VACUUM INTERRUPTER APPLICATION NOTES Filename: VIAN X-Rays and Vacuum Interrupters Revision: 0 PAGE 1

Size: px
Start display at page:

Download "VACUUM INTERRUPTER APPLICATION NOTES Filename: VIAN X-Rays and Vacuum Interrupters Revision: 0 PAGE 1"

Transcription

1 Revision: 0 PAGE 1 X-Rays and Vacuum Interrupters INTRODUCTION: Vacuum Interrupters made by Eaton carry a label that warns the user about the possibility of X-radiation. This warning needs some explanation so the reader can understand that under normal conditions, X-radiation is not detectable above normal background levels, and therefore is of no concern. And further, that only in rare situations when such emissions can occur is there a need for concern and protection. The label presently reads as follows: CAUTION This Device may emit X-rays if voltage higher than rated maximum is applied across the open contacts, or if the contacts are spaced less than rated stroke. In such cases personnel must be protected with appropriate shielding. This is a brief warning statement, small enough to fit on the label of a vacuum interrupter, intended to alert the user about a possibility of X-radiation. However, in reality, X-radiation is only produced under special conditions, and then, the only personnel that need be concerned are those involved in the testing of a vacuum interrupter. The discussion that follows is intended to put the issue of X- ray emission in perspective for both test personnel and anyone else that may be in the vicinity of vacuum interrupters or switching devices. 1. X-rays may be produced by a vacuum interrupter, but only under special, abnormal conditions X-rays that are measurable above the natural background level may possibly be produced by a vacuum interrupter only under the following special conditions: a) a voltage is applied to an interrupter whose contacts are open, and b) the applied voltage is typically much higher than the normal operating voltage of the interrupter, and c) the applied voltage is typically above about 50 to 60 kv, rms., (Although x- rays have been observed at voltages as low as 15 to 20 kv rms, this is a very rare occurrence.), and d) some amount of current driven by the high voltage is flowing through the open interrupter. (It is the current that produces the x-radiation, so the application of a high voltage from a source with severe current limiting may produce a much lower level of x-radiation than normally expected at that same voltage using a supply capable of a larger current output.)

2 Revision: 0 PAGE 2 2. A vacuum interrupter under normal conditions does not produce X- rays: X-rays that are measurable above the natural background level are not produced by a vacuum interrupter under the following conditions: a) sitting in a box b) sitting on the self c) in a de-energized switch d) in an energized switch when the interrupter contacts are closed e) in an energized switch at the normal operating voltage f) in a breaker switching either load currents or fault currents g) in a breaker undergoing impulse voltage withstand testing 3. X-rays are only an issue of concern for test personnel. AC or DC high voltage withstand testing is the only condition under which an interrupter with its contacts open can have a sustained voltage applied that is high enough in magnitude to possibly produce measurable x-rays. Therefore, the only people that need be concerned about x-ray exposure are: - high voltage test personnel at the vacuum interrupter factory, - high voltage test personnel at the switchgear factory, or - maintenance personnel in the field. Moreover, the level of x-rays produced increases as the magnitude of the applied voltage is increased. Therefore, the potential for x-ray emission is greatest during tests in a factory, since these tests are performed at 100% of the rated power frequency withstand voltage of the device. In addition, high voltage tests are performed frequently in a manufacturing setting and often by the same few people, thus providing the possibility of more accumulated exposure over time if in fact the person is exposed to any x-rays at all. Tests performed in the field are normally only performed at 75% of rating, and therefore, the level of x-ray production is automatically lower. Moreover, maintenance tests are performed very infrequently which greatly reduces the opportunity for an accumulation of exposure by one individual. Consequently, high voltage test personnel at a vacuum interrupter factory and at a switchgear factory are the people that need be most concerned with the possibility of x-ray exposure. 4. Distance avoids excessive exposure to x-rays during high voltage tests. A respectful, safe separation distance between test personnel and energized parts is always required during high voltage withstand testing, and, when testing vacuum interrupters, such a respectful, safe separation distance between test personnel and the vacuum interrupter under test also avoids the possibility of excessive exposure to x-rays. X-ray production is very directional from an

3 Revision: 0 PAGE 3 emitting source, and, moreover, the intensity of x-rays decreases as the separation distance increases. Therefore, the most expedient means of insuring a safe environment for test personnel is to maintain a minimum distance between test personnel and the vacuum interrupters under test. TABLE 1 at the end of this report which lists minimum recommended distances distance between test personnel and the vacuum interrupters under test provides a convenient guide for the test personnel to follow. 5. Minimum recommended distances are based on ANSI standards The Vacuum Interrupters manufactured by Eaton comply with the requirements of ANSI C entitled Alternating-Current High- Power Vacuum Interrupters - Safety Requirements for x-radiation Limits. Interrupters, tested as specified in Section 5 (of C ), shall be in compliance with this standard if x-radiation emitted does not exceed the following: (1) 0.5 milliroentgen per hour at the maximum operating voltage shown in column 2 of Table 1 of C (2) 15.0 milliroentgen per hour at the low frequency dielectric withstand test voltage shown in column 3 of Table 1 of C That is, at a distance of 1 meter from the interrupter, the observed x-radiation emitted complies with items (1) and (2) above. As reported in some excerpts from Appendix A of C , As a result of evaluating the results of the aforementioned tests, the manufacturers (of vacuum interrupters) concluded that neither the general public or users will be subjected to harmful X-radiation due to normal application and operation of 15.5 kilovolt-rated vacuum interrupter devices when applied within their assigned ratings and when the voltage applied across the open contacts of the interrupter is 15.5 kilovolts or less. The manufacturers also concluded that at the permissible user powerfrequency withstand test voltage of 37.5 kilovolts (the field test voltage is 75% of the rated withstand voltage), radiation levels are negligible for vacuum interrupters rated 15.5 kilovolts. Normal electrical safety precautions require the user to be at a distance from the interrupters that provide sufficient protection.... A minimum distance of 2 to 3 meters can normally be expected to be used for reasons of electrical safety. Since this test is performed only during maintenance, which normally occurs only once in a 1-year to 3-year period, (2000) 1 minute tests per year exceeds by a factor of 10 or more the number of interrupters a user such as a utility would be expected to test in a year.

4 Revision: 0 PAGE 4 Concerning the 50 kilovolt 1-minute withstand test voltage applied by the switchgear manufacturer during the factory test, the Vacuum Interrupter manufacturers believe that the higher level of possible emitted x-radiation could be injurious to personnel. Therefore, the manufacturers recommended that they take appropriate precautions to protect personnel and meet local codes by using monitoring devices and safety measures as required. Since the 1978 reaffirmation of this standard, manufacturers have conducted tests on interrupters rated through 38 kilovolts, as reflected in this (1985) revision. This testing and concurrent field experience has demonstrated that these higher voltage ratings meet the requirements of this standard. 6. Minimum recommended distances are further based on x-ray measurements. From many tests on 15 and 27 kv vacuum circuit breakers with separation distance of 1 to 3 meters, it has been observed that x-ray levels are almost indistinguishable from the background level at voltages up to 40 kv, AC rms. and just barely above background but still less that 0.5 milliroentgen per hour at voltages up the 60 kv, rms. So, as a general recommendation, x-ray levels from the testing of vacuum interrupters will be well within safe limits for test personnel that are located at a distances of 2 to 3 meters from the interrupter under test at test voltages up to 60 kv, rms. An x-ray survey was performed for a Cutler-Hammer 38 kv vacuum circuit breaker to determine the potential radiation dose that could be received by personnel testing these higher voltage rated circuit breakers. - Based on the survey results the radiation levels did not exceed 0.5 mr/hr at a distance of 3 meters from the device when the applied voltage was 60 kv AC rms. (the end user s test voltage) with all three phases of the device energized at the same time. - Under normal testing conditions performed by the circuit breaker manufacturer, the test voltage does not exceed 80 kv AC rms. and the maximum instantaneous radiation level did not exceed 3.5 mr/hr from a distance of 3 meters from the device (the ANSI limit is 15 mr/hr). ANSI Standard C37.85 (1989) was used as a guide for radiation exposure limits and test procedures. The background level where these tests were performed was about 0.2 mr/hr.

5 Revision: 0 PAGE 5 The effects of extra shielding were also evaluated in these tests - With a 3 mm thick steel shield and a separation of 3 meters, the x-ray levels at 60 kv AC rms are indistinguishable from the background level. At 80 kv AC rms the x-ray levels are only about 0.8 mr/hr, which is a negligible dose for testing personnel and only about 1/20th of the 15 mr/hr limit set in ANSI C37.85 (1989). - With a 1.5 mm thick portable lead shield and a separation of 3 meters, the x-ray levels at 60 kv AC rms are indistinguishable from the background level. At 80 kv AC rms the x-ray levels are only about 0.4 mr/hr, which is a negligible dose for testing personnel and only about 1/40th of the 15 mr/hr limit set in ANSI C37.85 (1989). 7. An x-ray absorbing barrier provides an extra measure of protection A barrier of steel or lead provides some extra protection for high voltage test personnel to avoid excessive x-ray exposure. Barrier Material Barrier Thickness x-ray level at 3 meters reduced to: Steel 3 mm less than 1/4 of the unshielded case Lead 1.5 mm less than 1/8 of the unshielded case For fixed test installations, either steel or lead can be provided as portable screens or fixed walls. For field tests, if the circuit breaker mechanism enclosure is located between the test personnel and the vacuum interrupter(s) under test, then the steel enclosure provides an extra barrier to reduce x-ray levels. 8. Vacuum Switchgear manufacturers should provide separation, monitoring and training (and shielding at higher test voltages or restricted spaces) for x-ray exposure precautions. For a switchgear manufacturer, good practices to insure that x-ray levels are within safe limits for test personnel include the following provisions. (1) Maintain at least the minimum recommended separation between the test personnel and the test object. (2) Provide x-ray cumulative dose monitoring of all test personnel. (3) Provide training of all test personnel in the hazards of x-rays and safe test practices. (4) At test voltages of 60 kv and above where significant x-ray levels may be observed, provide shielding between the test personnel and the test object for extra protection. This is also advisable in cases with restricted spaces where the minimum recommended separation is not practical. Establishing a high voltage test area where a minimum clearance between the vacuum interrupter under test and the test personnel is 3 to 4 meters is the first priority. In this manner, switchgear of all voltage ratings can be tested in the

6 Revision: 0 PAGE 6 same location and no special consideration between one voltage and another need be considered since the largest separation distance is employed. Exposure monitoring is also recommended for all high voltage test personnel or others that are regularly in close proximity to the test by wearing film badges that are checked monthly for accumulated radiation exposure. This practice monitors the actual accumulated exposure experienced by the people involved and provides a warning when the exposure exceeds allowable limits in a 1 month time period. This practice is followed at the Cutler-Hammer Horseheads Vacuum Interrupter plant where separation and shielding are in place. In our experience, no accumulated exposure is ever detected with the monitors worn by our test personnel. Training of high voltage test personnel should be provided to outline the potential hazards of x-rays from vacuum interrupters and to describe the proper precautions to take to keep the risk exposure to minimum levels. Shielding of the test object is an additional provision to consider under some circumstances. An enclosure for the switchgear device or barrier between the test personnel and the switchgear device under test consisting of sheet metal walls and possibly a portable lead screen or two can provide some additional protection from x-ray exposure. Such additional measures are recommended for test voltages of 60 kv and above where significant x-ray levels may be observed. Shielding is also recommended in cases with restricted spaces where the simpler measure of providing the minimum separation is not practical. In this case, adequate shielding can insure that x-ray levels immediately outside the enclosure are always within safe levels. The switchgear manufacture should also consult local and state codes for other requirements that should be considered. R. Kirkland Smith, Ph. D. Manager, Power Test Lab Eaton Corporation Phone: Westinghouse Circle FAX: Horseheads, NY USA KirklandSmith@eaton.com

7 Revision: 0 PAGE 7 TABLE 1 - Minimum Recommended Distances from a Test Object during High Testing of Vacuum Interrupters Applicable Standard Rated System Rated Power Frequency Withstand Factory Test at 100% of Rated Withstand Field Test at 75% of Rated Withstand Minimum Recommended Distance from Test Object Measured X-ray Emission kv, rms. kv, rms. kv, rms. kv, rms. kv, DC Meters milliroentgen per hour IEC to 3 <background IEC to 3 <background ANSI C to 3 <background ANSI C to 3 <background IEC to 3 <background IEC to 3 <background ANSI C to 3 <background ANSI C to 3 <background IEC to 3 <background IEC to 3 <background ANSI C to 3 <background ANSI C to 3 <background IEC to 3 <background IEC to 3 <background ANSI C to 3 <background ANSI C to 3 <0.5mR/hr IEC to 3 <background IEC to 3 <0.5mR/hr ANSI C to 3 <background ANSI C to 3 <0.5mR/hr ANSI C to 3 <background ANSI C to 3 <0.5mR/hr IEC to 4 <0.5mR/hr IEC to 4 <3.5mR/hr ANSI C to 4 <0.5mR/hr ANSI C to 4 <3.5mR/hr

Alternating-Current High-Voltage Power Vacuum Interrupters Safety Requirements for X-Radiation Limits

Alternating-Current High-Voltage Power Vacuum Interrupters Safety Requirements for X-Radiation Limits ANSI C37.85-1989 (Revision of ANSI C37.85-1972) American National Standard for Switchgear Alternating-Current High-Voltage Power Vacuum Interrupters Safety Requirements for X-Radiation Limits Secretariat

More information

TABLE OF CONTENTS. References

TABLE OF CONTENTS. References ANALYTICAL X-RAY EQUIPMENT USE POLICIES & PROCEDURES Page 1 of 9 Revised: 11/24/2003 TABLE OF CONTENTS 1.0 General 2.0 Purpose 3.0 Scope and Authority 4.0 Equipment Requirements 4.0.1 Safety device 4.0.2

More information

APPENDIX K UNF RADIATION GENERATING DEVICE SAFETY PROCEDURES

APPENDIX K UNF RADIATION GENERATING DEVICE SAFETY PROCEDURES APPENDIX K UNF RADIATION GENERATING DEVICE SAFETY PROCEDURES Policy and Purpose This policy provides administrative control over the use of radiation generating devices and is designed to ensure that such

More information

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com AN EXAMPLE OF A STANDARD ARC

More information

Minnesota Rules, Chapter 4732 X-ray Revision PROPOSED NON-MEDICAL CABINET X-RAY SYSTEMS, 1.0

Minnesota Rules, Chapter 4732 X-ray Revision PROPOSED NON-MEDICAL CABINET X-RAY SYSTEMS, 1.0 Minnesota Rules, Chapter 4732 X-ray Revision PROPOSED NON-MEDICAL CABINET X-RAY SYSTEMS, 1.0 4732.#### NON-MEDICAL CABINET X-RAY SYSTEMS Subpart 1. Applicability. A registrant s non-medical cabinet x-ray

More information

(a) This subchapter applies to installations using analytical x-ray equipment and establishes requirements for their use.

(a) This subchapter applies to installations using analytical x-ray equipment and establishes requirements for their use. SUBCHAPTER 21. ANALYTICAL X-RAY INSTALLATIONS 7:28-21.1 Scope (a) This subchapter applies to installations using analytical x-ray equipment and establishes requirements for their use. (b) The provisions

More information

RADIATION SAFETY REQUIREMENTS FOR ANALYTICAL X-RAY EQUIPMENT

RADIATION SAFETY REQUIREMENTS FOR ANALYTICAL X-RAY EQUIPMENT 420-3-26-.11 RADIATION SAFETY REQUIREMENTS FOR ANALYTICAL X-RAY EQUIPMENT (1) Purpose and Scope. This rule 420-3-26-.11 provides special requirements for analytical x- ray equipment; provided, however,

More information

By: Georgia Institute of Technology

By: Georgia Institute of Technology Date: / / Page 1 of 19 1.0 PURPOSE 2.0 SCOPE To provide instructions for the registration, use, operation, control, and accountability of radiation machines at the Georgia Institute of Technology (Georgia

More information

Minnesota Rules, Chapter 4732 X-ray Revision

Minnesota Rules, Chapter 4732 X-ray Revision Minnesota Rules, Chapter 4732 X-ray Revision PROPOSED DRAFT NON-MEDICAL HAND-HELD X-RAY SYSTEMS, 1.0 4732.#### NON-MEDICAL HAND-HELD X-RAY SYSTEMS. Subpart 1. Applicability. A registrant s non-medical

More information

Minnesota Rules, Chapter 4732 X-ray Revision

Minnesota Rules, Chapter 4732 X-ray Revision Minnesota Rules, Chapter 4732 X-ray Revision PROPOSED DRAFT GAUGING X-RAY SYSTEMS, 1.0 4732.#### GAUGING X-RAY SYSTEMS. Subpart 1. Applicability. A registrant s gauging x-ray system must comply with the

More information

Minnesota Rules, Chapter 4732 X-ray Revision

Minnesota Rules, Chapter 4732 X-ray Revision Minnesota Rules, Chapter 4732 X-ray Revision PROPOSED DRAFT BOMB DETECTION X-RAY SYSTEMS, 1.0 4732.#### BOMB DETECTION X-RAY SYSTEMS. Subpart 1. Applicability. A registrant s bomb detection x-ray system

More information

Minnesota Rules, Chapter 4732 X-ray Revision PROPOSED NON-MEDICAL ANALYTICAL X-RAY SYSTEMS, 1.0

Minnesota Rules, Chapter 4732 X-ray Revision PROPOSED NON-MEDICAL ANALYTICAL X-RAY SYSTEMS, 1.0 Minnesota Rules, Chapter 4732 X-ray Revision PROPOSED NON-MEDICAL ANALYTICAL X-RAY SYSTEMS, 1.0 4732.#### NON-MEDICAL ANALYTICAL X-RAY SYSTEMS Subpart 1. Applicability. A registrant s analytical x-ray

More information

1. Oklahoma Administrative Code (OAC) 252:410, titled Radiation Management

1. Oklahoma Administrative Code (OAC) 252:410, titled Radiation Management X-Ray Radiation Safety Management Program The University of Tulsa (TU) February 22, 2016 (version 2016.02.22) References: 1. Oklahoma Administrative Code (OAC) 252:410, titled Radiation Management 2. 10

More information

Appendix B to Working on Exposed Energized Parts

Appendix B to Working on Exposed Energized Parts Working on Exposed Energized Parts. - 1910.269 App B Regulations (Standards - 29 CFR) - Table of Contents Part Number: 1910 Part Title: Occupational Safety and Health Standards Subpart: R Subpart Title:

More information

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com AN EXAMPLE OF A STANDARD ARC

More information

Minnesota Rules, Chapter 4732 X-ray Revision

Minnesota Rules, Chapter 4732 X-ray Revision Minnesota Rules, Chapter 4732 X-ray Revision DRAFT NON-MEDICAL HAND-HELD X-RAY SYSTEMS, 2.0 4732.#### NON-MEDICAL HAND-HELD X-RAY SYSTEMS. Summary of Changes MDH made a number of changes to the Non-Medical

More information

X-RAY SAFETY REFRESHER EXAM

X-RAY SAFETY REFRESHER EXAM X-RAY SAFETY REFRESHER EXAM DIRECTIONS: Please print this quiz and fill in the information requested. Mark the correct answer to each question. When completed either scan and email the quiz to the Radiation

More information

Agilent 5DX System. X-ray Safety Test Procedure. for use with Software Release 8.20 and later

Agilent 5DX System. X-ray Safety Test Procedure. for use with Software Release 8.20 and later Agilent 5DX System for use with Software Release 8.20 and later Agilent Technologies, Inc. 1996-2008 Agilent Safety and Regulatory Information: Restricted Rights Notice If software is for use in the performance

More information

Comparison of recloser and breaker standards

Comparison of recloser and breaker standards s Technical Data TD280024EN Supersedes February 1994 (R280-90-5) COOPER POWER SERIES Comparison of recloser and breaker standards Technical Data TD280024EN Comparison of recloser and breaker standards

More information

SWITCHING SAFETY & RELIABILITY CONFERENCE

SWITCHING SAFETY & RELIABILITY CONFERENCE SWITCHING SAFETY & RELIABILITY CONFERENCE JARGON WORKSHEET Energize (v) Energize is the process of applying rated voltage to circuit or equipment. Modified IEEE or OSHA from Adj. to verb. To make a piece

More information

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D Electricity Ten Year Statement November 2017 01 Electricity Ten Year Statement November 2017 001 Appendix D 1 Short-circuit currents 02 2 Short-circuit current terminology 04 3 Data requirements 07 4 Fault

More information

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable: Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.

More information

2014 NEC Changes Part 1

2014 NEC Changes Part 1 www.garyklinka.com Page 1 of 8 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Appendix D Fault Levels

Appendix D Fault Levels Appendix D Fault Levels Page 1 Electricity Ten Year Statement November 2013 D.1 Short Circuit Currents Short Circuit Currents Three phase to earth and single phase to earth short circuit current analyses

More information

Analog Voltage Detector 0-40kV Operating Instructions VDA040CTM

Analog Voltage Detector 0-40kV Operating Instructions VDA040CTM Analog Voltage Detector 0-40kV Operating Instructions VDA040CTM CONTENTS Limitation of Warranty and Liability 2 Product Safety Information 3 Design and Function 4 Voltage Detection in the C Position 5-6

More information

1-1. GENERAL 1-2. DISCOVERY OF X-RAYS

1-1. GENERAL 1-2. DISCOVERY OF X-RAYS 1-1. GENERAL Radiography is a highly technical field, indispensable to the modern dental practice, but presenting many potential hazards. The dental radiographic specialist must be thoroughly familiar

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

LOCKOUT / TAGOUT PROGRAM

LOCKOUT / TAGOUT PROGRAM Page 1 of 7 1. SCOPE LOCKOUT / TAGOUT PROGRAM This Program outlines the purpose, rules, responsibilities and techniques to be followed by all University of Pittsburgh employees to guard against the unexpected

More information

OPERATION MANUAL FOR ALLIGATOR TUMBLE STIRRER* VP 710A

OPERATION MANUAL FOR ALLIGATOR TUMBLE STIRRER* VP 710A OPERATION MANUAL FOR ALLIGATOR TUMBLE STIRRER* VP 710A *US Patent # 6,176,609 TECHNICAL NOTE 270 Figure 1. Alligator Tumble Stirrer VP 710A. WARNING!!!!! Be advised that the Magnetic Tumble Stirrer has

More information

Protection from electromagnetic environment effects

Protection from electromagnetic environment effects ITU Regional Development Forum 2008 Bridging the ICT standardization gap in developing countries Protection from electromagnetic environment effects Roberto Pomponi, ITU-T SG 5 Chairman (Telecom Italia)

More information

Model 4210-MMPC-L. Multi-measurement Prober Cable Kit. Overview. Quick start guide topics. Related documents

Model 4210-MMPC-L. Multi-measurement Prober Cable Kit. Overview. Quick start guide topics. Related documents Model 0-MMPC-L Keithley Instruments, Inc. Multi-measurement Prober Cable Kit 877 Aurora Road Quick Start Guide Cleveland, Ohio 9-888-KEITHLEY http://www.keithley.com Overview The Keithley Instruments Model

More information

Analog Voltage Detector 1-450kV Operating Instructions VDAO450TM. Patent No. 6,275,022

Analog Voltage Detector 1-450kV Operating Instructions VDAO450TM. Patent No. 6,275,022 Analog Voltage Detector 1-450kV Operating Instructions VDAO450TM Patent No. 6,275,022 CONTENTS Limitation of Warranty and Liability 2 Product Safety Information 3 Design and Function 4 Operating Procedure

More information

ClearSpan Cedar 12' Wide End Frame Kit with Dutch Door

ClearSpan Cedar 12' Wide End Frame Kit with Dutch Door ClearSpan Cedar 12' Wide End Frame Kit with Dutch Door Photo may show a different but similar model. 2010 ClearSpan All Rights Reserved. Reproduction is prohibited without permission. STK # WIDTH 105366

More information

Webinar: An Effective Arc Flash Safety Program

Webinar: An Effective Arc Flash Safety Program Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of

More information

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017 Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and

More information

Minnesota Rules, Chapter 4732 X-ray Revision

Minnesota Rules, Chapter 4732 X-ray Revision Minnesota Rules, Chapter 4732 X-ray Revision DRAFT INDUSTRIAL X-RAY SYSTEMS DEFINTIONS, 1.0 4732.####. INDUSTRIAL X-RAY SYSTEMS DEFINITIONS. Subpart 1. Scope. For purposes of industrial x-ray systems under

More information

USER MANUAL Digital Wireless Gateway U9120-W4 (P/N: 44002G-01)

USER MANUAL Digital Wireless Gateway U9120-W4 (P/N: 44002G-01) USER MANUAL Digital Wireless Gateway U9120-W4 (P/N: 44002G-01) 19549P-82 (11-16) 2016 DAVID CLARK COMPANY INCORPORATED Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in

More information

A53106 SERIES DC-TO-DC CONVERTER

A53106 SERIES DC-TO-DC CONVERTER INSTALLATION & MAINTENANCE A53106 SERIES DC-TO-DC CONVERTER AUGUST 2011, REVISED AUGUST 2014 DOCUMENT NO. COM-00-04-20 VERSION C.1 Siemens Industry, Inc., Rail Automation 9568 Archibald Ave., Suite 100,

More information

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks 2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution

More information

Electrical Severity Measurement Tool Revision 4

Electrical Severity Measurement Tool Revision 4 Electrical Severity Measurement Tool Revision 4 November 2017 Electrical Severity Measurement Tool 1.0 Purpose: This tool is intended to measure the severity of exposure to an electrical safety event based

More information

STANDARDIZING ARC FLASH PPE LABELS

STANDARDIZING ARC FLASH PPE LABELS The Electrical Power Engineers Qual-Tech Engineers, Inc. 01 Johnson Road Building #1 Suite 03 Houston, PA 1534-1300 Phone 74-873-975 Fax 74-873-8910 www.qualtecheng.com STANDARDIZING ARC FLASH PPE LABELS

More information

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection

More information

First Draft Language

First Draft Language 110.16 First Draft Language (B) Service Equipment. In addition to the requirements in (A), service equipment shall contain the following information: (1) Nominal system voltage (2) Arc flash boundary (3)

More information

COUPLING DECOUPLING NETWORK MODEL CDN-AF4

COUPLING DECOUPLING NETWORK MODEL CDN-AF4 COUPLING DECOUPLING NETWORK MODEL CDN-AF4 II Warranty Com-Power warrants to its Customers that the products it manufactures will be free from defects in materials and workmanship for a period of 2 years.

More information

ELECTRIC TRANSMISSION (ET) Guideline G0104

ELECTRIC TRANSMISSION (ET) Guideline G0104 ELECTRIC TRANSMISSION (ET) ISSUING DEPARTMENT: ETM x ETEC ETPO ETTS EFFECTIVE DATE: 06-01-1997 DEPARTMENTS AFFECTED: ETM ETEC ETPO x ETTS REVIEW DATE: 01-01-1998 DEPARTMENT GROUP: ALL All All x All P E

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

Operating Manual. isolate501

Operating Manual. isolate501 Operating Manual isolate501 Document Number 413569 (See Last Page for Revision Details). Copyright Extronics Ltd, 2015 Page 2 of 21 Contents 1 Introduction... 4 2 Safety Information and Notes... 5 2.1

More information

SINGLE-PHASE VSV SWITCH

SINGLE-PHASE VSV SWITCH May 2006 Supercedes: March 2006 SINGLE-PHASE VSV SWITCH INSTALLATION AND OPERATING MANUAL Table of Content: Page I. General...2 II. Specifications...2 III. Installation...2 IV. Maintenance...4 V. VSV Power

More information

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL 1 Contents 1. Application... 5 2. meter set... 6 3. BASIC REQUIREMENTS, OPERATIONAL SAFETy... 6 4. installation... 10 4.1. Mounting... 10 4.2. External

More information

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL SINGLE PHASE INSTRUCTION MANUAL DIAGRAM D This manual applies to all single-phase buck & boost transformers sold by Larson Electronics. Please refer to the connection diagram on pages 4-6 for properly

More information

USER MANUAL Universal Gateway U9921-GUV (P/N: 40994G-01)

USER MANUAL Universal Gateway U9921-GUV (P/N: 40994G-01) USER MANUAL Universal Gateway U9921-GUV (P/N: 40994G-01) 2012 DAVID CLARK COMPANY INCORPORATED Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in this installation manual.

More information

Arc Flash Analysis Training

Arc Flash Analysis Training Arc Flash Analysis Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq An arc flash analysis study is

More information

Arc Flash Mitigation An Overview. Gus Nasrallah, P.E. Electroswitch May 30, 2013

Arc Flash Mitigation An Overview. Gus Nasrallah, P.E. Electroswitch May 30, 2013 Arc Flash Mitigation An Overview Gus Nasrallah, P.E. Electroswitch May 30, 2013 Agenda Origin of Modern Arc Flash studies Why Now more than before NFPA 70E Standards Protection Zone IEEE 1584 2002 IEEE

More information

Installation guide 971 SmartRadar LTi

Installation guide 971 SmartRadar LTi Installation guide 971 SmartRadar LTi March 2009 Part no. 4416.715 Revision 3 Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15 2701 111 E-mail : enraf-nl@honeywellenraf.nl

More information

Ch. 223 VETERINARY MEDICINE CHAPTER 223. VETERINARY MEDICINE GENERAL PROVISIONS X-RAYS RADIOACTIVE MATERIAL. Authority

Ch. 223 VETERINARY MEDICINE CHAPTER 223. VETERINARY MEDICINE GENERAL PROVISIONS X-RAYS RADIOACTIVE MATERIAL. Authority Ch. 223 VETERINARY MEDICINE 25 223.1 CHAPTER 223. VETERINARY MEDICINE Sec. 223.1. Purpose and scope. 223.2. [Reserved]. 223.2a. Definitions. 223.3 223.6. [Reserved]. 223.7. Structural shielding. 223.8.

More information

Biological Safety. Electromagnetic Compatibility (EMC) Observe the following precautions related to biological safety.

Biological Safety. Electromagnetic Compatibility (EMC) Observe the following precautions related to biological safety. Biological Safety Observe the following precautions related to biological safety. WARNING: Non-medical (commercial) grade peripheral monitors have not been verified or validated by SonoSite as being suitable

More information

Throttle Type. per Minute Inches (412 mm) (L) Lever

Throttle Type. per Minute Inches (412 mm) (L) Lever HENRY TOOLS Industrial Airtools at Work General Safety and Maintenance Manual Model Number Bore and Stroke 1.0 Inch x 2.0 Inch (25 mm x 51 mm) Throttle Type (L) Lever Blows Length per Minute 2500 16.2

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS SAUDI STANDARD NO. SASO IEC 60669-2-2: 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS Part 2-2: Particular requirements Electromagnetic remote-control switches (RCS) SAUDI ARABIAN

More information

PART H RADIATION SAFETY REQUIREMENTS FOR NON-HEALING ARTS RADIATION GENERATING DEVICES (RGD)

PART H RADIATION SAFETY REQUIREMENTS FOR NON-HEALING ARTS RADIATION GENERATING DEVICES (RGD) Sec. H.1-H.4 SSRCR Volume I - July 2016 PART H RADIATION SAFETY REQUIREMENTS FOR NON-HEALING ARTS RADIATION GENERATING DEVICES (RGD) Sec. H.1 - Purpose. This Part provides special requirements for non-healing

More information

Keene State College Center for Environmental BioGeoChemistry Radiation Protection Program Revised January

Keene State College Center for Environmental BioGeoChemistry Radiation Protection Program Revised January Keene State College Center for Environmental BioGeoChemistry Radiation Protection Program Revised January 21. 2009 XRF System Manager Timothy T. Allen, Professor of Geology and Environmental Studies Mailstop

More information

Generation Interconnection Requirements at Voltages 34.5 kv and Below

Generation Interconnection Requirements at Voltages 34.5 kv and Below Generation Interconnection Requirements at Voltages 34.5 kv and Below 2005 March GENERATION INTERCONNECTION REQUIREMENTS AT 34.5 KV AND BELOW PAGE 1 OF 36 TABLE OF CONTENTS 1. INTRODUCTION 5 1.1. Intent

More information

SINGLE-PHASE VSV SWITCH

SINGLE-PHASE VSV SWITCH Revision: September 2009 Supersedes: August 2007 SINGLE-PHASE VSV SWITCH INSTALLATION AND OPERATING MANUAL Table of Content: Page I. General...2 II. Specifications...2 III. Installation...3 IV. Maintenance...5

More information

Stationary Anode X-Ray Tube. General Data

Stationary Anode X-Ray Tube. General Data Technical Data TD TOSHIBA X-RAY TUBE D-041 D-041S D-041SB Stationary Anode X-Ray Tube Especially designed for dental radiography unit. Provided with an insulation cylinder (D-041S) and lead cylinder. (D-041SB)

More information

BIODEX MULTI- JOINT SYSTEM

BIODEX MULTI- JOINT SYSTEM BIODEX MULTI- JOINT SYSTEM CONFORMANCE TO STANDARDS 850-000, 840-000, 852-000 FN: 18-139 5/18 Contact information Manufactured by: Biodex Medical Systems, Inc. 20 Ramsey Road, Shirley, New York, 11967-4704

More information

CHANCE Proximity Voltage Indicator

CHANCE Proximity Voltage Indicator Revision D 10/16 CHANCE Proximity Voltage Indicator Operating Instructions Model No. PSC4033737 For use with Capacitive Test Point through 500 kv AC NOTICE: Before operating a Chance Proximity Voltage

More information

Application Note (Revision NEW) Original Instructions. EMI Control in Electronic Governing Systems

Application Note (Revision NEW) Original Instructions. EMI Control in Electronic Governing Systems Application Note 50532 (Revision NEW) Original Instructions EMI Control in Electronic Governing Systems General Precautions Read this entire manual and all other publications pertaining to the work to

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. Current Transducer CTSR 0.6-TP/SP2 I PRN = 600 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. Features

More information

Table of Contents. 1 Introduction. 2 System-Level Electrostatic Discharge (ESD) and Electrical Fast Transient (EFT) 3 Electromagnetic Interference

Table of Contents. 1 Introduction. 2 System-Level Electrostatic Discharge (ESD) and Electrical Fast Transient (EFT) 3 Electromagnetic Interference Electromagnetic Compatibility and Electrical Safety GR-1089-CORE Table of Contents Table of Contents 1 Introduction 1.1 Purpose and Scope.................................. 1 1 1.2 Items Not Covered in

More information

Verizon NEBS Compliance and Quality Assurance (NQA) Labeling Requirements for Light Emitting Products

Verizon NEBS Compliance and Quality Assurance (NQA) Labeling Requirements for Light Emitting Products Verizon NEBS Compliance Quality Assurance (NQA) Labeling Requirements f Light Emitting Products SIT.NEBS.TM.NPI.2005.030 February 21, 2006 SIT.NEBS.TM.NPI.2005.030 1 Infmation contained herein is subject

More information

JOY GLOBAL SERVICE BULLETIN

JOY GLOBAL SERVICE BULLETIN JOY GLOBAL SERVICE BULLETIN Bulletin No.: GSB0023 Page 1 of 4 Date Issued: 14 DECEMBER 2005 Product: CONTINUOUS MIINERS Type: ALL REMOTE CONTROL MACHINES Approval: MS/CCV/COH/RWW/RLB/LJL REMOTE CONTROL

More information

Pickens Savings and Loan Association, F.A. Online Banking Agreement

Pickens Savings and Loan Association, F.A. Online Banking Agreement Pickens Savings and Loan Association, F.A. Online Banking Agreement INTERNET BANKING TERMS AND CONDITIONS AGREEMENT This Agreement describes your rights and obligations as a user of the Online Banking

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

Yagi and Omni Antennas Installation Manual

Yagi and Omni Antennas Installation Manual Yagi and Omni Antennas Installation Manual 25500445 Rev. A0 0218 Printed in U.S.A. Copyright 2018 Federal Signal Corporation Limited Warranty This product is subject to and covered by a limited warranty,

More information

Electrical Measurement Safety. Sponsored By:

Electrical Measurement Safety. Sponsored By: Electrical Measurement Safety Sponsored By: About the Viewer Panel Slides: Go to the Links tab at the top and click on the link to download the PDF of the slides If you re watching the archive version,

More information

GrowSpan Series 2000 End Wall Cladding Kits

GrowSpan Series 2000 End Wall Cladding Kits GrowSpan Series 2000 End Wall Cladding Kits 35' Wide 2017 FarmTek All Rights Reserved. Reproduction is prohibited without permission. STK# 35' Wide (Twin Wall) Important Information READ THIS DOCUMENT

More information

GrowSpan Series 2000 End Wall Cladding Kits

GrowSpan Series 2000 End Wall Cladding Kits GrowSpan Series 2000 End Wall Cladding Kits 20' Wide 2017 FarmTek All Rights Reserved. Reproduction is prohibited without permission. STK# 20' Wide (Twin Wall) Important Information READ THIS DOCUMENT

More information

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

INSTALLATION, OPERATION AND MAINTENANCE GUIDE INSTALLATION, OPERATION AND MAINTENANCE GUIDE FOR INDOOR/OUTDOOR SINGLE PHASE ENCAPSULATED TRANSFORMERS Indoor/Outdoor Encapsulated Transformers The pictures used in this guide are only a representation

More information

Safety Manual. Omni-ID UHF Tags

Safety Manual. Omni-ID UHF Tags Safety Manual Omni-ID UHF Tags This page is intentionally left blank. Document Number 330556 (See Last Page for Revision Details) 2012 Extronics Limited. This document is Copyright Extronics limited. Extronics

More information

I Pr I P I OUT R L. Applications. Standards

I Pr I P I OUT R L. Applications. Standards Ref: ATO-XXX-B225-D10 I Pr = 10, 15, 16, 20, 30, 32, 50, 60, 63, 75 A ATO series is a split core current transformer for the electronic measurement of AC waveform current with galvanic separation between

More information

9007 Power Tube. VHF Linear Power Amplifier Tube 33 Kilowatt Peak Sync Output Thru VHF-TV Band

9007 Power Tube. VHF Linear Power Amplifier Tube 33 Kilowatt Peak Sync Output Thru VHF-TV Band 9007 Power Tube VHF Linear Power Amplifier Tube 33 Kilowatt Peak Sync Output Thru VHF-TV Band 14 db Gain High Gain-Bandwidth Products Efficient Forced-Air Cooling Full Input to 400 MHz CERMOLOX Construction

More information

iant200 iant212 iant213 iant214 iant215 iant216 iant217 iant218 iant219 iant220 iant221 iant222 Operating Manual iant2xx Series of Antennas

iant200 iant212 iant213 iant214 iant215 iant216 iant217 iant218 iant219 iant220 iant221 iant222 Operating Manual iant2xx Series of Antennas iant200 iant212 iant213 iant214 iant215 iant216 iant217 iant218 iant219 iant220 iant221 iant222 Operating Manual iant2xx Series of Antennas This page is intentionally left blank. Document Number 403449

More information

Report Of. Shielding Effectiveness Test For. DefenderShield. Test Date(s): September 1 October 2, 2012

Report Of. Shielding Effectiveness Test For. DefenderShield. Test Date(s): September 1 October 2, 2012 Report Of Test For Test Date(s): September 1 October 2, 2012 UST Project No: Total Number of Pages Contained Within This Report: 15 3505 Francis Circle Alpharetta, GA 30004 PH: 770-740-0717 Fax: 770-740-1508

More information

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS AS 2067 1984 Australian Standard Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv [Title allocated by Defence Cataloguing Authority: SWITCHGEAR ASSEMBLIES, ELECTRICAL AND

More information

LASER RADIATION REQUIREMENTS

LASER RADIATION REQUIREMENTS FLORIDA DEPARTMENT OF HEALTH LASER RADIATION REQUIREMENTS DECEMBER 15, 2016 EDITION LASER RADIATION REQUIREMENTS 4.002 As used in rule chapter 64E-4 Florida Administrative Code and this publication: (1)

More information

Receiver Type /Version Factory No. Frequency. Transmitter Type /Version Factory No. Frequency

Receiver Type /Version Factory No. Frequency. Transmitter Type /Version Factory No. Frequency Receiver Type /Version Factory No. Frequency Transmitter Type /Version Factory No. Frequency 1. STANDARD SPECIFICATION Portable transmitter. Receiver with integrated mounting holes. Multi-pin connecting

More information

Wilcoxon Research PA8HF power amplifier Operating guide

Wilcoxon Research PA8HF power amplifier Operating guide Wilcoxon Research PA8HF power amplifier Operating guide Meggitt Sensing Systems 20511 Seneca Meadows Parkway, Germantown MD 20876, USA Meggitt (Maryland), Inc d/b/a Meggitt Sensing Systems 97012 Rev C.1

More information

Series NRX with PXR - Instructions for Neutral Current Sensor Type NF

Series NRX with PXR - Instructions for Neutral Current Sensor Type NF Supersedes March 2016 Series NR Series NR with PR - Instructions for Neutral Current Sensor Type NF Instructions apply to: UL1066/ANSI, UL489 series NR NF frame IEC IZM16 WARNING (1) ONLY QUALIFIED ELECTRICAL

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

NSPL-500. AIS/VHF antenna splitter. User Manual ENGLISH.

NSPL-500. AIS/VHF antenna splitter. User Manual ENGLISH. NSPL-500 AIS/VHF antenna splitter User Manual ENGLISH www.bandg.com www.simrad-yachting.com www.lowrance.com Preface As Navico is continuously improving this product, we retain the right to make changes

More information

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc. Bruce L. Graves A Defining a Power System A power system is an assembly of generators, transformers, power lines, fuses, circuit breakers, protective devices, cables, and associated apparatus used to generate

More information

PC IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases

PC IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases PC57.13.3 IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases OUTLINE Scope References Need for grounding; Warning Definition of Instrument transformers Grounding secondary

More information

Power Tube. Beam Power Tube

Power Tube. Beam Power Tube 8977 Power Tube Beam Power Tube - 7 kw Aural Output Through VHF-TV Band - 19 db Gain - CERMOLOX Beam Power Tube - Full Input to 400 MHz - Forced-Air Cooled The BURLE 8977 is intended specifically to meet

More information

FM Safety Manual. Omni-ID UHF Tags

FM Safety Manual. Omni-ID UHF Tags FM Safety Manual Omni-ID UHF Tags This page is intentionally left blank. Document Number 334169 (See Last Page for Revision Details) 2012 Extronics Limited. This document is Copyright Extronics limited.

More information

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS AND MEDIUM-SIZE FACILITIES (5,000-25,000KW) CONNECTED

More information

INTELLIMETER REGISTER

INTELLIMETER REGISTER INTELLIMETER REGISTER MODEL RG2 INSTALLATION AND CONNECTIONS INSTALLATION MANUAL WARNING: Any work on or near energized metering equipment can present a danger of electrical shock. All work on these products

More information

Model 4210-MMPC-W. Multi-measurement Prober Cable Kit. Overview

Model 4210-MMPC-W. Multi-measurement Prober Cable Kit. Overview Model 4210-MMPC-W Keithley Instruments, Inc. Multi-measurement Prober Cable Kit 28775 urora Road Quick Start Guide Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Overview The Keithley Instruments

More information

FR-ABR-(H)0.4K to 22K

FR-ABR-(H)0.4K to 22K TRANSISTORIZED INVERTER INSTRUCTION MANUAL HIGH-DUTY BRAKE RESISTOR FR-ABR-(H)0.4K to 22K H Thank you for choosing the Mitsubishi transistorized inverter option unit. This instruction manual gives handling

More information

RULES OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION DIVISION OF RADIOLOGICAL HEALTH CHAPTER USE OF X-RAY APPARATUS

RULES OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION DIVISION OF RADIOLOGICAL HEALTH CHAPTER USE OF X-RAY APPARATUS RULES OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION DIVISION OF RADIOLOGICAL HEALTH CHAPTER 0400-20-06 USE OF X-RAY APPARATUS TABLE OF CONTENTS 0400-20-06-.01 Purpose 0400-20-06-.06 Veterinary

More information