Overview of voltage sag mitigation techniques

Size: px
Start display at page:

Download "Overview of voltage sag mitigation techniques"

Transcription

1 Overview of voltage sag mitigation techniques Ambra Sannino Department of Electrical Engineering University of Palermo, Italy Michelle Ghans Miller, Math H.J.Bollen Department of Electric Power Engineering Chalmers University of Technology Gothenburg, Sweden

2 2 outline need for voltage sag mitigation mitigation through system improvement increasing equipment immunity installation of additional equipment conclusions

3 today s scenario the need for power quality improvement 3 Factory sensitive equipment production lines Automated factories use sensitive equipment power electronics (AC and DC drives) process-control electronics (computers, PLCs) Faults in the power system can cause process interruptions with associated costs due to loss of production, damaged product and equipment, and other factors

4 different faults cause different sags 4 100% 80% Voltage 50% fuses remote MV networks transmission network local MV network motor starting 0% 0.1 s 1 s Duration interruptions

5 from system faults to process interruptions 5 Faults in the utility power system: three-phase single-phase-to-ground phase-to-phase Consequences at the PCC: voltage sags interruptions Consequences on the process: equipment trip process interruption

6 improving power quality for sensitive customers 6 system improvement mitigation equipment improvement of equipment immunity

7 mitigation through system improvement 7 critical factors: improvements: frequency of events reducing the number of faults sag duration reducing the duration of faults sag magnitude changing power system layout

8 equipment sensitivity (1) 8 ~ SINGLE-PHASE DIODE RECTIFIER DC-DC CONVERTER POWER SYSTEM ~ DIODE RECTIFIER ~ INVERTER AC MOTOR low-power electronics AC drive POWER SYSTEM ~ CONTROLLED RECTIFIER ~ FIELD WINDING + - DC MOTOR ARMATURE WINDING SINGLE-PHASE DIODE RECTIFIER DC drive

9 equipment sensitivity (2) 9 sag 70% magnitude, 100 ms duration voltage [V] time [s] effect of a sag on a single-phase rectifier

10 equipment sensitivity (3) sag 70% magnitude, 100 ms duration on phase C 200 voltage [V] time [s] effect of an unbalanced sag on a three-phase rectifier

11 improving equipment immunity 11 low-power electronics: adding capacitance, improving the dc/dc converter AC drives : adding capacitance, reducing the setting for the dc bus protection DC drives: implementing proper control algorithms for adjusting the firing angle of the devices according to changes in the input voltage. Adding capacitance is not a viable option

12 mitigation devices 12 motor-generator set ferroresonance transformer electronic tap changer uninterruptible power supply static transfer switch series-connected voltage source converter shunt-connected back-up source

13 different sags require different solutions % 80% Voltage 50% fuses transmission network remote MV networks equipment improvement local MV network motor starting 0% system improvement 0.1 s 1 s Duration interruptions

14 14 conclusions mitigation of voltage sags requires careful inspection of the characteristics of the process and of the nature and origin of sag events the installation of mitigation devices (normally the only choice for the customer) can be seen as a short-term solution. The mitigation capability of these devices is mainly limited by the energy storage capacity only improvement of system performance (for long, deep sags) and of equipment tolerance (for short, shallow sags) can solve the problem in the long term

Calculation of financial losses of Rice Industries against voltage sag

Calculation of financial losses of Rice Industries against voltage sag Calculation of financial losses of Rice Industries against voltage sag Er. Shankar Deep, Dr. D. K. Jain, Dr. Surender Dahiya Electrical Department, D.C.R.U.S.T, Murthal, Haryana, India Abstract: This paper

More information

Enhancing of Power Quality Using a SPWM Voltage Source Converter

Enhancing of Power Quality Using a SPWM Voltage Source Converter Enhancing of Power Quality Using a SPWM Voltage Source Converter P.Ramesh M.Tech (Student) Department of EEE (Power Systems) VITAM College, Mindivani Palem Village, Anandapuram Mandal, Visakhapatnam, Andhra

More information

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners IEEE Canada Webinar Presentation May 21, 2008 Bob Hanna, FIEEE, P.Eng. RPM Engineering Ltd. www.rpm-eng.com David

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS 66 CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS INTRODUCTION The use of electronic controllers in the electric power supply system has become very common. These electronic

More information

Automatic Transfer Switch (ATS) Using Programmable Logic Controller (PLC)

Automatic Transfer Switch (ATS) Using Programmable Logic Controller (PLC) Automatic Transfer Switch (ATS) Using Programmable Logic Controller (PLC) Dr. Hamdy Ashour Arab Academy for Science &Technology Department of Electrical & Computer Control Engineering P.O. 1029 Miami,

More information

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review S.N. Bhalerao 1, P.J. Bhakre, C.O.Reddy 3 1 Student, Department of Electrical Engineering, MSS Collage Of Engineering,

More information

Protection from Voltage Sags and Swells by Using FACTS Controller

Protection from Voltage Sags and Swells by Using FACTS Controller Protection from Voltage Sags and Swells by Using FACTS Controller M.R.Mohanraj 1, V.P.Suresh 2, G.Syed Zabiyullah 3 Assistant Professor, Department of Electrical and Electronics Engineering, Excel College

More information

Emicon Engineering Consultants L.L.C.

Emicon Engineering Consultants L.L.C. Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com

More information

ECE 528 Understanding Power Quality

ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 7 1 Today Sags and short interruptions Some Homework 2 pointers

More information

APPLICATION OF INVERTER BASED SHUNT DEVICE FOR VOLTAGE SAG MITIGATION DUE TO STARTING OF AN INDUCTION MOTOR LOAD

APPLICATION OF INVERTER BASED SHUNT DEVICE FOR VOLTAGE SAG MITIGATION DUE TO STARTING OF AN INDUCTION MOTOR LOAD APPLICATION OF INVERTER BASED SHUNT DEVICE FOR VOLTAGE SAG MITIGATION DUE TO STARTING OF AN INDUCTION MOTOR LOAD A. F. Huweg, S. M. Bashi MIEEE, N. Mariun SMIEEE Universiti Putra Malaysia - Malaysia norman@eng.upm.edu.my

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Electric Power Quality: Voltage Sags Momentary Interruptions

Electric Power Quality: Voltage Sags Momentary Interruptions Slide 1 Electric Power Quality: Voltage Sags Momentary Interruptions Ward Jewell Wichita State University ward.jewell@wichita.edu Slide 2 Power Quality Events Voltage sags Outages/interruptions Voltage

More information

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Design Strategy for Optimum Rating Selection of Interline D-STATCOM International Journal of Engineering Science Invention ISSN (Online): 2319 6734, ISSN (Print): 2319 6726 Volume 2 Issue 3 ǁ March. 2013 ǁ PP.12-17 Design Strategy for Optimum Rating Selection of Interline

More information

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Research Journal of Engineering Sciences ISSN 2278 9472 Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Abstract Srishti Verma * and Anupama Huddar Electrical Engineering

More information

Series Compensation Technique for Voltage Sag Mitigation

Series Compensation Technique for Voltage Sag Mitigation IOSR Journal of Engineering (IOSRJEN) ISSN: 2250-3021 Volume 2, Issue 8 (August 2012), PP 14-24 Series Compensation Technique for Voltage Sag Mitigation 1 NAGENDRABABU VASA, 2 SREEKANTH G, 3 NARENDER REDDY

More information

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India Abstract: The objective of this research is to develop a novel voltage control scheme that

More information

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 86 CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 5.1 INTRODUCTION Distribution systems face severe power quality problems like current unbalance, current harmonics, and voltage unbalance,

More information

Power Quality Improvement using Hysteresis Voltage Control of DVR

Power Quality Improvement using Hysteresis Voltage Control of DVR Power Quality Improvement using Hysteresis Voltage Control of DVR J Sivasankari 1, U.Shyamala 2, M.Vigneshwaran 3 P.G Scholar, Dept of EEE, M.Kumarasamy college of Engineering, Karur, Tamilnadu, India

More information

POWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM

POWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM POWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM A.Karthikeyan Dr.V.Kamaraj Sri Venkateswara College of Engineering Sriperumbudur, India-602105. Abstract: In this paper HVDC is investigated

More information

FLYWHEEL BASED ENERGY STORAGE SYSTEM FOR VOLTAGE SAG CORRECTION AND DETECTION

FLYWHEEL BASED ENERGY STORAGE SYSTEM FOR VOLTAGE SAG CORRECTION AND DETECTION FLYWHEEL BASED ENERGY STORAGE SYSTEM FOR VOLTAGE SAG CORRECTION AND DETECTION Anuradha 1, Dushyant Narang 2, Karan Khanayat 3 and Kunal Agarwal 4 1-4 Department of Electrical Engineering, College of Engineering

More information

VOLTAGE SAG COMPENSATION USING UNIFIED POWER FLOWER CONTROLLER IN MV POWER SYSTEM USING FUZZY CONTROLLER

VOLTAGE SAG COMPENSATION USING UNIFIED POWER FLOWER CONTROLLER IN MV POWER SYSTEM USING FUZZY CONTROLLER VOLTAGE SAG COMPENSATION USING UNIFIED POWER FLOWER CONTROLLER IN MV POWER SYSTEM USING FUZZY CONTROLLER Alefy B. 1, * Hosseini Firouz M. 1, and Memarinezhad H. 2 1 Department of Electrical Engineering,

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality

Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality Deeksha Bansal 1 Sanjeev Kumar Ojha 2 Abstract This paper shows the modelling and simulation procedure for power quality improvement

More information

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator Priyanka Sahu Columbia Institute of Engineering and Technology, Raipur,

More information

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation Prof. S. S. Khalse Faculty, Electrical Engineering Department, Csmss Chh Shahu College of Engineering, Aurangabad,

More information

Power Quality - 4. Flicker case study. Content. Course. Ljubljana, Slovenia 2013/14. Prof. dr. Igor Papič

Power Quality - 4. Flicker case study. Content. Course. Ljubljana, Slovenia 2013/14. Prof. dr. Igor Papič Course ower Quality - 4 Ljubljana, Slovenia 2013/14 rof. dr. Igor apič igor.papic@fe.uni-lj.si Flicker case udy Content Session 1 Session 2 Session 3 Session 4 1 day 2nd day 3rd day 4th day 5th day Flicker

More information

Industrial Electrician Level 3

Industrial Electrician Level 3 Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide

More information

T-68 Protecting Your Equipment through Power Quality Solutions

T-68 Protecting Your Equipment through Power Quality Solutions T-68 Protecting Your Equipment through Power Quality Solutions Dr. Bill Brumsickle Vice President, Engineering Nov. 7-8, 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. 2 Agenda What

More information

Modern Arrangement to Reduction of Voltage Perturbations

Modern Arrangement to Reduction of Voltage Perturbations Doctoral school of energy- and geo-technology January 15 20, 2007. Kuressaare, Estonia Modern Arrangement to Reduction of Voltage Perturbations R. Strzelecki Gdynia Maritime University, Department of Ships

More information

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS Le Tang, Jeff Lamoree, Mark McGranaghan Members, IEEE Electrotek Concepts, Inc. Knoxville, Tennessee Abstract - Several papers have

More information

Comparative Study of Sag & Swell Mitigation by a Novel Multi Level DVR with Wavelets

Comparative Study of Sag & Swell Mitigation by a Novel Multi Level DVR with Wavelets Comparative Study of Sag & Swell Mitigation by a Novel Multi Level DVR with Wavelets G. Devadasu Department of EEE, CMR College of Engineering and Technology Dr. M. Sushama Department of EEE, JNTUH University

More information

Implementation of UPQC for Voltage Sag Mitigation

Implementation of UPQC for Voltage Sag Mitigation Implementation of UPQC for Voltage Sag Mitigation C.H. Ram Jethmalani 1, V. Karthikeyan 2, and Narayanappa 3 1 Adhiyamaan College of Engineering, Hosur, India Email: malanisuryakumaran@gmail.com 2,3 Adhiyamaan

More information

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN Summary Capacitor Commutated Converters (CCC) were introduced to the HVDC market

More information

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N. COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.Booma 2 Electrical and Electronics engineering, M.E., Power and

More information

Available online at ScienceDirect. AASRI Procedia 7 (2014 ) Power and

Available online at  ScienceDirect. AASRI Procedia 7 (2014 ) Power and Available online at www.sciencedirect.com ScienceDirect AASRI Procedia 7 (2014 ) 107 113 2013 2nd AASRI Conference on Power and Energy Systems Design and Development of a Mini Custom Power Park Manitha

More information

OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT

OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT Shyam V. Alaspure 1, Snehal G. Vinchurkar 2, Swapnil D. Raut 1 Electronics & Telecommunication 2 Electronics & Power 3 Computer 1 Lecturer, G.H. Raisoni Polytechnic

More information

ECE 528 Understanding Power Quality. Paul Ortmann (voice) Lecture 6

ECE 528 Understanding Power Quality.   Paul Ortmann (voice) Lecture 6 ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 6 1 Today more on voltage sags Motor starting mitigation Impacts

More information

Inverter with static switch a. manual bypass up to 1000 VA

Inverter with static switch a. manual bypass up to 1000 VA Series PCI and PIT Type [VDC] Power PCI1628 U IN 20 32 500 VA PIT1638 / PIT3638 U IN 40 64 400 VA / 500 VA PIT1648 / PIT3648 U IN 50 80 400 VA / 500 VA PIT1658 U IN 80 160 PIT1678 U IN 160-320 Type of

More information

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM 64 CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM 4.1 INTRODUCTION Power electronic devices contribute an important part of harmonics in all kind of applications, such as power rectifiers, thyristor converters

More information

Power Quality Improvement of Grid Connected Wind Energy System by Statcom for Balanced and Unbalanced Linear and Nonlinear Loads

Power Quality Improvement of Grid Connected Wind Energy System by Statcom for Balanced and Unbalanced Linear and Nonlinear Loads International Journal of Engineering Research and Development e-issn: 2278-67X, p-issn: 2278-8X, www.ijerd.com Volume 3, Issue 1 (August 212), PP. 9-17 Power Quality Improvement of Grid Connected Wind

More information

3 Circuit Theory. 3.2 Balanced Gain Stage (BGS) Input to the amplifier is balanced. The shield is isolated

3 Circuit Theory. 3.2 Balanced Gain Stage (BGS) Input to the amplifier is balanced. The shield is isolated Rev. D CE Series Power Amplifier Service Manual 3 Circuit Theory 3.0 Overview This section of the manual explains the general operation of the CE power amplifier. Topics covered include Front End Operation,

More information

Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System

Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System Faculty of Electrical Engineering Universiti Teknologi Malaysia OL. 8, NO., 006, 3 37 ELEKTRIKA oltage Sag and Mitigation Using Dynamic oltage Restorer (DR) System Shairul Wizmar Wahab and Alias Mohd Yusof

More information

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013 A Statcom-Control Scheme for Power Quality Improvement of Grid Connected Wind Energy System B.T.RAMAKRISHNARAO*, B.ESWARARAO**, L.NARENDRA**, K.PRAVALLIKA** * Associate.Professor, Dept.of EEE, Lendi Inst.Of

More information

Smart Power Relay E I...

Smart Power Relay E I... Smart Power Relay E-48-8I... Description The Smart Power Relay E-48-8I.- is a remotely controllable electronic load disconnecting relay with three functions in a single unit: l electronic relay l electronic

More information

IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR)

IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR) IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR) Hadi Suyono 1, Lauhil Mahfudz Hayusman 2 and Moch. Dhofir 1 1 Department of Electrical Engineering, Brawijaya University, Malang,

More information

Auxiliary DC Voltage

Auxiliary DC Voltage THE 9 th INTERNATIONAL SYMPOSIUM ON ADVANCED TOPICS IN ELECTRICAL ENGINEERING May 7-9, 2015 Bucharest, Romania DVR with Auxiliary DC Voltage Source Provided by A High Power Diode Based Rectifier Used in

More information

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics

More information

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America,

More information

Photovoltaic DC Arc Fault Detector Testing at Sandia National Laboratories

Photovoltaic DC Arc Fault Detector Testing at Sandia National Laboratories Photovoltaic DC Arc Fault Detector Testing at Sandia National Laboratories Jay Johnson 1, Birger Pahl 2, Charles Luebke 2, Tom Pier 2, Theodore Miller 3, Jason Strauch 1, Scott Kuszmaul 1, and Ward Bower

More information

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY Department of Electrical Engineering Senior Design Project ELEC 499 DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY Student Names: Chresteen Baraket Marina Messiha Supervised

More information

A REVIEW PAPER ON REGULATION TECHNIQUE FOR VOLTAGE SAG AND SWELL USING DVR

A REVIEW PAPER ON REGULATION TECHNIQUE FOR VOLTAGE SAG AND SWELL USING DVR A REVIEW PAPER ON REGULATION TECHNIQUE FOR VOLTAGE SAG AND SWELL USING DVR 1 Ms.Santoshi Gupta, 2 Prof.Paramjeet Kaur 1 M.Tech Scholar, 2 Associate Professor Department of Electrical and Electronics Engineering

More information

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Mitigating Voltage Sag Using Dynamic Voltage Restorer Mitigating Voltage Sag Using Dynamic Voltage Restorer Sumit A. Borakhade 1, R.S. Pote 2 1 (M.E Scholar Electrical Engineering, S.S.G.M.C.E. / S.G.B.A.U. Amravati, India) 2 (Associate Professor, Electrical

More information

EH2741 Communication and Control in Electric Power Systems Lecture 2

EH2741 Communication and Control in Electric Power Systems Lecture 2 KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment

More information

StarSine Power Quality Products

StarSine Power Quality Products StarSine Power Quality Products Medium Voltage Static Voltage Regulator ( MV SVR ) MV SVR PROTECTS THE WHOLE FACILITY LOADS FROM VOLTAGE SAGS CAUSED BY UTILITY GRID FAULTS Voltage sags, whether due to

More information

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating P.Ankineedu Prasad 1, N.Venkateswarlu 2. V.Ramesh 3, L.V.Narasimharao 4 Assistant Professor 12 & Professor 4& Research Scholar

More information

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE - 519 Solutions Harmonics Tutorial 1 Power Conversion Equipment can save energy and control motors, heaters,

More information

OVERVIEW OF IEEE STD GUIDE FOR VOLTAGE SAG INDICES

OVERVIEW OF IEEE STD GUIDE FOR VOLTAGE SAG INDICES OVERVIEW OF IEEE STD 1564-2014 GUIDE FOR VOLTAGE SAG INDICES ABSTRACT Daniel SABIN Electrotek Concepts USA d.sabin@ieee.org IEEE Std 1564-2014 Guide for Voltage Sag Indices is a new standard that identifies

More information

Power Quality and Digital Protection Relays

Power Quality and Digital Protection Relays Power Quality and Digital Protection Relays I. Zamora 1, A.J. Mazón 2, V. Valverde, E. Torres, A. Dyśko (*) Department of Electrical Engineering - University of the Basque Country Alda. Urquijo s/n, 48013

More information

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Mr. A. S. Patil Mr. S. K. Patil Department of Electrical Engg. Department of Electrical Engg. I. C. R. E. Gargoti I. C. R. E. Gargoti

More information

IMPORTANCE OF VSC IN HVDC

IMPORTANCE OF VSC IN HVDC IMPORTANCE OF VSC IN HVDC Snigdha Sharma (Electrical Department, SIT, Meerut) ABSTRACT The demand of electrical energy has been increasing day by day. To meet these high demands, reliable and stable transmission

More information

Overview of Actuation Thrust

Overview of Actuation Thrust Overview of Actuation Thrust Fred Wang Thrust Leader, UTK Professor Prepared for CURENT Course September 4, 2013 Actuation in CURENT Wide Area Control of Power Power Grid Grid Measurement &Monitoring HVDC

More information

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Riya Philip 1, Reshmi V 2 Department of Electrical and Electronics, Amal Jyothi College of Engineering, Koovapally, India 1,

More information

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203 Unit.2-Voltage Sag D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203 13/09/2012 Unit.2 Voltage sag 1 Unit-2 -Voltage Sag Mitigation Using

More information

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS SIMUATION OF D-STATCOM AND DVR IN POWER SYSTEMS S.V Ravi Kumar 1 and S. Siva Nagaraju 1 1 J.N.T.U. College of Engineering, KAKINADA, A.P, India E-mail: ravijntu@gmail.com ABSTRACT A Power quality problem

More information

U I. HVDC Control. LCC Reactive power characteristics

U I. HVDC Control. LCC Reactive power characteristics Lecture 29 HVDC Control Series Compensation 1 Fall 2017 LCC Reactive power characteristics LCC HVDC Reactive compensation by switched filters and shunt capacitor banks Operates at lagging power factor

More information

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM International Journal of Electrical Engineering. ISSN 0974-2158 Volume 5, Number 7 (2012), pp. 889-902 International Research Publication House http://www.irphouse.com Voltage Sags in Distribution Systems

More information

ITEE Journal. Information Technology & Electrical Engineering International Journal of Information Technology and Electrical Engineering

ITEE Journal. Information Technology & Electrical Engineering International Journal of Information Technology and Electrical Engineering Total Harmonic Distortion (THD) Analysis of Neural Network Controller Based Dynamic Voltage Restorer for Voltage Sag Mitigation Yogesh Popat Taurian World School, Ranchi, India Email: yogeshpopat28@gmail.com,

More information

2-1 DC DRIVE OVERVIEW EXERCISE OBJECTIVE. Familiarize yourself with the DC Drive. Set the DC Drive parameters to control the DC Motor.

2-1 DC DRIVE OVERVIEW EXERCISE OBJECTIVE. Familiarize yourself with the DC Drive. Set the DC Drive parameters to control the DC Motor. 2-1 DC DRIVE OVERVIEW EXERCISE OBJECTIVE Familiarize yourself with the DC Drive. Set the DC Drive parameters to control the DC Motor. DISCUSSION The DC Drive of your training system is shown in Figure

More information

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL Saravanan.R 1, Hariharan.M 2 1 PG Scholar, Department OF ECE, 2 PG Scholar, Department of ECE 1, 2 Sri Krishna College

More information

QUANTIFYING VOLTAGE VARIATIONS ON A TIME SCALE BETWEEN 3 SECONDS AND 10 MINUTES

QUANTIFYING VOLTAGE VARIATIONS ON A TIME SCALE BETWEEN 3 SECONDS AND 10 MINUTES C I R E D 8 th International Conference on Electricity Distribution Turin, 6-9 June QUANTIFYING VOLTAGE VARIATIONS ON A TIME SCALE BETWEEN SECONDS AND MINUTES Math H.J. Bollen Mats Häger Christine Schwaegerl

More information

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic

More information

Endeavour Energy Power Quality & Reliability Centre Voltage Sag Mitigation

Endeavour Energy Power Quality & Reliability Centre Voltage Sag Mitigation e n d e a v o u r e n e r g y power quality & reliability centre Endeavour Energy Power Quality & Reliability Centre Voltage Sag Mitigation Technical Note 11 August 2012 Table of Contents 1. Executive

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

Series PCI + PIT PIT5738 U IN PIT5748 U IN PCI5748 PCI5738. Series PIT 19 - Cabinet G10

Series PCI + PIT PIT5738 U IN PIT5748 U IN PCI5748 PCI5738. Series PIT 19 - Cabinet G10 PCI + PIT PCI5728 U IN 20 32 PIT5738 U IN 40 64 PIT5748 U IN 50 80 PIT5658 U IN 80 160 PIT5678 3000VA 3000VA 3000VA 3000VA 3000VA Serie PCI5728 U IN 20 32 PCI5738 U IN 40 64 PCI5748 U IN 50 80 PCI5758

More information

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing. 1.0 Scope This document describes the specification for Toshiba 1000 Series On-Line Uninterruptible Power System (UPS). The UPS will supply a computer grade AC output sine wave which is unaffected by the

More information

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Modeling and Simulation of SRF and P-Q based Control DSTATCOM International Journal of Engineering Research and Development ISSN: 2278-067X, Volume 1, Issue 10 (June 2012), PP.65-71 www.ijerd.com Modeling and Simulation of SRF and P-Q based Control DSTATCOM Kasimvali.

More information

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids

More information

A Voltage Controlled Dstatcom for Power Quality Improvement

A Voltage Controlled Dstatcom for Power Quality Improvement IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 6 Ver. I (Nov Dec. 2015), PP 27-34 www.iosrjournals.org A Voltage Controlled Dstatcom

More information

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION International Journal of Electrical, Electronics and Data Communication, ISSN: 23284 Volume, Issue-4, April14 INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION 1 V.S.VENKATESAN, 2 P.CHANDHRA

More information

Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter

Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter Mahesh Ahuja 1, B.Anjanee Kumar 2 Student (M.E), Power Electronics, RITEE, Raipur, India 1 Assistant

More information

Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System

Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System Rosli Omar, 1 N.A Rahim 2 1 aculty of Electrical Engineering, Universiti Teknikal Malaysia

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 09 (September. 2014), V3 PP 11-20 www.iosrjen.org A Versatile Control Scheme for UPQC for Power Quality Improvement

More information

ISSN: ; e-issn

ISSN: ; e-issn 834 VOLTAGE SAG AND SWELL MITIGATION USING CUSTOM POWER DEVICE JYOTHILAL NAYAK BHAROTHU 1 Asst.professor & Head, Department of Electrical & Electronics Engineering, Columbia Institute of Engineering &

More information

EE 741 Spring Electric Power Distribution Systems An Overview

EE 741 Spring Electric Power Distribution Systems An Overview EE 741 Spring 2017 Electric Power Distribution Systems An Overview Basic Power System Layout There are over 100 substations in the Las Vegas Valley pic of closest substation Substation Design Substation

More information

MONITORING OF DISTRIBUTION TRANSFORMER PARAMETERS USING PLC

MONITORING OF DISTRIBUTION TRANSFORMER PARAMETERS USING PLC MONITORING OF DISTRIBUTION TRANSFORMER PARAMETERS USING PLC Shubhangi Landge¹, Snehal Waydande², Sanjay Sangale³, Somesh Gaikwad⁴ ¹Assistant Professor, Dept. Of Electrical Engineering, AISSMS IOIT College,

More information

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS Saheb Hussain MD 1, K.Satyanarayana 2, B.K.V.Prasad 3 1 Assistant Professor, EEE Department, VIIT, A.P, India, saheb228@vignanvizag.com 2 Ph.D Scholar,

More information

Grid-Voltage Regulation Controller: IUPQC

Grid-Voltage Regulation Controller: IUPQC Grid-Voltage Regulation Controller: IUPQC G Vasu Kumar M.Tech Second Year, Electrical Power Systems, Department of EEE, MJR Collage of Engineering and Technologies. ABSTRACT: This paper presents an improved

More information

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 04 September 2016 ISSN (online): 2349-6010 A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link

More information

VOLTAGE SAG MITIGATION USING A NEW DIRECT CONTROL IN D-STATCOM FOR DISTRIBUTION SYSTEMS

VOLTAGE SAG MITIGATION USING A NEW DIRECT CONTROL IN D-STATCOM FOR DISTRIBUTION SYSTEMS U.P.B. Sci. Bull., Series C, Vol. 7, Iss. 4, 2009 ISSN 454-234x VOLTAGE SAG MITIGATION USING A NEW DIRECT CONTROL IN D-STATCOM FOR DISTRIBUTION SYSTEMS Rahmat-Allah HOOSHMAND, Mahdi BANEJAD 2, Mostafa

More information

Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer

Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer Lightweight 9,5 kg Test current 5 ma 40 A DC Measuring range 0,1-2 k Two voltage sense channels Extremely quick measurement Rapid automatic

More information

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR Rongali. Shiva Kumar P.G Student Scholar, Department of Electrical & Electronics Engineering, Gokul Group Of Institutions Abstract:

More information

LV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING

LV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING Training Title LV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING Training Duration 5 days Training Venue and Dates LV/MV/HV Circuit Breakers (Switchgear):

More information

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side 1 Jaykant Vishwakarma, 2 Dr. Arvind Kumar Sharma 1 PG Student, High voltage and Power system, Jabalpur

More information

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Harmonics Reduction using 4-Leg Shunt Active Power Filters Harmonics Reduction using 4-Leg Shunt Active Power Filters K Srinivas Assistant Professor & Department of EEE & JNTUH CEJ Telangana, India. Abstract Harmonics in power system are caused by highly non-linear

More information

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling 2, rue d Artois, F-758 PARIS B4-7 CIGRE 28 http : //www.cigre.org A cost effective hybrid HVDC transmission system with high performance in DC line fault handling Mats Andersson, Xiaobo ang and ing-jiang

More information

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) ABHIYANTRIKI Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) An International Journal of Engineering & Technology (A Peer Reviewed & Indexed Journal) Vol.

More information

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information