1 Part 3 The Ins and Outs of Basic Sch ematic Symbols A practical approach to reading and understanding the schematic diagrams used to explain how HVACR systems operate. B y H o w a r d L. P e m p e r, C M S Editor s Note: Due to the length of Part 3 and the number of diagrams associated with it, this last part has been separated. To ensure all of the information gets into readers hands, a Part 4 has been added to the series and will appear in the May 2011 issue of RSES Journal. RUNGS OF A LADDER Figure 1 Figure 2 Figure 3 10 RSES Journal APRIL 2011 RUNGS OF A LADDER The previous article discussed several components that are used on schematic diagrams. Part 3 incorporates these elements into complete diagrams. The HVACR industry uses three basic diagrams for equipment. First, and probably least used, is the label diagram; then the installation diagram; and finally the one most often used is the ladder or schematic diagram. Figure 1 is an example of a very basic label diagram of a simple condensing unit. It has a contactor, condenser fan motor, pressure controls and terminal blocks. Note that the components are drawn as they would appear physically. The label diagram does not use symbols to represent parts. It relies on the physical description of the part itself. Figure 2 is a basic form of an installation diagram. It is primarily used for wiring one component to another. The thermostat to an air-conditioner as shown in Figure 2, are just the external terminals. It does not help in diagnosing any problems. As was stated in Part 1, most lines on an installation diagram are dashed. These normally represent wires that are field-installed.

2 "c" Figure 5a "a" "e" Figure 5b "d" Figure 4 "b" CAP CAPACITOR CC COMPRESSOR CONTACTOR CCHR CRANKCASE HEATER CFM CONDENSER FAN MOTOR COMP COMPRESSOR DISC DISCONNECT FPS FREEZE PROTECTION SWITCH FU FUSE GND GROUND GV GAS VALVE Figure 4 Legend IFM INDOOR FAN MOTOR IFMR INDOOR FAN MOTOR RELAY IGNC IGNITION CONTROL IGNCR IGNITION CONTROL RELAY HPS HIGH PRESSURE SWITCH LPS LOW PRESSURE SWITCH LS LIMIT SWITCH RS ROLLOUT SWITCH TB TERMINAL BOARD TRAN TRANSFORMER Figure 3 is the ladder diagram of Figure 1. The reason it is called a ladder diagram is because the components are normally drawn in a horizontal plane while the power supply wires are vertical. Together, they look like rungs on a step ladder. These diagrams simplify the circuits, which will aid in diagnosing any electrical problem with the unit. The contactor coil C-1 controls the two sets of contacts marked C-1 terminals 11, 21, 12 and 22. These are at line-voltage potential. The contactor coil C-1 is controlled by the terminals C and Y1 on the terminal block TB-2. These are connect- Figure 6 ed to an external thermostat that is not shown. These are in the low-voltage circuit. The compressor is protected by the low-pressure switch LPS1 and the high-pressure switch HPS1. Note that the safety switches are wired in a series configuration. Complex diagrams in basics At first glance, most schematics look complex, but isolating or breaking them down into separate areas helps make troubleshooting easier. Figure 4 represents a generic package rooftop gas/electric unit and is more complex, but can be broken down into four or five basic parts. The two most important divisions of a schematic that most manufacturers do not deviate from is the letter a at the top of Figure 4, normally considered the high-voltage section; and the letter b, usually the low-voltage section. The normal breaking point between the low and high voltage of any schematic is a transformer, which is represented by the letter e. Remember there can be more than one transformer on a schematic, depending upon the equipment. The letter c is considered the line side of the diagram, which is normally where the controls and switches are drawn; and the letter d represents the load side where the power-consuming components are located. Several components on the diagram only have a letter next to them; each of which can be deciphered using an accompanying legend. APRIL 2011 RSES Journal 11

3 Figure 7 Figure 13 Figure 8 Figure 9 Figure 10 Figure 14 Figure 11 Figure 12 Now, to put all of these components together: The series of numbers listed vertically from the top of most diagrams to the bottom represents line-side numbering. In Figure 5a, line 1 is the disconnect switch; and in Figure 5b, line 22 is the capacitor for the condenser-fan motor (CFM). Manufacturers will frequently use these line numbers when describing the sequence of operations. The numbers grouped together at specific points or at specific loads on the right side of a diagram represent load-side numbering. In Figure 6, the numbers 10, 13, 17 and 21 depict the safety controls and the compressor contactor (CC). Each of these numbers represents a line that corresponds to a switch or control that the coil operates. Figure 7 shows the CC is controlling N/O contacts CC 1 and CC 2 to start the compressor; and CC 4 at line 21 which is a N/O set of open contacts. This in turn energizes on the CFM, as is illustrated in Figure 8. Lastly, the compressor contactor CC also is controlling CC 3 at line 17. Note that the number is underlined. Any time an underlined number on the load side of a schematic appears, it will indicate an N/C set of contacts. This switch will open when the compressor is energized, de-energizing the crankcase heater (CCHR) shown in Figure 9. The next controlling relay shown in Figure 10 is the indoor-fan-motor relay (IFMR), which is used to control the indoor-fan-motor s speed from heating (low speed) to cooling (high speed). This device controls a single-pole double-throw (SPDT) set of contacts at lines 28 and 30. Note in Figure 4 line 28 by the IFMR is underlined, so is N/C and will switch over when the coil energized. The last controlling device is the ignition control (IGNC), which closes the gas valve (IGNCR 2 ) at line 51, as illustrated in Figure 11. The IFM is turned on after a certain period of time and turns on the fan at line 28. This is determined by the IGNCR 1, shown in Figure 12. Note that 12 RSES Journal APRIL 2011

4 indoor outdoor Figure 15 Figure 16 Figure 17 the controlling coil can be at a different position on the diagram than the contacts, as illustrated in the previous diagrams. The last item to connect to this unit to make it run would be a thermostat. Figure 13 is an illustration of a generic thermostat connected to TB-1. To facilitate the location of components used on schematics, some manufacturers will place a component layout diagram next to the wiring diagram. This speeds up finding a failed element or component of the circuit. Figure 14 is an example of a component diagram and a legend. Figure 15 is diagram of hypothetical generic heat-pump system. It is a combination of a ladder, installation and component diagram. Starting with the circuit on the right side at the top, we find that the compressor has a three-phase power supply. It has a crankcase heater that is controlled by the contactor s open contacts. Figure 16 illustrates that when the contacts are open, current flows through the crankcase heater (which per this legend is now referenced as CCHTR) and the compressor s windings, maintaining enough temperature in the compressor to keep the oil and refrigerant separate. When the contactor s contacts close the CCHTR is de-activated. APRIL 2011 RSES Journal 13

5 Figure 18 Figure 19 a b c O C. R d e f DFT. R C Editors Note: These points are from Figure 18 and RSES Journal APRIL 2011 Figure 17 illustrates the single-phase outdoor-fan motor (OFM). Note that the motor is energized when power is applied to the compressor. However, this is a heat-pump system, and the fan motor must be off when in defrost. This is accomplished with the N/C defrost relay (DR) contacts. The last item on the outdoor section of this heat pump is the printed circuit board PCB This control s defrost, reversing valve and the compressor are shown in Figure 18. There are a few items of note about the PCB. The first is some of the hardwired connections that are made to push on connectors right on the board, such as the reversing-valve solenoid (RVS). It is made to terminals O(a) and C(b). The DFT (defrost thermostat) is connected to the PCB at points R(c)and DFT(d). There are a number of devices that cannot be removed from the board and can be somewhat difficult to troubleshoot. Deciding which circuit controls each component can be figured out by inspecting the diagram of the PCB. The next series of hard-wired devices are the safety controls and the contactor, which are shown in Figure 19. The high-pressure switch is wired directly to the contactor and the low-pressure switch is wired to the PCB at R(e). The other side of the contactor is wired to the PCB at C(f). The indoor section of Figure 15 is shown more clearly in Figure 20, where several different circuits not yet discussed are incorporated in this portion of the system.

6 Figure 21 illustrates the operation of the first sequencer (SEQ-1), which has a two-fold function. The first is when W2 is energized and the SEQ-1 starts its timing process. Upon completion of the timing the contacts SEQ-1 close. This causes the HTR-1 is energized. Simultaneously, the fan motor (FM) is energized in medium speed. If more heat is required, the next two sequencers, SEQ-2 and SEQ-3, will be energized causing the heaters HTR-2 and HTR-3 to become energized, as is shown in Figure 22. Next month, Part 4 will break down the more complex schematic of a ficticious two-stage heating/cooling rooftop unit. Figure 20 Howard L. Pemper, CMS, is the Supervisor of Training and Technical Support for Malden, MA-based Distributor Corp. He is a former RSES E&E Board Member and Editor of the Electrical Training Manuals. He can be reached at hlpemper@rcn.com. Figure 21 Figure 22 APRIL 2011 RSES Journal 15

SAMPLE. Electrical Diagrams C H A P T E R 7

SAMPLE. Electrical Diagrams C H A P T E R 7 H A P T E 7 Electrical Diagrams INTODUTION Quite often, when you encounter a problem with a piece of HVA equipment, the problem turns out to be electrical in nature. If you have a clear understanding of

More information

Electrical Controls. Isaac Queen

Electrical Controls. Isaac Queen Electrical Controls Isaac Queen iqueen@atn.org www.atn.org 1 Contact blocks include normally open (NO), normally closed (NC), or both NO and NC contacts. 2 A joystick is used to control many different

More information

AWUF Series. Wall-Mount Air Handler 1½ to 3 Tons. Contents. Product Features

AWUF Series. Wall-Mount Air Handler 1½ to 3 Tons. Contents. Product Features Series Wall-Mount Air Handler 1½ to 3 Tons Contents Nomenclature...2 Accessories...2 Product Specifications...3 Dimensions...6 Airflow Data...8 Wiring Diagram...9 Product Features Equipped with a Check

More information

C0330, C0530, C0630, C0830, C1030 Service Parts

C0330, C0530, C0630, C0830, C1030 Service Parts This part list contains the service parts for the air cooled, water cooled and remote air cooled C00, C00, C00, C00, C00 ice machines. There was a change to panels and the C00 air cooled condenser in late

More information

ADDENDUM NO. 4 November 15, Page 1

ADDENDUM NO. 4 November 15, Page 1 ADDENDUM NO. 4 November 15, 201 8 Page 1 PROJECT MANUAL FOR CONSTRUCTION OF HVAC REPLACEMENT FOR NORTH OCONEE HIGH SCHOOL FOR OCONEE COUNTY SCHOOLS WATKINSVILLE, GEORGIA DATED: SEPTEMBER 14, 2018 CUNNINGHAM,

More information

C0330, C0530, C0630, C0830, C1030 Service Parts

C0330, C0530, C0630, C0830, C1030 Service Parts This part list contains the service parts for the air cooled, water cooled and remote air cooled C00, C00, C00, C080, C00 ice machines. To avoid costly and time consuming errors, double check the model

More information

Technical Information

Technical Information Date of last update: Aug-14 Ref: REFRIGERATION - CONTROLLING DIGITAL SCROLL Application Engineering Europe 1 Introduction Refrigeration applications such as retail and convenience stores are requesting

More information

ECET 211 Electric Machines & Controls Lecture 2-1 (Part 1 of 3) Symbols and Drawing for Electric Motor Control Systems

ECET 211 Electric Machines & Controls Lecture 2-1 (Part 1 of 3) Symbols and Drawing for Electric Motor Control Systems ECET 211 Electric Machines & Controls Lecture 2-1 (Part 1 of 3) Symbols and Drawing for Electric Motor Control Systems Text Book: Chapter 2. Understanding Electrical Drawings, Electric Motors and Control

More information

Unit 2 Electrical Circuit Diagrams

Unit 2 Electrical Circuit Diagrams 2.1. Electrical Circuit Definition Unit 2 Electrical Circuit Diagrams In general terms, a circuit can be described as any group of electrical or electronic devices connected together by conductors. Conductors

More information

Closed loop Heat Temperature Thermostat Heater Voltage to Heater

Closed loop Heat Temperature Thermostat Heater Voltage to Heater EET 273 Spring 2017 HW1 1. Control Terminology For the following 3 systems, explain which element of the system corresponds to which control element. An open loop system may not have all of the elements

More information

KeyTrain Applied Technology Course Objectives, Outlines and Estimated Times of Completion

KeyTrain Applied Technology Course Objectives, Outlines and Estimated Times of Completion KeyTrain Applied Technology Course Objectives, Outlines and Estimated Times of Completion Applied Technology Course Description: KeyTrain's Applied Technology course teaches the ability to solve work-place

More information

Commercial Refrigeration Price List

Commercial Refrigeration Price List Commercial Refrigeration Price List KPL3_004_073118 Effective Date: August 1, 2018 Krack Commercial Refrigeration Price Lists are updated quarterly; January, April, July and October; and posted on our

More information

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION GUIDE SPECIFICATIONS 256920-UGS-A-0506 Simplicity Intelli-Comfort Optional Control in 3-25 Ton Packaged Units GENERAL DESCRIPTION CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP Equipment with Simplicity

More information

McQuay. Commercial Unitary Rooftop Cooling with Gas Heat. LGA 088, 100 Design 1. Last Manufactured: 2004

McQuay. Commercial Unitary Rooftop Cooling with Gas Heat. LGA 088, 100 Design 1. Last Manufactured: 2004 Replacement Parts List No. 700021800 New 08/2011 McQuay Commercial Unitary Rooftop Cooling with Gas Heat LGA 088, 100 Design 1 Last Manufactured: 2004 To find your Daikin Applied parts distributor, call

More information

Take for instance this circuit:

Take for instance this circuit: Ladder diagrams Ladder diagrams are specialized schematics commonly used to document industrial control logic systems. They are called "ladder" diagrams because they resemble a ladder, with two vertical

More information

SmartZone-2 & SmartZone-4

SmartZone-2 & SmartZone-4 SmartZone-2 & SmartZone-4 Quick-Start Guide UPDATED 2011-7-26 This guide is intended to give the installer a brief set of instructions about how to set up the XCI Zoning SmartZone System. For more detailed

More information

ECET 211 Electric Machines & Controls Lecture 2-1 (Part 1 of 3) Symbols and Drawing for Electric Motor Control Systems

ECET 211 Electric Machines & Controls Lecture 2-1 (Part 1 of 3) Symbols and Drawing for Electric Motor Control Systems ECET 211 Electric Machines & Controls Lecture 2-1 (Part 1 of 3) Symbols and Drawing for Electric Motor Control Systems Text Book: Chapter 2. Understanding Electrical Drawings, Electric Motors and Control

More information

2017 Price List. Krack Corporation Hussmann Corporation St. Charles Rock Rd. Bridgeton, MO Phone: Fax:

2017 Price List. Krack Corporation Hussmann Corporation St. Charles Rock Rd. Bridgeton, MO Phone: Fax: Expires: 1/1/2018 2017 Price List Changes since the last Price List: 3.5% Price Increase Effective August 15th Correct SV evaporators pricing. Changes on previous revision: Correct rupture disc assembly

More information

electrical components

electrical components electrical components solenoid valves for air-cooled machines 4 9090 bin thermostat Gala DP0-40, Pulsar P5-45 909 thermostat for defrosting Gala DP0-70_, Pulsar P45-45 0074 005 90577 thermostat for defrosting

More information

Product Launch Package. Refrigeration Marketing Units Emerson Climate Technologies Europe

Product Launch Package. Refrigeration Marketing Units Emerson Climate Technologies Europe Digital Receiver Unit - HLR Product Launch Package Refrigeration Marketing Units Emerson Climate Technologies Europe Emerson Climate Technologies Existing Digital Range Application Outdoor Installations,

More information

WIRING DIAGRAM MANUAL Split System Heat Pump

WIRING DIAGRAM MANUAL Split System Heat Pump Split System Heat Pump NXH6 Safety Labeling and Signal Words DANGER, WARNING, AUTION, and NOTE The signal words DANGER, WARNING, AUTION, and NOTE are used to identify levels of hazard seriousness. The

More information

Introduction to PLC and Ladder Logic Programming

Introduction to PLC and Ladder Logic Programming Introduction Introduction to PLC and Ladder Logic Programming A PLC (Programmable Logic Controller) is an industrial computer used for automation of electromechanical processes, such as control of machinery

More information

Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting

Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting FANs 216, 121 Technical Bulletin R48 Issue Date 0695 Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting Table of Contents Mounting... 1 Output Control... 2 Wiring...

More information

MODEL 421 Over/Under Motor Load Monitor

MODEL 421 Over/Under Motor Load Monitor MODEL 421 Over/Under Motor Load Monitor Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or, Single-phase or 3-phase Built-in Trip and Restart

More information

FDM Medium Voltage Controller

FDM Medium Voltage Controller 1-1 LMR PLUS Product Description For over 50 years, EATON Corporation has been the industry leader in Medium Voltage Motor Control. The FDM Medium Voltage Fire Pump Controller is based on the AMPGARD controller

More information

What is VC-VH? Old capacitor voltage terminology. Terminals on capacitor

What is VC-VH? Old capacitor voltage terminology. Terminals on capacitor What is VC-VH? Old capacitor voltage terminology Terminals on capacitor VC=Voltage common; VH= voltage hermetic 2-Stage Board Voltage constantly monitored at compressor run capacitor. Looks for voltage

More information

Click Here for Live Online Chat

Click Here for Live Online Chat Click Here for Live Online Chat Spare parts suitable for: TV Spare parts suitable for ice-cube machines electrical components solenoid valves for air-cooled machines 4 9090 bin thermostat Gala DP0-40,

More information

Comparison that shows the differences between a PFD and P&ID :

Comparison that shows the differences between a PFD and P&ID : Comparison that shows the differences between a PFD and P&ID : PFD P&ID Used during construction? No Yes* Shows all process and service piping? No Yes Indicates presence of all controls? No Yes Shows all

More information

Over or Under Current. Over and Under Current Monitor. Current Transducer. Current Indicator. DIN Rail Mounting Current Monitors

Over or Under Current. Over and Under Current Monitor. Current Transducer. Current Indicator. DIN Rail Mounting Current Monitors Selection Guide...8.2 Over or Under ECS... 8.4 TCS... 8.8 Over and Under Monitor ECSW... 8.6 Transducer TCSA... 8.10 DCSA... 8.12 Indicator LCS... 8.14 LPM... 8.14 DIN Rail Mounting CM-SFS CM-SRS.1 CM-SRS.2

More information

True. Why. Truly. Today s current green-energy movement has stimulated

True. Why. Truly. Today s current green-energy movement has stimulated Why True RMS Truly Matters Increasingly energy-efficient HVAC equipment is changing the way systems are maintained and making true-rms meters a must -have for every service professional. B y G r e g J

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION SECTION 15190 MECHANICAL IDENTIFICATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Identification of mechanical products installed under Division 15. B. Related Sections: 1.02 REFERENCES 1.

More information

One line and Three line diagrams Schematics Wiring Diagrams Logic ladders Ancillary prints Pictorial instructions

One line and Three line diagrams Schematics Wiring Diagrams Logic ladders Ancillary prints Pictorial instructions One line and Three line diagrams Schematics Wiring Diagrams Logic ladders Ancillary prints Pictorial instructions One line diagram (1) One line diagrams will typically show in a simple fashion an over

More information

Copeland Digital Scroll

Copeland Digital Scroll Copeland Digital Scroll Technology & Advantages Presented by: Bruce Hilsabeck Application Engineer Copeland Australia / New Zealand Introduction 1. Scroll Compressor Basics 2. Digital Compressor Technology

More information

W7100A-E Discharge Air Controller

W7100A-E Discharge Air Controller W7100A-E W7100A-E Discharge Air Controller The microprocessor based W7100 Discharge Air Controller maintains an average discharge air (DA) temperature in variable air volume (VAV) cooling systems by modulating

More information

PARTS CATALOG R410A. No. OCB603 REVISED EDITION-A. March 2016 HFC SUZ-KA25VA5.TH-ET SUZ-KA35VA5.TH-ET SUZ-KA50VA5.TH-ET SUZ-KA60VA5.

PARTS CATALOG R410A. No. OCB603 REVISED EDITION-A. March 2016 HFC SUZ-KA25VA5.TH-ET SUZ-KA35VA5.TH-ET SUZ-KA50VA5.TH-ET SUZ-KA60VA5. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PARTS CATALOG R410A [Model Name] SUZ-KA5VA5 SUZ-KA35VA5 SUZ-KA50VA5 SUZ-KA60VA5 SUZ-KA71VA5 [Service Ref.] SUZ-KA5VA5.TH SUZ-KA5VA5.TH-ET SUZ-KA35VA5.TH SUZ-KA35VA5.TH-ET

More information

SECTION MECHANICAL IDENTIFICATION. 1. Identification of mechanical products installed under Division 15.

SECTION MECHANICAL IDENTIFICATION. 1. Identification of mechanical products installed under Division 15. SECTION 15190 MECHANICAL IDENTIFICATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Identification of mechanical products installed under Division 15. B. Related Sections: 1. Section 09900 -

More information

PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES

PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Assign unit identification numbers to operating units of equipment within a class or subclass during the design phase of new buildings, additions,

More information

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards The Solo, Select and Sync PWM boards provide a pulse-width modulated (PWM) signal to the EC motor to control fan speed.

More information

PREVIEW COPY. Table of Contents. Troubleshooting with Electrical Schematics...3. Troubleshooting with Building Drawings...19

PREVIEW COPY. Table of Contents. Troubleshooting with Electrical Schematics...3. Troubleshooting with Building Drawings...19 Table of Contents Lesson One Lesson Two Lesson Three Troubleshooting with Electrical Schematics...3 Troubleshooting with Building Drawings...9 Troubleshooting Control Circuits...37 Lesson Four Troubleshooting

More information

SUZ-KA25VA3.TH SUZ-KA35VA3.TH SUZ-KA50VA3.TH SUZ-KA60VA3.TH SUZ-KA71VA3.TH

SUZ-KA25VA3.TH SUZ-KA35VA3.TH SUZ-KA50VA3.TH SUZ-KA60VA3.TH SUZ-KA71VA3.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS February 013 No. OCB530 REVISED EDITION-A PARTS CATALOG R410A Outdoor unit [Model names] SUZ-KA5VA3 SUZ-KA35VA3 SUZ-KA50VA3 SUZ-KA60VA3 SUZ-KA71VA3 [Service Ref.]

More information

CIRCUITS THAT ARE AVAILABLE ON LODAR RECEIVERS Features listed below are available on 92 Series and 93 Series

CIRCUITS THAT ARE AVAILABLE ON LODAR RECEIVERS Features listed below are available on 92 Series and 93 Series CIRCUITS THAT ARE AVAILABLE ON LODAR RECEIVERS Features listed below are available on 9 Series and 9 Series STOP CIRCUIT uses are: - OVER TEMPERATURE and OVER PRESSURE, etc. ALLOWS AN EXTERNAL SENSOR TO

More information

Lessons In Industrial Instrumentation

Lessons In Industrial Instrumentation Lessons In Industrial Instrumentation c 2008-207 by Tony R. Kuphaldt under the terms and conditions of the Creative Commons Attribution 4.0 International Public License Version 2.25 (development) Last

More information

Installation and Operation Manual

Installation and Operation Manual SUPER-Selector PT Control Part No. 0 and 0C Installation and Operation Manual CHORE-TIME EQUIPMENT P.O. BOX 000 - MILFORD, DIANA -000 H H SET 0 POT TEMP HIGH TEMP LOW TEMP DANGER TIME ST AGE # TIMER TIME

More information

VEXUS TROUBLESHOOTING GUIDE MINI SPLIT SYSTEM EV10C2DB6 / H10C2MR63 EV13C2DB6 / H13C2MR63 EV18C2DB6 / H18C2MR63 EV24C2DB6 / H24C2MR63

VEXUS TROUBLESHOOTING GUIDE MINI SPLIT SYSTEM EV10C2DB6 / H10C2MR63 EV13C2DB6 / H13C2MR63 EV18C2DB6 / H18C2MR63 EV24C2DB6 / H24C2MR63 VEXUS TROUBLESHOOTING GUIDE VEXUS E1 EV10C2DB6 / H10C2MR63 VEXUS EV13C2DB6 / H13C2MR63 EV18C2DB6 / H18C2MR63 EV24C2DB6 / H24C2MR63 MINI SPLIT SYSTEM Troubleshooting Indoor unit error display Display Operation

More information

DLC-PDC PHOTODIODE CONTROLLER

DLC-PDC PHOTODIODE CONTROLLER DLC-PDC PHOTODIODE CONTROLLER INSTALLATION AND OPERATION INSTRUCTIONS 203 Cooper Circle, Peachtree City, GA 30269 Customer Service: Telephone: (800) 553-3879 Fax: (800) 954-7016 DLC-PDC Rev. 2 TABLE of

More information

PLEASE READ FIRST (NEW 2011 VERSION) Main features:

PLEASE READ FIRST (NEW 2011 VERSION) Main features: PLEASE READ FIRST (NEW 2011 VERSION) Main features: engine control system, the user can set different types of crankshaft independent Signal output (for all models of the computer-driven) automatic transmission

More information

Power Proportional Distribution (PPD)

Power Proportional Distribution (PPD) AN-PPD-11-18 Power Proportional Distribution (PPD) Application Note Table of Contents 1. Description... 3 2. Application and Design... 3 2.1 PPD Application with an intelligent Touch Controller (itc)...

More information

pi2ig-l 1988 STANDARD for GRAPHIC ELECTRICAL/ 00 ELECTRONIC AIR-CONDITIONING AND REFRIGERATING EQUIPMENT SYMBOLS FOR AIR-CONDITIONING

pi2ig-l 1988 STANDARD for GRAPHIC ELECTRICAL/ 00 ELECTRONIC AIR-CONDITIONING AND REFRIGERATING EQUIPMENT SYMBOLS FOR AIR-CONDITIONING 1988 STANDARD for STANDARD for GRAPHIC ELECTRICAL/ 00 ELECTRONIC s SYMBOLS FOR AIR-CONDITIONING AND REFRIGERATING EQUIPMENT 0 I AIR-CONDITIONING & REFRIGERATION INSTITUTE pi2ig-l 1501 WILSON BOULEVARD

More information

PARTS CATALOG R410A. September 2008 AIR TO WATER HEAT PUMP. No. OCB439 REVISED EDITION-A. [Service Ref.] [model name]

PARTS CATALOG R410A. September 2008 AIR TO WATER HEAT PUMP. No. OCB439 REVISED EDITION-A. [Service Ref.] [model name] AIR TO WATER HEAT PUMP PARTS CATALOG R40A [model name] PUHZ-W50VHA PUHZ-W5VHA PUHZ-HWYHA PUHZ-HW40VHA PUHZ-HW40YHA [Service Ref.] PUHZ-W50VHA PUHZ-W5VHA PUHZ-HWYHA PUHZ-HW40VHA PUHZ-HW40YHA September 00

More information

PRESSURE REGULATORS PARKER PRESSURE REGULATING VALVES PRESSURE REGULATORS

PRESSURE REGULATORS PARKER PRESSURE REGULATING VALVES PRESSURE REGULATORS PARKER PRESSURE REGULATING VALVES For R-22, R-502, R-404A, R-507 and other common refrigerants Pilot operated for close control at desired set point. Long life diaphragms. No bellows to fail. Lightweight

More information

IPS INTELLIGENT PUMP STARTER. Integrated Tru-power electronic motor and pump protection

IPS INTELLIGENT PUMP STARTER. Integrated Tru-power electronic motor and pump protection IPS INTELLIGENT PUMP STARTER With TM Smartstart Ø & Ø, 0/60 Hz, 20~600 VAC, /~00HP Integrated electronic pump protection overload Power metering and data logging options Motor Protection Key dealer yr.

More information

13acd MERIT SERIES R 22 A I R C O N D I T I O N E R S. SEER up to to 5 Tons Cooling Capacity 17,500 to 60,000 Btuh

13acd MERIT SERIES R 22 A I R C O N D I T I O N E R S. SEER up to to 5 Tons Cooling Capacity 17,500 to 60,000 Btuh E N G I N E E R I N G D A T A A I R C O N D I T I O N E R S 13acd MERIT SERIES R 22 Bulletin No. 210423 April 2008 Supersedes January 2008 SEER up to 14.0 1.5 to 5 Tons Cooling Capacity 17,500 to 60,000

More information

Hardware Installation Manual

Hardware Installation Manual Hardware Installation Manual Modular Silicon Expansion Valve (MSEV) High Capacity Modular Silicon Expansion Valve (HC-MSEV) Universal SuperHeat Controller/Sensor (USHX) Revision 1.5 DunAn Microstaq, Inc.

More information

CAUTION All safety information must be followed as provided in Service Manual

CAUTION All safety information must be followed as provided in Service Manual Domestic Microwave Technical Information AMV6167BD* JMV8166BA* JMV9169BA* Due to possibility of personal injury or property damage, always contact an authorized technician for servicing or repair of this

More information

STANDARD WIRING DIAGRAMS FOR SMART MODEL 20

STANDARD WIRING DIAGRAMS FOR SMART MODEL 20 CODING SYSTEM FOR AV ACTUATOR WIRING DIAGRAMS There are 3 elements to the wiring codes used in AVA electric actuators: WIRING CODE 1 3 Wire system, single pole double throw, switching the live SPDT 2 3

More information

3/4/2015. Basic relay construction. Shading coil in AC relays. Timothy L. Skvarenina and William E. DeWitt Electrical Power and Controls, 2e

3/4/2015. Basic relay construction. Shading coil in AC relays. Timothy L. Skvarenina and William E. DeWitt Electrical Power and Controls, 2e FIGURE 12-1 Basic relay construction. FIGURE 12-2 Shading coil in AC relays. 1 FIGURE 12-3 Contactor coil and shaded pole stators. FIGURE 12-4 Magnetic motor starter. 2 FIGURE 12-5 Thermal overload devices.

More information

Model 2400 Explosion-Proof M/P Converters -- LOCK IN LAST POSITION --

Model 2400 Explosion-Proof M/P Converters -- LOCK IN LAST POSITION -- A Explosion-Proof M/P Converters -- LOCK IN LAST POSITION -- Electrical AC Control Unit Motor Voltage...115vAC, 60Hz Power Consumption (watts) 10 Regulator...5(Max.) 16 Regulator...3(Max.) 80 Regulator...3(Max.)

More information

ECET 211 Electrical Machines and Controls

ECET 211 Electrical Machines and Controls ECET 211 Electrical Machines and Controls 2016/4/27 Class Review and Wrapping Up Comprehensive Exam, Friday, 1:00-3:00 PM, May 6, 2016 Close books/allow 1-page (8 x 11 and ½) hand-written review note,

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

ITV. Spare parts suitable for: Spare parts suitable for ice-cube machines

ITV. Spare parts suitable for: Spare parts suitable for ice-cube machines Spare parts suitable for: ITV Spare parts suitable for ice-cube machines Furnizor Professionall Srl. TEL: 004-0745 68 Email: contact@mag-pro.ro Str. Bucegi 5/, Cluj Napoca. Romania Fax: 004-064 86 9 Web:

More information

Relay Driver Overview and Applications

Relay Driver Overview and Applications Relay Driver Overview and Applications Describes Basic and Advanced Settings for common and alternative/novel uses for the Relay driver (RD-1). Morningstar s Relay Driver (RD-1) is a fully programmable

More information

PRODUCT: DODGE PROMASTER MAX SYSTEM 530 / 560 RELEASE DATE: 02/24/15 REVISION DATE: 02/24/15 PART NUMBER: B

PRODUCT: DODGE PROMASTER MAX SYSTEM 530 / 560 RELEASE DATE: 02/24/15 REVISION DATE: 02/24/15 PART NUMBER: B Parts List 30 01 000 319 Wire,12 Ga Red w/white Stripe 7 02 000 653 Linestake, 2.5" Vinyl Coated 35 01 000 335 Wire,12 Ga Red 2 02 000 656 Bolt,7/16-14 x 4 1/2 Zinc Plate 30 01 000 421 Wire,6 Ga. Red (Max.

More information

SPLIT DUCTED UNIT TECHNICAL SELECTION DATA SRA141C / SRA140E SPECIFICATION SUMMARY UNIT FEATURES CONTROL FEATURES CONTROL OPTIONS. PLENUMS (Optional)

SPLIT DUCTED UNIT TECHNICAL SELECTION DATA SRA141C / SRA140E SPECIFICATION SUMMARY UNIT FEATURES CONTROL FEATURES CONTROL OPTIONS. PLENUMS (Optional) TECHNICAL SELECTION DATA SPLIT DUCTED UNIT 1 SINGLE PHASE SCROLL SINGLE STAGE SS M SOFT START CENTRIFUGAL LOUVRE AXIAL UNIT FEATURES Scroll Compressor Multiple Speed Outdoor Fans Single Phase Soft Starter

More information

SC30-SM2 Series Signal Conditioners

SC30-SM2 Series Signal Conditioners Read these instructions carefully and completely before installing or operating. Failure to follow them could result in a fire or explosion causing property damage, personal injury, or loss of life. The

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

Cover Page - Electric Actuators & Accessories. Standard & Optional Features. OM Actuator Standard Features. OM Actuator Optional Features

Cover Page - Electric Actuators & Accessories. Standard & Optional Features. OM Actuator Standard Features. OM Actuator Optional Features SECTION 5 INDEX DESCRIPTION Cover Page - Electric Actuators & Accessories Standard & Optional Features OM Actuator Standard Features OM Actuator Optional Features V / Actuator Selection Chart OM1 Actuator

More information

Circuit Analysis and Ohm s Law

Circuit Analysis and Ohm s Law Excerpt from Circuit Analysis and Ohm s Law By Robert Cecci iii Preview The following is a sample excerpt from a study unit converted into the Adobe Acrobat format. A sample online exam is available for

More information

SUZ-KA25VA3.TH SUZ-KA35VA3.TH SUZ-KA50VA3.TH SUZ-KA60VA3.TH SUZ-KA71VA3.TH

SUZ-KA25VA3.TH SUZ-KA35VA3.TH SUZ-KA50VA3.TH SUZ-KA60VA3.TH SUZ-KA71VA3.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS October 202 PARTS CATALOG R40A Outdoor unit [Model names] SUZ-KA25VA3 SUZ-KA35VA3 SUZ-KA50VA3 SUZ-KA60VA3 SUZ-KA7VA3 [Service Ref.] SUZ-KA25VA3.TH SUZ-KA50VA3.TH

More information

INSTALLATION INSTRUCTIONS FOR SYMCOM S MODEL 77C-LR-KW/HP ELECTRONIC OVERLOAD RELAY

INSTALLATION INSTRUCTIONS FOR SYMCOM S MODEL 77C-LR-KW/HP ELECTRONIC OVERLOAD RELAY INSTALLATION INSTRUCTIONS FOR SYMCOM S MODEL 77C-LR-KW/HP ELECTRONIC OVERLOAD RELAY BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES. READ THESE INSTRUCTIONS

More information

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777- MV ELECTRONIC OVERLOAD RELAY MEDIUM VOLTAGE

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777- MV ELECTRONIC OVERLOAD RELAY MEDIUM VOLTAGE INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777- MV ELECTRONIC OVERLOAD RELAY MEDIUM VOLTAGE BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES. READ THESE INSTRUCTIONS

More information

Microprocessor Step Controller/Sequencer

Microprocessor Step Controller/Sequencer PRODUCT DATA 745/904 Series Microprocessor Step Controller/Sequencer The 745 and 904 Microprocessor Controllers are identical in every respect except for one feature. The 904 Series Sequencer includes

More information

PARTS CATALOG R410A. January 2012 PUHZ-HW112YHA PUHZ-HW112YHA-BS PUHZ-HW140VHA PUHZ-HW140VHA-BS PUHZ-HW140YHA PUHZ-HW140YHA-BS PUHZ-HW140VHA2R2-BS

PARTS CATALOG R410A. January 2012 PUHZ-HW112YHA PUHZ-HW112YHA-BS PUHZ-HW140VHA PUHZ-HW140VHA-BS PUHZ-HW140YHA PUHZ-HW140YHA-BS PUHZ-HW140VHA2R2-BS AIR TO WATER HEAT PUMP PARTS CATALOG [Model name] PUHZ-W50VHA PUHZ-W50VHA-BS PUHZ-W85VHA PUHZ-W85VHA-BS PUHZ-HWYHA PUHZ-HWYHA-BS PUHZ-HWYHA PUHZ-HWYHA-BS PUHZ-HW0VHA PUHZ-HW0VHA-BS PUHZ-HW0YHA PUHZ-HW0YHA-BS

More information

Street Light Controller

Street Light Controller Street Light Controller Table of Content Introduction:...3 Scope of the problem:...3 What we can do..?...3 The Device Light Controller:...4 Circuit Diagram:...4 Circuit Description:...5 PCB Layout design...5

More information

(267 kw THROUGH 735 kw)

(267 kw THROUGH 735 kw) YCWS (HFC-407C) 50 HZ WATER COOLED LIQUID CHILLERS INSTALLATION, OPERATION AND MAINTENANCE New Release Form 201.24-NM2.1 (202) YCWS WATER COOLED LIQUID CHILLERS YCWS0313SB 0663SB (ADDENDUM FOR HFC-407C

More information

4 T V H A D A A

4 T V H A D A A 4 T V H 0 0 8 6 A D 0 0 0 A A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Name All of units Outline Function Outdoor unit installation manual 1 Outdoor unit user manual 1 Be sure to deliver it to the customer

More information

Draw the symbol and state the applications of : 1) Push button switch 2) 3) Solenoid valve 4) Limit switch ( 1m each) Ans: 1) Push Button

Draw the symbol and state the applications of : 1) Push button switch 2) 3) Solenoid valve 4) Limit switch ( 1m each) Ans: 1) Push Button Subject Code: 17641Model AnswerPage 1 of 16 Important suggestions to examiners: 1) The answers should be examined by key words and not as word-to-word as given in the model answer scheme. 2) The model

More information

Creating Electrical Designs

Creating Electrical Designs C h a p t e r 2 Creating Electrical Designs In this chapter, we will learn the following to World Class standards: Understanding Control and Power Circuits Drawing the Control Circuit Selecting the Pushbutton

More information

ILLUSTRATED PARTS LIST COUNTERTOP ICEMAKER IMD SERIES

ILLUSTRATED PARTS LIST COUNTERTOP ICEMAKER IMD SERIES Distributed By: Commercial Refrigeration Service, Inc. http://www.corneliusparts.com http://www.icecubes.net toll free (8) Ice Maker () 89-888 ILLUSTRATED PARTS LIST COUNTERTOP ICEMAKER IMD SERIES IMD

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information

Operating Instructions. Single SBC-Control Systems. Seite 1 von 13. U:\SINGLE\Regler\SBC\Englisch\SBC_e_Version 2_6.doc

Operating Instructions. Single SBC-Control Systems. Seite 1 von 13. U:\SINGLE\Regler\SBC\Englisch\SBC_e_Version 2_6.doc Operating Instructions Single SBC-Control Systems U:\SINGLE\Regler\SBC\Englisch\SBC_e_Version 2_6.doc Seite 1 von 13 Inhaltsverzeichnis 1 SBC 2.6 structuring... 3 2 SBC 2.6 display- and control elements...

More information

TIG 250 AC-DC. POWER SOURCE art

TIG 250 AC-DC. POWER SOURCE art CEBORA S.p.A. 1 TIG 250 AC-DC POWER SOURCE art. 236.76 SERVICE MANUAL CEBORA S.p.A. 2 CONTENTS 1 - GENERAL INFORMATION... 3 1.1 - Introduction.... 3 1.2 - General service policy.... 3 1.3 - Safety information....

More information

STANDARD WIRING DIAGRAMS FOR SMART MODEL 20

STANDARD WIRING DIAGRAMS FOR SMART MODEL 20 SMART SERIES CODING SYSTEM FOR AV ACTUATOR WIRING DIAGRAMS There are 3 elements to the wiring codes used in AVA electric actuators: WIRING CODE 1 3 Wire system, single pole double throw, switching the

More information

Electromechanical Technology /Electromechanical Engineering Technology CIP Task Grid

Electromechanical Technology /Electromechanical Engineering Technology CIP Task Grid 1 Secondary Task List 100 DEMONSTRATE KNOWLEDGE OF TECHNICAL REPORTS 101 Identify components of technical reports. 102 Demonstrate knowledge of the common components of technical documents. 103 Maintain

More information

Optional end of travel limit switches for user setting of minimum and maximum pressure values.

Optional end of travel limit switches for user setting of minimum and maximum pressure values. A M/P Converters Features (Varies with s) AC Control Unit (CC) Output pressure locks in last position in event of power failure. Continuous AC Motor unit is instant start-stop, heavy duty impedance protected

More information

Optional end of travel limit switches for user setting of minimum and maximum pressure values.

Optional end of travel limit switches for user setting of minimum and maximum pressure values. A M/P Converters Features (Varies with s) AC Control Unit (CC) Output pressure locks in last position in event of power failure. Continuous AC Motor unit is instant start stop, heavy duty impedance protected

More information

Code. Edition 04/2013. CPA Screw Air Compressors. Parts List Book

Code. Edition 04/2013. CPA Screw Air Compressors. Parts List Book Code 2205 1084 06 Edition 04/2013 CPA7.5-10-15-20 Screw Air Compressors Parts List Book REF. PART NUM. QTY. NAME REF. PART NUM. QTY. NAME 1095 2205 1020 83 1 BASE 1195 2205 1053 83 1 PANEL 1100 2205 1028

More information

US2, US4, US6 Electronic step controllers

US2, US4, US6 Electronic step controllers 4 98 US, US4, Electronic step controllers The electronic step controllers are used in linear mode to switch devices (pumps, compressors, humidifiers and fans etc.) on and off in stages. Switch-on time

More information

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv) Outdoor Transmission (69 kv through 230 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The circuit-switcher shall conform to the following specification. 1.02 The circuit-switcher shall be

More information

TROUBLESHOOTING. KSIO MINI Split DC Inverter Air Conditioner. Model Numbers:

TROUBLESHOOTING. KSIO MINI Split DC Inverter Air Conditioner. Model Numbers: KSIO MINI Split DC Inverter Air Conditioner TROUBLESHOOTING Model Numbers: KSIO009-H24-I KSIO02-H23-I KSIO08-H22-I KSIO024-H29-I KWIO09-H2 KWIO2-H2 WARNING Installation MUST conform with local building

More information

Application of Electrical Signature Analysis. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN

Application of Electrical Signature Analysis. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN Application of Electrical Signature Analysis Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN Introduction Over the past months we have covered traditional and modern methods of testing electric

More information

INSTALLATION INSTRUCTIONS FOR THE MODEL 777 ELECTRONIC OVERLOAD RELAY

INSTALLATION INSTRUCTIONS FOR THE MODEL 777 ELECTRONIC OVERLOAD RELAY INSTALLATION INSTRUCTIONS FOR THE MODEL 777 ELECTRONIC OVERLOAD RELAY BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES. READ THESE INSTRUCTIONS ENTIRELY BEFORE

More information

Basic Electricity 30 Hour - Part 1 Student Workbook Issue: US140/30/2a-IQ-0402A. Written by: LJ Technical Dept

Basic Electricity 30 Hour - Part 1 Student Workbook Issue: US140/30/2a-IQ-0402A. Written by: LJ Technical Dept Basic Electricity 30 Hour - Part Issue: US40/30/a-IQ-040A Copyright 004,. No part of this Publication may be adapted or reproduced in any material form, without the prior written permission of. Written

More information

COURSE SYLLABUS. COURSE NUMBER AND TITLE: INTC-1357 AC/DC Motor Controls (2-4-3)

COURSE SYLLABUS. COURSE NUMBER AND TITLE: INTC-1357 AC/DC Motor Controls (2-4-3) COURSE NUMBER AND TITLE: INTC-1357 AC/DC Motor Controls (2-4-3) COURSE SYLLABUS COURSE (CATALOG) DESCRIPTION A study of electric motors and motor control devices common to a modern industrial environment.

More information

TECHNICAL SUPPORT MANUAL Fan Coils FXM4X

TECHNICAL SUPPORT MANUAL Fan Coils FXM4X Fan Coils FXM4X DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product

More information

Model 12200A RCN PTAC/PTHP/FAN COIL CONTROL NODE OPERATION OUTPUTS G1 = FAN 1 G2 = FAN 2 G3 = FAN 3 O/B = Rev Valve W = HEAT Y = COMPRESSOR

Model 12200A RCN PTAC/PTHP/FAN COIL CONTROL NODE OPERATION OUTPUTS G1 = FAN 1 G2 = FAN 2 G3 = FAN 3 O/B = Rev Valve W = HEAT Y = COMPRESSOR Model 12200A RCN PTAC/PTHP/ COIL CONTROL NODE OPERATION OUTPUTS G1 = 1 G2 = 2 G3 = 3 O/B = Rev Valve W = HEAT Y = COMPRESSOR Operating Modes Summary (Refer to Logic Tables 1 5): 1. PTAC (Standard) Fan

More information

Table of Contents. MOUNTING Mounting Diagram... Page 2. WIRING DIAGRAMS Wiring Diagrams. Pages 3-6

Table of Contents. MOUNTING Mounting Diagram... Page 2. WIRING DIAGRAMS Wiring Diagrams. Pages 3-6 Table of Contents MOUNTING Mounting Diagram......... Page 2 WIRING DIAGRAMS Wiring Diagrams. Pages 3-6 PROGRAMMABLE RELAY Programmable Relay Wiring.. Page 7 OTHER INPUTS RS232 and Two (2) Wire Digital

More information

For Immediate Delivery call KMParts.com at (866)

For Immediate Delivery call KMParts.com at (866) Moeller Wiring Manual / Page Overview - ON-OFF Switches, main switches, maintenance switches - Changeover switches, reversing switches - (Reversing) star-delta switches - Multi-speed switches - Interlock

More information

WESTERN IOWA TECH COMMUNITY COLLEGE. Course Syllabus. Electrical Technician Level 2

WESTERN IOWA TECH COMMUNITY COLLEGE. Course Syllabus. Electrical Technician Level 2 Course Title: Electrical Technician Level Total Hours:56 Meeting time/ location :TBA Instructor: Chris Sewalson Phone:712-274-8733 ext1407 E-mail Chris.sewalson@witcc.edu Office Location: Lemars Center

More information

INSTRUCTION MANUAL S EN1000/EN1001 SERIES CONTROLS

INSTRUCTION MANUAL S EN1000/EN1001 SERIES CONTROLS INSTRUCTION MANUAL 700120S EN1000/EN1001 SERIES CONTROLS MICROPROCESSOR BASED Weld Sequence Controls With Solid State Thyristor Contactors INCLUDES: Appendix E EN1000/EN1001 Bench Controls Appendix F EN1003

More information

P o w e r. C O N T R O L S A N D a t h e n a c o n t r o l s. c o m. ATHENA CONTROLS, INC Campus Drive Plymouth Meeting, PA U.S.A.

P o w e r. C O N T R O L S A N D a t h e n a c o n t r o l s. c o m. ATHENA CONTROLS, INC Campus Drive Plymouth Meeting, PA U.S.A. P o w e r C O N T R O L S A N D a t h e n a c o n t r o l s. c o m ATHENA CONTROLS, INC. 5145 Campus Drive Plymouth Meeting, PA 19462-1129 U.S.A. TABLE OF CONTENTS Model Page Series 19/39 1 and Zero-Switched

More information