electrocon.com Venkat TIRUPATI Electrocon Int l, Inc. USA eii@electrocon.com Russell

More information

Protecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved.

Protecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved. Protecting Feeders With Distributed Resource Scott Elling HDR Inc. 2015 HDR, all rights reserved. Background Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

More information

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 PRC-025-1 Generator Relay Loadability A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities

More information

Distance Protection of Cross-Bonded Transmission Cable-Systems

Distance Protection of Cross-Bonded Transmission Cable-Systems Downloaded from vbn.aau.dk on: April 19, 2019 Aalborg Universitet Distance Protection of Cross-Bonded Transmission Cable-Systems Bak, Claus Leth; F. Jensen, Christian Published in: Proceedings of the 12th

More information

NEW DESIGN OF GROUND FAULT PROTECTION

NEW DESIGN OF GROUND FAULT PROTECTION NEW DESIGN OF GROUND FAULT PROTECTION J. Blumschein*, Y. Yelgin* *SIEMENS AG, Germany, email: joerg.blumschein@siemens.com Keywords: Ground fault protection, directional element, faulted phase selection

More information

Protection Challenges for Transmission Lines with Long Taps

Protection Challenges for Transmission Lines with Long Taps Protection Challenges for Transmission Lines with Long Taps Jenny Patten, Majida Malki, Quanta Technology, Matt Jones, American Transmission Co. Abstract Tapped transmission lines are quite common as they

More information

Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation

Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation Harag Margossian 1, Florin Capitanescu 2, Juergen Sachau 3 Interdisciplinary Centre for Security, Reliability

More information

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis 1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

PROTECTION SIGNALLING

PROTECTION SIGNALLING PROTECTION SIGNALLING 1 Directional Comparison Distance Protection Schemes The importance of transmission system integrity necessitates high-speed fault clearing times and highspeed auto reclosing to avoid

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

What s New in C TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines

What s New in C TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines What s New in C37.113 TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines This paper is a product of the IEEE PSRC D36 Working Group. The working group consisted of the following

More information

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Level 6 Graduate Diploma in Engineering Electrical Energy Systems 9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,

More information

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage POWERENG 2007, April 12-14, 2007, Setúbal, Portugal Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage Amin Helmzadeh, Javad Sadeh and Omid Alizadeh

More information

Analysis of Phenomena, that Affect the Distance Protection

Analysis of Phenomena, that Affect the Distance Protection Analysis of Phenomena, that Affect the Distance Protection C. Gallego, J. Urresty, and J. Gers, IEEE Abstract--This article presents the impact of changes in distance protection reach and zone changes

More information

Babak Enayati National Grid Thursday, April 17

Babak Enayati National Grid Thursday, April 17 2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April

More information

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection Engineered Solutions for Power System Protection, Automaton and Control APPLICATION NOTE Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection 180622 Abstract This

More information

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Dynamic Model Of 400 Kv Line With Distance Relay. Director Research, The MRPC Company, Hyderabad, India 2

Dynamic Model Of 400 Kv Line With Distance Relay. Director Research, The MRPC Company, Hyderabad, India 2 Dynamic Model Of 400 Kv Line With Distance Relay Ramleela Khare 1, Dr Filipe Rodrigues E Melo 2 1 Director Research, The MRPC Company, Hyderabad, India 2 Assoc. Professor Commerce, St. Xavier s College

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

Impedance protection on power transformer.

Impedance protection on power transformer. Impedance protection on power transformer www.siemens.com/siprotec5 SIPROTEC 5 Application Impedance Protection on Power Transformer APN-045, Edition 1 Content 1...3 1.1 Introduction...3 1.2 Application

More information

Using a Multiple Analog Input Distance Relay as a DFR

Using a Multiple Analog Input Distance Relay as a DFR Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at

More information

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS S1. Standard Interconnection Methods with Typical Circuit Configuration for Single or Multiple Units Note: The protection requirements

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

CP CU1. Coupling unit for line and ground testing

CP CU1. Coupling unit for line and ground testing CP CU1 Coupling unit for line and ground testing Line and ground test system CPC 100 The CPC 100 is a multifunctional test set for primary assets. When combined with the CP CU1 it covers the following

More information

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation TSAI-HSIANG CHEN a NIEN-CHE YANG b Department of Electrical Engineering National Taiwan University

More information

Distance Protection in Distribution Systems: How It Assists With Integrating Distributed Resources

Distance Protection in Distribution Systems: How It Assists With Integrating Distributed Resources 1 Distance Protection in Distribution Systems: How It Assists With Integrating Distributed Resources David Martin and Pankaj Sharma, Hydro One Networks Inc. Amy Sinclair and Dale Finney, Schweitzer Engineering

More information

DIRECTIONAL PROTECTION

DIRECTIONAL PROTECTION UNIVERSITY OF LJUBLJANA FACULTY OF ELECTRICAL ENGINEERING DIRECTIONAL PROTECTION Seminar work in the course Distribution and industrial networks Mentor: Prof. Grega Bizjak Author: Amar Zejnilović Ljubljana,

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

Utility Interconnection and System Protection

Utility Interconnection and System Protection Utility Interconnection and System Protection Alex Steselboim President, Advanced Power Technologies, Inc. Utility paralleling vs. isolated operation. Isochronous kw load sharing Reactive power (VAR) sharing

More information

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng.

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng. Distance Protection for Distribution Feeders Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng. Why use distance protection for distribution feeders? Distance protection is mainly used for protecting

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR

More information

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System

More information

Advanced Paralleling of LTC Transformers by VAR TM Method

Advanced Paralleling of LTC Transformers by VAR TM Method TAPCHANGER CONTROLS Application Note #24 Advanced Paralleling of LTC Transformers by VAR TM Method 1.0 ABSTRACT Beckwith Electric Company Application Note #11, Introduction of Paralleling of LTC Transformers

More information

Transmission System Phase Backup Protection

Transmission System Phase Backup Protection Reliability Guideline Transmission System Phase Backup Protection NERC System Protection and Control Subcommittee Draft for Planning Committee Approval June 2011 Table of Contents 1. Introduction and Need

More information

How to maximize reliability using an alternative distribution system for critical loads

How to maximize reliability using an alternative distribution system for critical loads White Paper WP024001EN How to maximize reliability using an alternative distribution system for critical loads Executive summary The electric power industry has several different distribution topologies

More information

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES C.E.T. Foote*, G.W. Ault*, J.R. McDonald*, A.J. Beddoes *University of Strathclyde, UK EA Technology Limited, UK c.foote@eee.strath.ac.uk

More information

Southern Company Interconnection Requirements for Inverter-Based Generation

Southern Company Interconnection Requirements for Inverter-Based Generation Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS 1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com

More information

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third one of Distance Relays M. Azari, M. Ojaghi and K. Mazlumi* Electrical Engineering Department University of anjan anjan,

More information

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) 1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1

More information

G. KOEPPL Koeppl Power Experts Switzerland

G. KOEPPL Koeppl Power Experts Switzerland PS3: Substation Design: New Solutions and Experiences Bus-Node Substation A Big Improvement in Short-Circuit and Switching Properties at Reduced Substation Costs G. KOEPPL Koeppl Power Experts Switzerland

More information

ISSN: Page 298

ISSN: Page 298 Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006 October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date

More information

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 Charles J. Mozina, Consultant Beckwith Electric Co., Inc. www.beckwithelectric.com I. Introduction During the 2003 blackout,

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

Power System Protection Where Are We Today?

Power System Protection Where Are We Today? 1 Power System Protection Where Are We Today? Meliha B. Selak Power System Protection & Control IEEE PES Distinguished Lecturer Program Preceding IEEE PES Vice President for Chapters melihas@ieee.org PES

More information

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D Electricity Ten Year Statement November 2017 01 Electricity Ten Year Statement November 2017 001 Appendix D 1 Short-circuit currents 02 2 Short-circuit current terminology 04 3 Data requirements 07 4 Fault

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

Line protection with transformer in the protection zone

Line protection with transformer in the protection zone Line protection with transformer in the protection zone www.siemens.com/siprotec5 Three-end line protection with transformer in the protection range SIPROTEC 5 Application Three-end line protection with

More information

BED INTERCONNECTION TECHNICAL REQUIREMENTS

BED INTERCONNECTION TECHNICAL REQUIREMENTS BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2

More information

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays

More information

ECE 528 Understanding Power Quality

ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 22 1 Today Homework 5 questions Homework 6 discussion More on

More information

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8] Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant

More information

Transmission Line Applications of Directional Ground Overcurrent Relays. Working Group D24 Report to the Line Protection Subcommittee January 2014

Transmission Line Applications of Directional Ground Overcurrent Relays. Working Group D24 Report to the Line Protection Subcommittee January 2014 Transmission Line Applications of Directional Ground Overcurrent Relays Working Group D24 Report to the Line Protection Subcommittee January 2014 Working Group Members: Don Lukach (Chairman), Rick Taylor

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Protection of Extra High Voltage Transmission Line Using Distance Protection

Protection of Extra High Voltage Transmission Line Using Distance Protection Protection of Extra High Voltage Transmission Line Using Distance Protection Ko Ko Aung 1, Soe Soe Ei Aung 2 Department of Electrical Power Engineering Yangon Technological University, Insein Township

More information

The Advantages and Application of Three Winding Transformers

The Advantages and Application of Three Winding Transformers The Advantages and Application of Three Winding Transformers MSc, CEng, FIEE, FIMechE, FIPENZ Principal, Sinclair Knight Merz Abstract Although seldom used in Australia and New Zealand, three winding transformers

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

Protection of distributed generation interfaced networks

Protection of distributed generation interfaced networks Protection of distributed generation interfaced networks Manjula Dewadasa B.Sc (Hons) in Electrical Engineering A Thesis submitted in partial fulfilment of the requirements for the degree of Doctor of

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

IMPACT OF SERIES COMPENSATION ON THE PERFOMANCE OF DISTANCE PROTECTION ON ESKOM TRANSMISSION GRID. Sihle Qwabe

IMPACT OF SERIES COMPENSATION ON THE PERFOMANCE OF DISTANCE PROTECTION ON ESKOM TRANSMISSION GRID. Sihle Qwabe i IMPACT OF SERIES COMPENSATION ON THE PERFOMANCE OF DISTANCE PROTECTION ON ESKOM TRANSMISSION GRID Sihle Qwabe The dissertation submitted in fulfillment of the requirements for the degree of Master of

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Appendix D Fault Levels

Appendix D Fault Levels Appendix D Fault Levels Page 1 Electricity Ten Year Statement November 2013 D.1 Short Circuit Currents Short Circuit Currents Three phase to earth and single phase to earth short circuit current analyses

More information

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS AND MEDIUM-SIZE FACILITIES (5,000-25,000KW) CONNECTED

More information

Chapter 10: Compensation of Power Transmission Systems

Chapter 10: Compensation of Power Transmission Systems Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome

More information

Performance Evaluation of Mho and Quadrilateral Characteristic Relays on UPFC Incorporated Transmission Line

Performance Evaluation of Mho and Quadrilateral Characteristic Relays on UPFC Incorporated Transmission Line International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 7, Number 8 (2014), pp. 827-835 International Research Publication House http://www.irphouse.com Performance Evaluation

More information

9 Overcurrent Protection for Phase and Earth Faults

9 Overcurrent Protection for Phase and Earth Faults Overcurrent Protection for Phase and Earth Faults Introduction 9. Co-ordination procedure 9.2 Principles of time/current grading 9.3 Standard I.D.M.T. overcurrent relays 9.4 Combined I.D.M.T. and high

More information