Using DFR to determine dissipation factor temperature dependence

Size: px
Start display at page:

Download "Using DFR to determine dissipation factor temperature dependence"

Transcription

1 Using DFR to determine dissipation factor temperature dependence by Matz Ohlen and Peter Werelius, Megger With an aging power component population, today s electrical utility industry faces a tough challenge as failures and consequent repair and revenue loss may inflict major costs. Transformers have become one of the most mission critical components in the electrical grid. The need for reliable diagnostic methods drives the world s leading experts to evaluate new technologies that improve reliability and optimise the use of the power network. Modern technology and developments in signal acquisition and analysis techniques have provided new tools for transformer diagnostics. Of particular interest are dielectric response measurements where insulation properties of oil-paper systems can be investigated. Dielectric frequency response(dfr), was introduced more than a decade ago and has been thoroughly evaluated in a number of research projects and field tests with good results. DFR data in combination with mathematical modelling of the oil-paper insulation is proven as an excellent tool for moisture assessment. Since the modelling theory contains influence of temperature, DFR and modelling can be used to calculate the temperature dependence of the insulation system. The condition of the insulation is an essential component of the operational reliability of electrical power transformers, generators, cables and other high voltage equipment. Transformers with high moisture content cannot sustain higher loads without risk. Bushings and cables with high dissipation factor at high temperature can explode due to thermal runaway. It is also very important to identify good units in the aging population of equipment. Adding just a few operating years to the expected end-of-life for a transformer or cable means substantial cost savings. Traditional dissipation factor measurements The most common insulation diagnostic test involves measuring capacitance and power factor at 50/60 Hz. Most tests are done at 10 kv (or sometimes Typical power factor 20 C New Old Warning-alert limit Power transformers, oil insulated 0,2 0,4% 0,3,5% > 0,5% Bushings 0,2 0,3% 0,3 0,5% > 0,5% lower, depending on the voltage rating of the component), and at operating temperature, but there are also tests with variable voltage (tip-up/step-up testing) as well as tests where power factor versus temperature is measured. Analysis is based on (historical) statistics and comparison with factory values. Since insulation properties depend on temperature, temperature compensation has to be used for measurements not performed at 20 C. This is normally achieved by using temperature correction table values for certain classes of devices [1]. In IEEE , typical power factor measurement values for transformers and bushings are categorised. Typical temperature corrections are shown in Fig. 1. It is obvious that the given values are approximate guidelines only. IEEE states; The power factors recorded for routine overall tests on older apparatus provide information on the general condition of the ground and inter-winding insulation of transformers and reactors. They also provide a valuable index of dryness, and are helpful in detecting undesirable operating conditions and failure hazards resulting from moisture, carbonisation of insulation, defective bushings, contamination of oil by Table 1: Typical power factor values (IEEE). dissolved materials or conducting particles, improperly grounded or ungrounded cores, etc. While the power factors for older transformers will also be <0,5% (20 C, power factors between 0,5% and 1,0% (20 C) may be acceptable; however, power factors >1,0% (20 C) should be investigated. Dielectric frequency response measurements The first field instrument for DFR measurements was introduced 1995 [2]. Since then the numerous developments of the technology have taken place and several international projects/reports define dielectric response measurements together with insulation modelling as the preferred method for measuring moisture content of the cellulose insulation in power transformers [3,4,5]. In DFR tests, capacitance and dissipation/power factor is measured. The measurement principle and setup is very similar to traditional 50/60 Hz testing with the difference that a lower measurement voltage is used (200 V) and instead of measuring at line frequency 50/60 Hz, insulation properties are measured over a frequency range, typically from 1 khz to 1 mhz. The results are normally presented as capacitance and/or tan delta/power factor versus frequency. The measurement setup is Fig. 1: Typical power factor temperature corrections. Fig. 2: DFR/FDS test setup. energize - April Page 38

2 Fig. 3: DFR measurements on four different transformers at different temperatures with moisture content ranging from 0,3 to 3,4%. Fig. 5: MODS moisture analysis. Fig. 4: Parameters that effects the dissipation factor at various frequencies. Fig. 6: MODS analysis for two transformers with different oil quality and moisture content. shown in Fig. 2 and typical DFR results from measurement on transformers in different conditions in Fig. 3. Moisture assessment The capability of DFR to measure dissipation factor as function of frequency, gives the user a powerful tool for diagnostic testing. Moisture assessment is one example. High moisture levels in transformers is a serious issue since it limits the maximum loading capacity (IEEE Std C ) and the aging process is accelerated. Accurate knowledge of the actual moisture content is necessary in order to make decisions on corrective actions, replacement/ scrapping or relocation to a different site in the network with reduced loading. Using DFR for determining moisture content in the oil-paper insulation inside an oilimmersed power transformer has been described in detail in several papers and articles elsewhere [3,4,5], and is only briefly summarised in this paper. The dissipation factor for an oil/cellulose insulation plotted against frequency shows a typical inverted S-shaped curve. With increasing temperature the curve shifts towards higher frequencies. Moisture influences mainly the low and the high frequency areas. The middle section of the curve with the steep gradient reflects oil conductivity. Fig. 4 describes parameter influence on the master curve. Using DFR for moisture determination is based on a comparison of the transformers dielectric response to a modelled dielectric response (master curve). A matching algorithm rearranges the modelled dielectric response and delivers a new curve that reflects the measured transformer. The moisture content along with the oil conductivity for the master curve is presented. Only the insulation temperature (top oil temperature and/or winding temperature) needs to be entered as a fixed parameter. Two different transformers are shown in Fig. 6. The two units have the same 0,7%, 50/60 Hz dissipation factor, characterised by IEEE as warning/alert status calling for investigation. The investigation is done as moisture analysis using MODS. The two transformers are very different and maintenance measures for the two would also be different. Transformer 1 has good oil but needs drying. Transformer 2 has low moisture but needs oil change or regeneration. Bushing diagnostics Aging/deterioration of high-voltage bushings is a growing problem and manufacturers as well as utilities and test system providers are suggesting and testing various methods for detecting bushing problems before they turn into catastrophic failures. This includes on-line monitoring as well as off-line diagnostic measurements [6,7]. Traditional 50/60 Hz dissipation/power factor testing may give an indication of aging/high moisture content, especially if performed at various temperatures as shown in Fig. 7, [8] and Fig. 8, [10]. As seen in Fig. 7: Dissipation factor (%) vs temperature for OIP bushings with various moisture content [6]. Fig. 8: Power factor (%) vs temperature ( C) for good and bad bushings, [10]. energize - April Page 39

3 Fig. 9: Power factor at 60 Hz for oil impregnated cellulose insulation with various moisture contents as a function of temperature (ºC). Fig. 11: Bushing dissipation factor as a function of temperature. Measured and converted data compared to published data, [6]. Fig. 10: Relationship between power factor values at different frequencies taken at different temperatures. Fig. 12: Power factor as function of temperature (ºC) for four different transformers [11]. Fig. 7, dissipation factor values at lower temperatures are quite similar from very low to moderate moisture content. A significant change is not seen until measuring at about 50 C. The bad bushing in Fig. 8 can be compared with bushing data in Fig. 7. Estimated moisture content is about 4%. Increased dissipation factor at higher temperatures is a good indicator of bushing problems. Catastrophic bushing failures (explosions) are often caused by what is called thermal runaway. A high dissipation factor at higher temperatures result in an increased heating of the bushing which in turn increases the losses causing additional heating which increases the losses even further and the bushing finally explodes. Individual temperature correction (ITC) DFR measurements and analysis together with modelling of the insulation system includes temperature dependence. A new methodology (patent pending) is to perform DFR measurements and convert the results to dissipation factor at 50/60 Hz as a function of temperature. This technique has major advantages in measurement simplicity. Instead of time consuming heating/cooling of the bushing and doing several measurements at various temperatures, one DFR measurement is performed and the results are converted to 50/60 Hz tan delta values as a function of temperature. A result of the technique is shown and compared with the classical results presented by Blodget [9] in Fig. 9. The method is based on the fact that a certain power factor measurement at a certain frequency and temperature corresponds to a measurement made at a different temperature at a different frequency. The conversion calculations are based on Arrhenius' law/equation, describing how the insulation properties are changing over temperature. The relationship is depicted for three different activation energies in Fig. 10. Applying this technique on real-world DFR measurements on bushings gives results as shown in Fig. 11. Two bushings, OK and bad are compared with manufacturer's values from Fig 7, [6]. The bad bushing is estimated to have about 4% moisture and should be considered at risk. Temperature correction tables such as in IEEE/C give average values assuming average conditions and are not correct for an individual transformer or bushing. This was confirmed in field experiments and some utilities try to avoid applying temperature correction by recommending performing measurements within a narrow temperature range [11]. Examples are shown in Figs. 12 and 13. Power factor was measured at 10 kv on four transformers and three bushings of different age, condition and at various temperatures. Temperature dependence is very different for the transformers and bushings and using standard temperature correction tables will not give correct values for the 20 C reference value. With DFR and the technique for converting data to temperature dependence, it Fig. 13: Power factor as function of temperature (ºC) for three different bushings [11]. Fig. 14: Standard temperature correction compared with individual temperature correction for samples of GE Type U bushings. energize - April Page 40

4 Fig. 15: Temperature correction for transformers in various conditions. Fig. 17: Tan delta at 50 Hz for dry Kraft paper as function of temperature. Fig. 16: Dissipation factor as function of frequency for dry Kraft paper. Fig. 18: DFR measurements and moisture analysis results at different temperatures. is possible to do accurate, individual temperature compensation. For a good component, the temperature dependence is weak. When the component gets older and/or deteriorated, the temperature correction factor becomes much larger, i.e. the temperature correction is a function of aging status. This is in line with several projects and studies [8,10]. Examples of individual temperature correction for bushings are shown in Fig. 14. Manufacturer's table data is only valid for as-new bushings. As soon as the bushing starts to show deterioration, the temperature dependence increases. Bad bushings have a very large temperature correction. Individual temperature correction for transformers is more complex compared to single-material components e.g. bushings. The oil-paper insulation activation energy constant W a in Arrhenius' law, for oil impregnated paper is typically 0,9 1 ev, while for transformer oil W a is typically around 0,4 0,5 ev Individual temperature corrections for transformers of various ages are shown in Fig. 15. transformer data is summarised in Table 2. As seen in the figure, each transformer has its individual temperature correction. New units have a negative correction for slightly elevated temperatures and will show dramatically different results if the standard table are used. Aged transformers show the same behaviour as the standard tables but with a much stronger temperature dependence compared to the average IEEE values. Experimental results Oil impregnated Kraft paper Samples of Kraft paper with various moisture contents was measured at different temperatures [13]. Results for dry paper, moisture content <0,5% is shown in Fig. 16 Using DFR technique to estimate temperature dependence based on measurements at one temperature only, gives the results shown in Fig. 17. As seen in the diagram, the calculated temperature dependence matches very closely to the actually measured dissipation factors. Transformers DFR measurements on a distribution Manufacturer Year Moisture Power rating Status Pauwels ,4% 80 MVA New, at factory Pauwels ,3% 20 MVA New, at utility Westinghouse ,5% 40 MVA Used, spare at utility Yorkshire ,5% 10 MVA Used and scrapped Table 2: Transformer data. transformer at various temperatures are shown in Fig. 18. As expected the moisture analysis (moisture in paper insulation) show the same values independent of insulation temperature (insulation temperature was estimated as winding temperature, measured as winding resistance). Oil and paper insulation must be treated separately when modeling a transformer to estimate temperature dependence. This is described in Fig. 18. Combining the modeling results and converting to temperature dependence gives the temperature curves in Fig. 20. Also for this insulation system containing two different temperature dependent materials, the conversion gives results very close to the actual measured tan delta values. Bushings An Asea/ABB GOB OIP bushing, used but expected to be in good condition, has been measured at different temperatures. Tan Delta and DFR measurements were performed at three temperatures; Indoor at 22 C, outdoor at -8 C and in a heated chamber at 42 C. Results are shown in Table 3. Calculated temperature corrections using DFR results are presented together with the manufacturer's average temperature correction data in Fig. 20. For the specific bushing, individual temperature correction (ITC) both at 22 C and 42 C fits very well with manufacturer's data, indicating a bushing in normal condition. energize - April Page 42

5 Fig. 19: Dissipation factor as function of frequency for oil and cellulose insulation. Fig. 21: Temperature correction curves for ABB/ASEA GOB bushing. Insulation Temperature, C Measured Power kv Comments -8 0,86 1,04 1, ,46 0, ,34 0,32 Voltage dependent at low temperatures Table 3: Power factor measurents on ABB GOB bushing. Fig. 20: Tan delta at 50 Hz for a distribution transformer as function of temperature. Discussion The temperature dependence of the dissipation factor of an insulating material needs to be considered when comparing measurement results with previous tests or factory values. Historically this has been done by the use of average temperature correction tables. Results are disappointing and many asset owners try instead to perform diagnostic measurements at a specific (narrow) temperature range. The new method of using frequency data and calculate/model the temperature dependence of the actual component offers an alternative to waiting for the correct temperature and then do the test. It gives the possibility to have correct 20 C reference values and also to make a correct comparison to previously measured non-corrected data at other insulation temperatures. How accurate the individual temperature correction can be is a valid question. As presented in this paper, using standard tables can easily give power factor errors in the order of ±50 100% or more. The ITC examples presented show good correlation between the calculated and actually measured dissipation factor at various temperatures. However, envisioning a standard method used for a large population of components of various design and makes, a certain variation is anticipated. Preliminary tests with commercial test instruments and SW indicates that the inaccuracy for ITC is about ±5 10% at the extremes of a 5 50 C temperature range i.e. correcting from 5 or 50 to 20 reference. Summary and conclusions Dielectric Frequency Response (DFR/FDS) measurement is a technique/methodology for general insulation testing and diagnostics. In comparison with standard 50/60 Hz dissipation factor measurements, DFR measurements provide the following advantages: Capability of performing individual temperature correction of measured 50/60 Hz dissipation/power factor at various temperatures to values at reference temperature, 20 C. Capability of comparing test results from a new measurement at a certain temperature to another measurement at a different temperature Capability of estimating dissipation/ power factor at operating temperature in order to assess risk of thermal runaway catastrophic failure. Capability of estimating the moisture content of oil-immersed cellulose insulation in power transformers and bushings Capability of investigating increased dissipation factor in power components The insulation properties are very important for determining the condition of a power system component. Knowing the condition helps to avoid potential catastrophic failure and identifying good units and decide upon correct maintenance can save significant money due to postponed investment costs. References [1] "IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus; Part 1: Oil Filled Power Transformers, Regulators, and Reactors, IEEE [2] P Werelius et al, Diagnosis of Medium Voltage XLPE Cables by High Voltage Dielectric Spectroscopy, paper presented at ICSD [3 ]U Gäfvert et al, Dielectric Spectroscopy in Time and Frequency Domain Applied to Diagnostics of Power Transformers, 6th International Conference on Properties and Applications of Dielectric Materials, June 21-26, 2000, Xi'an, China. [4] S M Gubanski et al, "Dielectric Response Methods for Diagnostics of Power Transformers, Electra, No. 202, June 2002, pp also in CIGRE Technical Brochure, No. 254, Paris [5] S M Gubanski et al, Reliable Diagnostics of HV Transformer Insulation for Safety Assurance of Power Transmission System. REDIATOOL - a European Research Project, paper D1-207 CIGRÉ [6] Swedish Bushings Plant Sees Growth in RIP Designs, INMR Quarterly, Issue 68, [7] J M Braun et al. Accelerated Aging and Diagnostic Testing of 115 kv Type U Bushings, paper presented at IEEE Anaheim [8] C Kane, Bushing, PD and Winding Distortion Monitoring, paper presented at ABB Seminar Power Transformer Health Monitoring and Maintenance Johannesburg [9] R B Blodget, Influence of Absorbed Water and Temperature on Tan Delta and Dielectric Constant of Oil-Impregnated Paper Insulation, Trans. AIEE, [10] R Brusetti, Experience with On-line Diagnostics for Bushings and Current Transformers, NETA Fall 2002, paper A335. [11] R K Tyagi, S Victor, N S Sodha, Application of Temperature Correction Factors for dissipation factor Measurements for Power Transformers A case study, Doble Client Conference, Vadodara, India [12] P Werelius, M Ohlen, Dielectric Frequency Response Measurements on Power Transformers, EuroTechCon 2008, Liverpool, UK. [13] R Niemanis et al, Determination of Moisture Content in Mass Impregnated Cable Insulation Using Low Frequency Dielectric Spectroscopy, IEEE Power Engineering Society Summer Meeting 2000, Seattle, Washington, USA. Contact Marius Pitzer, Megger, Tel , marius.pitzer@megger.com energize - April Page 43

Matz Ohlen Director Transformer Test Systems. Megger Sweden

Matz Ohlen Director Transformer Test Systems. Megger Sweden Matz Ohlen Director Transformer Test Systems Megger Sweden Frequency response analysis of power transformers Measuring and analyzing data as function of frequency, variable frequency diagnostics Impedance

More information

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy IDAX 300 Insulation Diagnostic Analyzer Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy 1 Frequency Domain Spectroscopy Hi V A Lo Ground C HL Measure at several frequencies Use

More information

Power Factor Insulation Diagnosis: Demystifying Standard Practices

Power Factor Insulation Diagnosis: Demystifying Standard Practices Power Factor Insulation Diagnosis: Demystifying Standard Practices Dinesh Chhajer, PE 4271 Bronze Way, Dallas Tx Phone: (214) 330 3238 Email: dinesh.chhajer@megger.com ABSTRACT Power Factor (PF) testing

More information

Dielectric analysis of high-voltage power transformers DIAGNOSIS ABSTRACT KEYWORDS. 1. Introduction

Dielectric analysis of high-voltage power transformers DIAGNOSIS ABSTRACT KEYWORDS. 1. Introduction DIAGNOSIS ABSTRACT Dielectric tests have been used for decades for diagnosis of power transformers and bushings. In addition to the traditional tests at line frequency, modern types of dielectric tests

More information

Effective maintenance test techniques for power transformers

Effective maintenance test techniques for power transformers Effective maintenance test techniques for power transformers by Alexander Dierks, Herman Viljoen, Alectrix, South Africa, and Dr. Michael Krüger, Omicron Electronics, Austria Due to ever-increasing pressure

More information

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB MV Power Cable Diagnostics by Frequency Domain Spectroscopy Peter Werelius Programma Electric AB Frequency Domain Spectroscopy Measurements of insulation capacitance and losses in a frequency interval

More information

TECHNIQUES AND STANDARD

TECHNIQUES AND STANDARD TRANSFORMER TESTING TECHNIQUES AND STANDARD DEVELOPMENT BY DIEGO M. ROBALINO, PhD, PMP, MEGGER-AVO Training Institute Transformer manufacturers and field operators have always benefitted when new technologies

More information

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Alexander Dierks, Herman Viljoen, Alectrix (Pty) Ltd, South Africa

More information

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)

More information

Advanced Diagnostic Testing Services. Provides detailed and reliable results

Advanced Diagnostic Testing Services. Provides detailed and reliable results Advanced Diagnostic Testing Services Provides detailed and reliable results Advanced Diagnostic Testing Services from the world s leading manufacturer of power transformers ABB leadership begins with our

More information

Why is water killing power transformer insulation? Water is a slow but deadly poison for power transformers

Why is water killing power transformer insulation? Water is a slow but deadly poison for power transformers Table of Contents Why is water killing power transformer insulation? Water is a slow but deadly poison for power transformers Dielectric frequency response analysis is a powerful tool used to determine

More information

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander

More information

Transformer condition assessment with an integrated test van

Transformer condition assessment with an integrated test van Transformer condition assessment with an integrated test van 1 2012 SebaKMT Measuring and locating techniques MADE in GERMANY 2 Testing and Standards for Power Transformers CIGRE CIGRE Brochure 342 (SFRA-FRAX)

More information

CDAX 605 High Precision Capacitance & Dissipation Factor Test Set

CDAX 605 High Precision Capacitance & Dissipation Factor Test Set CDAX 605 High Precision Capacitance & Dissipation Factor Test Set 1 Tan delta and capacitance measurements Hi V A Lo Ground C HL Measure with AC test signal, use Ohms law to calculate: Dissipation factor

More information

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to

More information

Insulation Assessment of Oil Impregnated Paper Condenser Bushings using Dielectric Frequency Response Technique

Insulation Assessment of Oil Impregnated Paper Condenser Bushings using Dielectric Frequency Response Technique Indian Journal of Science and Technology, Vol 10(21), DOI: 10.17485/ijst/2017/v10i21/114368, June 2017 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 Insulation Assessment of Oil Impregnated Paper

More information

USING DAMPED AC VOLTAGES

USING DAMPED AC VOLTAGES MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States

More information

ABB Power Products Service

ABB Power Products Service Raben Naidoo, Technology days, May 21-22th, 2014, Cape Town, South Africa, Enhanced availability of transformers via transformer remote monitoring - TEC ABB Power Products Service Why a session on availability?

More information

Field Measurement of Transmission Cable Dissipation Factor

Field Measurement of Transmission Cable Dissipation Factor Workshop 2000, Alexandria, Virginia, 13 & 14 September 2000 paper No.: 1 Field Measurement of Transmission Cable Dissipation Factor John H. Cooper, Power Delivery Consultants, Inc. Abstract This presentation

More information

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM, ONLINE OFFLINE VERSUS FEATURE PARTIAL DISCHARGE TESTING FOR CABLE ASSESSMENT B Y WIL L IAM H IG INBOT H AM, EA Technology, LLC Medium voltage cables have three distinct phases to their lifecycle: (1) new

More information

Correlation between time and frequency domain polarisation measurements for transformer moisture assessment

Correlation between time and frequency domain polarisation measurements for transformer moisture assessment Australasian Universities Power Engineering Conference (AUPEC 24) 26-29 September 24, Brisbane, Australia Correlation between time and frequency domain polarisation measurements for transformer moisture

More information

Transformers handling and transport

Transformers handling and transport Special tests (Credit: http://www.breakbulk.com/wp-content/uploads/2015/02/20141117160247x.jpg) Transformers handling and transport Damages that may arise and how to find them Table of contents summary

More information

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser - OMICRON Transformers Diagnostic Testing - OVERALL DGA Oil Screen Power Factor / Capacitance Exciting Current Transformer

More information

Vallabh Vidyanagar, Anand, INDIA

Vallabh Vidyanagar, Anand, INDIA IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 1 Ver. V (Feb. 2014), PP 01-06 Interpretation of Sweep Frequency Response Analysis

More information

Transformer Shunt Fault Detection using Two Techniques

Transformer Shunt Fault Detection using Two Techniques Transformer Shunt Fault Detection using Two Techniques Swathy Sasikumar 1, Dr. V. A. Kulkarni 2 P.G. Student, Department of Electrical Engineering, Government College of Engineering, Aurangabad, Maharashtra,

More information

Dispersing the clouds gain clear insight into your bushings using advanced diagnostic methods

Dispersing the clouds gain clear insight into your bushings using advanced diagnostic methods Topic Dispersing the clouds gain clear insight into your bushings using advanced diagnostic methods Abstract: Bushing diagnosis can include various methods, from a simple visual inspection or a conventional

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

Cable testing and diagnostics

Cable testing and diagnostics Cable testing and diagnostics To ensure the flow Cost-optimised maintenance through cable diagnostics The sheath and cable testing supports you in assessing whether a cable system is safe and ready to

More information

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES Hein PUTTER Frank PETZOLD Philipp LEGLER Megger Germany Megger Germany Megger - Germany hein.putter@megger.com frank.petzold@megger.com philipp.legler@megger.com

More information

N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon

N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon POWER TRANSFORMERS Factory condition POWER TRANSFORMERS Site condition POWER TRANSFORMER FAULTS Faults in a Transformer 1. Internal Faults

More information

The measurement and normalisation of dielectric dissipation factor for diagnostics of transformer insulation

The measurement and normalisation of dielectric dissipation factor for diagnostics of transformer insulation DIAGNOSIS The measurement and normalisation of dielectric dissipation factor for diagnostics of transformer insulation Introduction The Dielectric Dissipation Factor (DDF) is known as the loss factor or

More information

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation CIGRE SC A1 & D1 JOINT COLLOQUIUM October 24, 2007 Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation S. A. BHUMIWAT Independent Consultant

More information

The importance of partial discharge testing throughout the development and operation of power transformers

The importance of partial discharge testing throughout the development and operation of power transformers The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense

More information

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis feature By brandon dupuis An Introduction to Electrical diagnostic TesTIng of Power Transformers 38 Transformers are the largest, most expensive, and highly critical components of most utility substations.

More information

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results 2016 International Conference on Electrical Engineering and Automation (ICEEA 2016) ISBN: 978-1-60595-407-3 Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results Cristian DAN

More information

Onsite Mobile AC High Voltage Test System

Onsite Mobile AC High Voltage Test System TSGMF(T) series Onsite Mobile AC High Voltage Test System Onsite mobile AC high voltage test systems are used for withstand voltage testing, partial discharge measurement, tan delta measurement to instrument

More information

Be on guard for effective testing: Introduction

Be on guard for effective testing: Introduction Be on guard for effective testing: Introduction The development of the insulation tester by Evershed and Vignoles is part of our electrical history, with insulation testers produced by Megger Instruments

More information

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,

More information

Chapter 7 Conclusion 7.1 General

Chapter 7 Conclusion 7.1 General Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due

More information

MONTRANO. Continuous monitoring system for power transformers

MONTRANO. Continuous monitoring system for power transformers MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in

More information

The Basics of Insulation Testing

The Basics of Insulation Testing The Basics of Insulation Testing Feature by Jim Gregorec IDEAL Industries, Inc. What Is Insulation Testing? In a perfect world, all the electrical current sent along a conductive wire would reach its intended

More information

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen Aspects of PD interpretation in HV power cables by Edward Gulski, Piotr Cichecki, Rogier Jongen General There are several aspects having influence on the diagnostic information and the condition judgment

More information

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:

More information

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications: SGMF(T) series Onsite Mobile AC High Voltage Test System On-site AC high voltage test systems are used for voltage withstanding test, partial discharge measurement, tan delta measurement on those instrument

More information

Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables

Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables 163 24 th Nordic Insulation Symposium on Materials, Components and Diagnostics Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables Sarajit Banerjee, Ali Naderian Kinectrics Inc., Toronto,

More information

Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA)

Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA) Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA) Priti G 1*, Sindekar AS 2 P.G. Scholar, Department of Electrical Engineering, Government College of

More information

Maintenance & Diagnosis Strategies. for. High Voltage Substations

Maintenance & Diagnosis Strategies. for. High Voltage Substations Maintenance & Diagnosis Strategies for High Voltage Substations 1/ 52 Robin Fischer, 28 April 2004 Diagnosis of Substation Equipment Power Transformers Instrument Transformers Switch-Gears Breakers Coils

More information

New Techniques for the Monitoring of Transformer Condition

New Techniques for the Monitoring of Transformer Condition New Techniques for the Monitoring of Transformer Condition Thomas Prevost OMICRON electronics USA IEEE T&D Conference Chicago, Illinois April 17, 2014 Agenda Monitoring Expectations & Needs Bushing Monitoring

More information

INCREASE TRANSFORMER RELIABILITY AND AVAILBILITY: FROM CONDITION ASSESSMENT TO SITE REPAIR

INCREASE TRANSFORMER RELIABILITY AND AVAILBILITY: FROM CONDITION ASSESSMENT TO SITE REPAIR INCREASE TRANSFORMER RELIABILITY AND AVAILBILITY: FROM CONDITION ASSESSMENT TO SITE REPAIR Pierre Lorin Pravin Khanna Peter Werle Lars Eklund pravin.t.khanna@us.abb.com peter.werle@de.abb.com ABB Transformers

More information

HV AC TESTING OF SUPER-LONG CABLES

HV AC TESTING OF SUPER-LONG CABLES HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The

More information

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences

More information

AMR Current Sensors for Evaluating the Integrity of Concentric Neutrals in In-Service Underground Power Distribution Cables

AMR Current Sensors for Evaluating the Integrity of Concentric Neutrals in In-Service Underground Power Distribution Cables AMR Current Sensors for Evaluating the Integrity of Concentric Neutrals in In-Service Underground Power Distribution Cables Michael Seidel Dept. of Mechanical Engineering mjseidel@berkeley.edu Kanna Krishnan

More information

Revision of C Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components. Mike Spurlock Chairman

Revision of C Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components. Mike Spurlock Chairman Revision of C57.143-2012 Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components Mike Spurlock Chairman All participants in this meeting have certain obligations under

More information

DIAGNOSIS. TRANSFORMERS MAGAZINE Volume 3, Issue 2

DIAGNOSIS. TRANSFORMERS MAGAZINE Volume 3, Issue 2 DIAGNOSIS 26 TRANSFORMERS MAGAZINE Volume 3, Issue 2 ADVERTORIAL A test instrument must effectively overcome measuring complexities that are present in a live power system test environment and must consistently

More information

PD Testing Considerations for MV Plant Cables

PD Testing Considerations for MV Plant Cables PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz

More information

Advanced Insulation Diagnostic by Dielectric Spectroscopy

Advanced Insulation Diagnostic by Dielectric Spectroscopy Page 1 of 13 Advanced Insulation Diagnostic by Dielectric Spectroscopy By Maik Koch, Michael Krueger and Markus Puetter Page 2 of 13 Second Page is left blank Page 3 of 13 Abstract Advanced Insulation

More information

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES HEIN PUTTER Productmanager cable testing and -diagnosis Megger Site Germany 1 13 th Insucon conference 16-18 th Mai 2017, Birmingham, UK Agenda Introduction

More information

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002 Page 1 of 10 January 9, 2002 TECHNICAL BULLETIN 012a Principles of Insulation Testing Introduction Probably 80% of all testing performed in electrical power systems is related to the verification of insulation

More information

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C S O L U T I O N S Y O U R S O U R C E F O R T O P Q U A L I T Y T E S T E Q U I P M E N T w w w. h v t e c h n o l o g i e s. c o m Company

More information

Transformer energisation after network blackout

Transformer energisation after network blackout Transformer energisation after network blackout Impact on network restoration and improvement of its process ABSTRACT According to ENTSO-E Network policy 5, responsibility for system restoration after

More information

FRAX Series Sweep Frequency Response Analyzers

FRAX Series Sweep Frequency Response Analyzers FRAX Series Highest dynamic range and accuracy in the industry Fulfills international standards for SFRA measurements Advanced analysis and decision support built into the software. FRAX 150 with built

More information

We can classify test failure modes in power transformers according to transformer components

We can classify test failure modes in power transformers according to transformer components ON-SITE TESTS We can classify test failure modes in power transformers according to transformer components ABSTRACT To prevent unexpected outages it is necessary to implement a field test programme. It

More information

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

GENERATOR TESTING APPLICATION GUIDE.  reliable. precision. GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing

More information

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER JESSE M LOPEZ CPS ENERGY USA EMILIO MORALES CRUZ QUALITROL USA SUMMARY Power transformers are essential

More information

Evaluation of Distribution Line Spacers through the Leakage Current Monitoring

Evaluation of Distribution Line Spacers through the Leakage Current Monitoring Tsinghua University, Beijing, China, August -9, H-6 Evaluation of Distribution Line Spacers through the Leakage Current Monitoring A. G. Kanashiro *, W. Pinheiro and G. F. Burani Institute of Electrotechnics

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

Operational Management of Grid Transformers An Experience of POWERGRID

Operational Management of Grid Transformers An Experience of POWERGRID Operational Management of Grid Transformers An Experience of POWERGRID 1.0 Introduction P.N. Dixit, GM; S. Victor, AGM; V.K. Bhaskar, CM; Gunjan Agrawal, Manager Operation Services Department Power Grid

More information

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV

More information

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES Edward GULSKI, Delft University of Technology, (The Netherlands), e.gulski@tudelft.nl Johan J SMIT, Delft University of Technology, (The Netherlands),

More information

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS Pantelis D. AGORIS 1, Sander MEIJER 1, Edward GULSKI 1, Johan J. SMIT 1, A. Jos L.M. KANTERS 2 1 Delft University of Technology - The Netherlands 2 TenneT

More information

Diagnostic measurements on instrument transformers. Part II. A classification and overview of diagnostic measurements DIAGNOSIS EVENTS ABSTRACT

Diagnostic measurements on instrument transformers. Part II. A classification and overview of diagnostic measurements DIAGNOSIS EVENTS ABSTRACT EVENTS DIGNOSIS BSTRCT Part 1 of this article, published in Vol ume 3 Issue 4, pages 100ff, describes the measurements of excitation, wind ing resistance, turns ratio and accu racy as the most common diagnostic

More information

Performing reliable and reproducible frequency response measurements on power transformers

Performing reliable and reproducible frequency response measurements on power transformers Topic Performing reliable and reproducible frequency response measurements on power transformers Prof. Dr. Stephanie Uhrig, Munich University of Applied Sciences Michael Rädler, OMICRON electronics GmbH

More information

Design Improvement by Diagnostics of Transformers still in Operation and of Apparatuses taken out of Service

Design Improvement by Diagnostics of Transformers still in Operation and of Apparatuses taken out of Service Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006 "New Diagnostic Concepts for Better Asset Management" Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque,

More information

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment

More information

PHG 70 TD PD / PHG 80 TD PD

PHG 70 TD PD / PHG 80 TD PD PHG 70 TD PD / PHG 80 TD PD BAUR VLF test and diagnostics system Functions Universal test and diagnostics system flexible, modular, extendable Cutting-edge testing and diagnostics technology: VLF truesinus

More information

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon OMICRON Seminar on Partial Discharge Diagnostics on HV Assets January 30, 2018 Beirut, Lebanon Substation Asset Testing and Diagnosis LOW ACCURACY LEVEL HIGH Take better maintenance decisions through accurate

More information

Primary Test Manager (PTM) Testing and management software for primary assets

Primary Test Manager (PTM) Testing and management software for primary assets Primary Test Manager (PTM) Testing and management software for primary assets Asset diagnostics now easier than ever How well do you know your assets? High-voltage assets are subjected to aging and wear

More information

Winding Temperature Measurement in a 154 kv Transformer Filled with Natural Ester Fluid

Winding Temperature Measurement in a 154 kv Transformer Filled with Natural Ester Fluid J Electr Eng Technol Vol. 8, No. 1: 156-162, 2013 http://dx.doi.org/10.5370/jeet.2013.8.1.156 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Winding Temperature Measurement in a 154 kv Transformer Filled

More information

R. MALEWSKI* J. SUBOCZ M. SZROT, J. PŁOWUCHA, R. ZALESKI Instytut Elektrotechniki Politechnika Szczecińska Energo-Complex Poland

R. MALEWSKI* J. SUBOCZ M. SZROT, J. PŁOWUCHA, R. ZALESKI Instytut Elektrotechniki Politechnika Szczecińska Energo-Complex Poland 21, rue d Artois, F-75008 PARIS A2-209 CIGRE 2008 http : //www.cigre.org CONDITION ASSESSMENT OF MEDIUM-POWER TRANSFORMERS USING DIAGNOSTIC METHODS: PDC, FDS, FRA TO SUPPORT DECISION TO MODERNIZE OR REPLACE

More information

TRAX Transformer and Substation Test System

TRAX Transformer and Substation Test System TRAX Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components

More information

TRAX Transformer and Substation Test System

TRAX Transformer and Substation Test System Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components for

More information

Power Measurements and Basic Electrical Diagnostic Tests

Power Measurements and Basic Electrical Diagnostic Tests Power Measurements and Basic Electrical Diagnostic Tests Instrument Basics Burden VA Sources V and I Meters V and I KVL and KCL Kelvin Connection KVL and KCL Kelvin Connection 4-Wire Technique Exclude

More information

TRAX Transformer and Substation Test System

TRAX Transformer and Substation Test System TRAX Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components

More information

FAULT IDENTIFICATION IN TRANSFORMER WINDING

FAULT IDENTIFICATION IN TRANSFORMER WINDING FAULT IDENTIFICATION IN TRANSFORMER WINDING S.Joshibha Ponmalar 1, S.Kavitha 2 1, 2 Department of Electrical and Electronics Engineering, Saveetha Engineering College, (Anna University), Chennai Abstract

More information

IMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES

IMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES IMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES Thomas Steiner HIGHVOLT Prüftechnik Dresden GmbH Lifecycle of utilities time schedule utilities Tests during life cycle of utilities

More information

Partial Discharge Theory, Modeling and Applications To Electrical Machines

Partial Discharge Theory, Modeling and Applications To Electrical Machines Partial Discharge Theory, Modeling and Applications To Electrical Machines V. Vahidinasab, A. Mosallanejad, A. Gholami Department of Electrical Engineering Iran University of Science and Technology (IUST)

More information

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of

More information

SYSTEMS AND COMPONENTS FOR TRANSFORMER TESTING

SYSTEMS AND COMPONENTS FOR TRANSFORMER TESTING SYSTEMS AND COMPONENTS FOR TRANSFORMER TESTING 9.11/2 Transformer Testing n Type tests n Routine tests n Special tests n Applicable for tests on power and distribution transformers in factory and on-site

More information

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings J Electr Eng Technol Vol. 9, No. 1: 280-285, 2014 http://dx.doi.org/10.5370/jeet.2014.9.1.280 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Characteristics of Insulation Diagnosis and Failure in Gas Turbine

More information

EFFECETIVE TRANSFORMER CONDITION ASSESSMENT

EFFECETIVE TRANSFORMER CONDITION ASSESSMENT EFFECETIVE TRANSFORMER CONDITION ASSESSMENT Luwendran Moodley, Doble Engineering Africa Abstract. This paper details a novel approach to transformer condition assessment. This method has proven itself

More information

(

( (www.xatianhong.com) Introduction to XATH Xi'an Tianhong Electric Co., Ltd. (XATH) is a solely state-owned enterprise, set up by China Shipbuilding Industry Corporation (CSIC). It is one of the largest

More information

ON-SITE TESTING OF SPECIAL TRANSFORMERS

ON-SITE TESTING OF SPECIAL TRANSFORMERS ON-SITE TESTING OF SPECIAL TRANSFORMERS Simanand GANDHI JEYARAJ, Megger Ltd, UK, Simanand.gandhi@megger.com, Robert MILNE, UK Power Networks, UK, robert.milne83@googlemail.com Grant MITCHELL, Transmag

More information

DELTA Reference Manual Applications Guide. 12 kv Insulation Diagnostic System ZM-AH02E

DELTA Reference Manual Applications Guide. 12 kv Insulation Diagnostic System ZM-AH02E DELTA 4000 12 kv Insulation Diagnostic System Reference Manual Applications Guide WWW.MEGGER.COM ZM-AH02E DELTA 4000 12 kv Insulation Diagnostic System Reference Manual Applications Guide NOTICE OF COPYRIGHT

More information

MEDIUM & HIGH VOLTAGE

MEDIUM & HIGH VOLTAGE MEDIUM & HIGH VOLTAGE TESTING EQUIPMENT VOLTAGE WITHSTAND SGM Series Resonant Systems The SGM series are used for generating high AC voltages at a fixed frequency (mainly 50 or 60 Hz) by means of an excited

More information

Return to Session BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION ABSTRACT KEYWORDS INTRODUCTION

Return to Session BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION ABSTRACT KEYWORDS INTRODUCTION BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION Erling ILDSTAD, NTNU, (Norway), Erling.Ildstad@elkraft.ntnu.no Mildrid SELSJORD, SINTEF Energy Research, (Norway), Mildrid.Selsjord@sintef.no

More information

Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers

Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers in cooperation with Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers BZ-MS/1 pazifik power Complete Transformer Monitoring System (TMS) ZVCM-1001 Bushing Monitoring

More information

Autotransformer Condition Monitoring Systems

Autotransformer Condition Monitoring Systems Autotransformer Condition Monitoring Systems The Bidders shall offer separately the following systems of par.1 Integrated Condition Monitoring System and par.2 UHF PD Monitoring System. Two systems following

More information

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Charles Sweetser, Services Manager, PRIM Engineering, Waltham, Mass. Topics of Discussion

More information

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch. Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training

More information