Sizing of and Ground Potential Rise Calculations for Grounding Transformers for Photovoltaic Plants

Size: px
Start display at page:

Download "Sizing of and Ground Potential Rise Calculations for Grounding Transformers for Photovoltaic Plants"

Transcription

1 1 Sizing of and Ground Potential Rise Calculations for Grounding Transformers for Photovoltaic Plants M. Ropp, Member, IEEE, D. Schutz, Member, IEEE, C. Mouw, Member, IEEE Abstract Due to concerns about ground fault overvoltage, increasing numbers of North American utilities are requiring that PV plants be effectively grounded before an interconnect permit can be issued. This generally equates to a requirement that a grounding transformer be installed, because most PV inverters are not inherently grounded. This requirement creates two challenges. First: there is uncertainty amongst PV plant designers as to how to correctly specify these grounding transformers in terms of impedance and current-handling capability. The grounding transformer impedance must balance the concerns of maintaining effective grounding while not desensitizing utility protection. The ratio-ofimpedances method described in IEEE 142 cannot be applied to inverter-based sources because the inverter impedances are not well defined. A new recommendation for the grounding transformer impedance is being proposed in IEEE , but many developers and field engineers are either unaware of it, or are not clear on how to use it, and in any case this recommendation does not address how to find the short-duration and steady-state current ratings. Second: ground potential rise calculations are also needed often in this situation, but for PV grounding transformers there is uncertainty regarding proper quantification of the current that leads to the ground potential rise. The existence of this problem is acknowledged in IEEE 367 Clause 4.4, but in the case of PV grounding transformers, there is no clear guidance on how to solve it. This is especially true in the case in which the PV distribution or GSU transformer H and X neutrals, along with the grounding transformer neutral, all share the same grounding electrodes, which is the most common configuration in the field. This paper provides background on these problems, and presents: a) a simple, fundamentally-based procedure for sizing PV grounding transformers that utilizes the IEEE recommendation and yields defensible but not Manuscript received September 11, This work was supported by Advanced Energy Industries and Gerlicher Solar. M. Ropp, D. Schutz and C. Mouw are with Northern Plains Power Technologies, Brookings, SD USA (phone: ; michael.ropp@northernplainspower.com). excessively overdesigned results; and b) quantitative recommendations for calculating the correct current to be used in IEEE 367 ground potential rise calculations, again based on fundamental considerations. The procedures presented are demonstrated via examples, and vetted by testing against simulation results from a detailed 4-wire feeder model. Index Terms Ground fault overvoltage, effective grounding, photovoltaics, inverter, distributed generation, grounding transformer. DG GFO GPR GSU M I. NOMENCLATURE Distributed Generation Ground Fault Overvoltage Ground Potential Rise Generator Step-Up (transformer) II. INTRODUCTION ANY US utilities are starting to require that PV power plants be effectively grounded so that these plants will not cause a ground fault overvoltage (GFO) on a threephase four-wire feeder after the utility breaker opens. GFO is a phenomenon that can occur if an ungrounded voltage source feeds an ungrounded feeder containing a single-phase to ground fault, resulting in a phase-to-ground overvoltage on the unfaulted phases. The GFO phenomenon is well-known in rotating generators [1], but there is an ongoing debate about how to think of this phenomenon with inverter-based distributed generation that acts as a current source [2]. Until that debate is resolved, utilities are understandably erring on the side of caution, meaning that increasing numbers of interconnect permits for inverter-based distributed generation (DG) will run into utility policy requiring effective grounding. There is thus a need for a grounding transformer design procedure that is simple and minimally situationally-specific, and that requires a minimum of input data from the utility, but that still results in a grounding transformer specification that is rigorously defensible. This paper proposes such a procedure. Inclusion of a grounding transformer also gives rise to the possibility of ground potential rise (GPR) becoming an issue at the DG site. This paper also suggests a method for determining the fault current for use in GPR calculations.

2 2 A. Procedure III. GROUNDING TRANSFORMER SIZING 1) Fundamental considerations Consider the generic distribution feeder shown schematically in Figure 1. The utility source is at the left, and it serves the feeder through a substation transformer that grounds the feeder, marked here as a delta-yg. For simplicity, no loads are shown. At the right end of the distribution feeder is an inverter-based DG (a PV plant in this case), assumed here to be tied to the feeder through a Yg-Yg distribution transformer. The PV plant has a grounding transformer, shown here as a Yg-delta but which could also be a zigzag. However, for consistency with standard practice, that factor is not considered here, and its exclusion will lead to a conservative design recommendation for the grounding transformer. There are several ways of obtaining the needed zerosequence path. One way is to connect the DG to the feeder using a Yg-delta distribution transformer, with the Yg on the feeder side and probably grounded through a grounding reactor to control the fault current contribution. When viewed from the Yg (feeder) side, this transformer provides a zerosequence path to ground through its delta winding [3] and prevents GFO for faults on the distribution feeder. In this configuration, a ground fault on the 480 V bus will result in a GFO driven by the utility source. Thus, in this case it might still be necessary to include a grounding transformer on the distribution transformer LV bus. Figure 1. One-line diagram of a generic 15 kv class feeder circuit, with a PV plant and a Yg-delta grounding transformer. The situation of concern to utilities occurs when a single phase fault to ground occurs. To understand this situation, consider Figure 2, which shows the sequence networks for Phase A of the feeder in Figure 1 under a single-phase fault on the PV plant 480 V bus, before opening of the substation breaker. The top loop is the positive sequence network, the middle loop is the negative sequence, and the bottom loop is the zero sequence. The variables used in Figure 2 are listed in Table 1. Derivation of the sequence networks and interconnecting them to represent the single-phase fault is explained in [3-5]. When unfaulted, the sequence networks are decoupled, and since there are no sources in the negative or zero sequence networks there are no currents in those loops. When the single-phase fault occurs, the sequence networks become coupled at the fault point through the fault impedance Z F. Figure 2 shows that the inverter s zero-sequence shunt impedance is infinite. This is true for most (but not all) DG inverters. While the utility is still connected, the substation transformer provides a path for zero-sequence currents, through the substation grounding impedance Z 0,gnd,sub. However, when the utility s overcurrent protection detects the fault and opens, the feeder is cut off from the substation transformer and Z 0,gnd,sub. If the grounding transformer impedance Z 0,g were not present in Figure 2, the DG would not provide a path for the zero-sequence current, which would then have to flow through the zero-sequence impedance of the phase-ground connected load, the charging capacitances of the feeder conductors, and any other phase-ground connected impedances, such as arrestors. These phase-ground connected loads and elements are not included in the sequence network diagram. This is standard practice, but this exclusion can cause an interpretation problem when dealing with inverterbased DGs acting as current sources, because after opening of the utility breaker it is these elements that provide the path for the DG currents. The phase voltages and any resulting GFO will then be determined by the DG phase currents and the current-voltage relationship of the Yg-connected load. Figure 2. The sequence networks of the generic feeder in Figure 1, including a single-phase fault on the PV plant 480 V bus. Table 1. Variable names used in Figure 2. I PVa1 Positive-sequence PV output current V a1 Positive-sequence utility source voltage Z 1,source; Z 2,source; Z 0,source Positive, negative and zero-sequence utility source impedances Z 1,line; Z 2,line; Z 0,line Positive, negative and zero-sequence impedances of the distribution feeder between the substation and the fault Z 1,disttx; Z 2,disttx; Z 0,disttx Positive, negative and zero-sequence impedances of the distribution transformer Z 1,inv,s; Z 2,inv,s; Z 0,inv,s Positive, negative and zero-sequence series impedances of the inverter Z 1,inv,sh; Z 2,inv,sh; Z 0,inv,sh Positive, negative, and zero-sequence shunt impedances of the inverter Z 1,g; Z 2,g; Z 0,g Positive, negative and zero-sequence impedances of the grounding transformer Z 0,gnd,sub Substation grounding impedance (if not includes in Z0,source) Fault impedance Z f If a Yg-Yg distribution transformer is used to connect the DG to the feeder, then a separate grounding transformer can be used to effectively ground the PV plant, and this configuration is the topic of the present paper. Grounding transformers are either Yg-delta or zigzag types, both of which

3 3 provide the finite zero sequence shunt impedance needed to mitigate GFO. It is assumed that the grounding transformer is connected on the LV side of the distribution transformer. The grounding transformer must have sufficient currenthandling capability to survive three sets of conditions: the fault current that flows after the fault strikes but before the utility breaker opens, the fault current that flows after the utility breaker opens but before the PV trips, and the steadystate circulating current that will flow in the grounding transformer due to phase-phase voltage imbalance under normal unfaulted operating conditions. Inverter fault current contributions are limited; during the fault, the inverter current will typically be on the order of 1.2 times the inverter s rated current [6], meaning that the PV fault current contribution will be much smaller than the utility-driven fault current that flows before disconnection. Thus, the fault current flowing after initiation of the fault but before the utility breaker opens will be the current that determines the short-term current handling capability the transformer must possess. The steady-state circulating current can also be sizeable, depending on the transformer impedance and the level of phase-phase voltage imbalance expected on the feeder. 2) Grounding transformer electrical specification To electrically specify the grounding transformer, one must specify six parameters: the transformer s nominal terminal voltage (assumed here to be 480 V LL,RMS), the zero-sequence current required and its duration (taken here to be 2 sec), the continuous circulating current the transformer must endure due to steady-state phase-phase voltage imbalance on the feeder, and the transformer s zero-sequence impedances R 0 and X 0. The strategy used here is to first find the transformer impedances, and then use those to calculate the transformer s needed fault current and continuous current withstand capabilities. There are two methods by which the transformer impedance is commonly specified. One is from IEEE-142 [7] and involves setting the grounding transformer impedances (R 0 and X 0) so that the ratios of R 0/X 1 and X 0/X 1 of the circuit without the utility connected result in a TOV of 120% or less. This process involves drawing the sequence network circuit, and the R 0, X 0 and X 1 values referred to in the ratios are those of the circuit, again with the utility disconnected. Usually, the recommended values for the ratios are X 0/X 1 3, and R 0/X 1 1. However, this definition can be difficult to use with inverters because it is difficult to properly define the inverter s positive- and negative-sequence impedances. The other means for finding the transformer impedances appears in an appendix to draft standard IEEE [8]. In this approach, one first finds the impedance base of the inverter, Z base,pv, as follows: where V PV is the line-to-neutral PV plant terminal voltage and S PV is the plant s rated output apparent power per phase in VA. Note that 1) S PV usually equals P PV because PV plants normally operate at unity power factor; and 2) if one uses the line-line voltage and total three-phase S PV, the same numerical (1) result is obtained. Then, the grounding transformer reactance and resistance, X g and R g, are found using these relationships: For example, a 500 kva (500 kw) inverter connected at 480 V has a Z base,pv of , so the required X g of the grounding transformer would be 0.276, and the grounding transformer s R g value can be anything less than or equal to 69.1 m. The value of 60% of Z base,pv corresponds to a steady-state fault current contribution of about 167% of the PV nominal current, which is a conservative value. In this document, we will assume that R g = X g/4 (i.e., the maximum allowed R g value), because this minimizes the grounding transformer size without violating the requirements for TOV prevention. In general, one should also allow for a tolerance band on these impedances, so in this paper a ±10% tolerance on the impedance values is assumed. Figure 1 shows a representation of a generic distribution feeder with a PV plant and a grounding transformer on the PV plant s 480 V bus. This is the configuration that will be considered throughout this document. This basic configuration is the same whether a zigzag or Yg-delta grounding transformer is used. B. Grounding Transformer Sizing Results 1) Calculation of the steady-state circulating current rating The steady-state circulating current in the grounding bank arises because of the zero-sequence component of the unbalanced distribution feeder phase voltages. Denote the circulating current by I g. Looking at Figure 2, the DG appears on the right of each of the sequence networks. It is usually assumed that the DG current is entirely positive sequence, so the DG current source becomes an open circuit in the negative and zero sequences. Because we are concerned with the time period between the initiation of the fault and opening of the utility breaker, we will assume that the DG inverter s shunt impedances in the sequence domain, Z 1,inv,sh and Z 2,inv,sh, are large enough at 60 Hz relative to the other impedances in the circuit that the currents through them can be neglected while the utility is still connected. Because of the open circuit at the far right of the zerosequence network, the DG s zero-sequence impedance is entirely determined by the impedance of the grounding transformer. Also, notice that the grounding transformer only appears in the zero sequence network. Because the grounding transformer is not serving load on its secondary windings (which is usually, but not always, true), there is an open circuit on the secondary side of the grounding transformer s positive and negative sequences, so only zero sequence currents can flow in the grounding transformer. Because the impedance of the grounding transformer is known from Equations (2) and (3), it is now possible to find the circulating current I g by determining the zero-sequence voltage across the grounding bank as a function of the phase- (2) (3)

4 4 phase imbalance. Using that voltage, Ohm s Law will give I g. The first step in this process is to determine an expression for the zero-sequence voltage across Z 0,g that results from a given level of phase-phase voltage imbalance. To obtain this relationship, we first write expressions for the phase voltages expressing the level of unbalance. For generality, we will allow for different levels of imbalance on each phase. We will assume the Phase A voltage V a to be the reference, so that it has a magnitude of 1 per unit and a phase of zero. Then, let the ratio of V b to V a be x and the ratio of V c to V a be y. This can be written: where a is the 120 o phase shift operator. The symmetrical components of this unbalanced set of voltages are: (4) (5) and. Substituting these relationships into Equation (9) and performing the indicated algebra, the following result is obtained: (10) Equation (10) gives the zero-sequence voltage as a function of the percent imbalance, under the assumptions described above. Now the circulating current can be found using the circuit in Figure 2 by setting the voltage across the grounding transformer impedance equal to the zero-sequence voltage at that point and using Ohm s Law: (11) Substituting Equations (4) and (5) into (6) and carrying out the top line of the matrix multiplication to get V a0, the following expression results: Note that the general form of Equation (7) for arbitrary x and y and for arbitrary phase shifting between phases, would be: where b and c are the Phase B and Phase C phase shifts relative to Phase A. Equation (8) will become important shortly, but for the time being, we rewrite Equation (7) in rectangular form, making use of the fact that This gives: and. Equation (9) is a generalized expression for the magnitude of V a0 for arbitrary values of x and y but for b = 120 o and c = o. An additional simplifying assumption can be made: for planning calculations, the phase-phase voltage imbalance is often approximated by assuming that the Phase B and C voltages are equally spaced from the Phase A voltage. For example, if the total imbalance is 5%, then Phase B would be assumed to be 2.5% above Phase A and Phase C would be 2.5% below. Define P to be the percent imbalance between the phases. Then, (6) (7) (8) (9) However, empirical data, along with simulation results performed using the MATLAB/Simulink model in Figure 3 and a well-validated manufacturer-specific inverter model [2], suggest that Equation (11) consistently underpredicts the continuous current expected to flow in the grounding transformer. The reason is that two of the assumptions that were used to simplify Equation (8) to Equation (10) are not entirely valid. First, in the real world, the phase imbalance is not symmetrical. For example, for x = 1 and y = 1.05, the magnitude of V a0 from Equation (9) becomes 15% larger than for the symmetrical case of x = 0.975, y = (P = 5% in both cases). Figure 4 shows a surface plot of the magnitude of V a0, relative to the P = 5% case, as a function of x and y. Note that for feeder imbalances up to 10%, which is a larger value than expected in practice, the largest value seen in the surface plot in Figure 4 is 2.0. Second, under unbalanced conditions, the phase voltages are not necessarily spaced by 120 o. Simulations conducted using the MATLAB model shown in Figure 3 suggest that for 5% imbalance or greater, b and c may be shifted by two or three degrees on each phase. The primary impact of the phase separation being different than 120 o is imperfect cancellation of terms in Equation (8). Figure 5 shows a surface plot of the magnitude of V a0, relative to the case of P = 5% and normal phase shifts, as a function of b and c. Figure 5 suggests that Equation (8) is quite sensitive to changes in the phases, with the change in the magnitude of V a0 approaching a factor of 4, but fortunately in practice the phase changes are rarely such that the change in V a0 is very large, and this factor can be neglected. To get an exact value, one should use Equation (8) directly, but in the planning stage one does not know the values of x, y, b or c. Thus, to arrive at an equation that gives a realistic value but maintains the simplicity of Equation (11), based on the results in Figures 4 and 5, the proposed procedure is to double Equation (11), resulting in Equation (12). (12)

5 5 90% of V a1, if the substation grounding impedance Z 0,gnd,sub is on the order of an ohm or larger (which would be unusual in practice; for well-designed substations, this value should be in the low hundreds of milliohms). Thus, it would be prudent to simply use the worst-case value of fault current and set the fraction equal to 100%: (13) Figure 3. Generic feeder model and inverter used to test the grounding transformer design equations. Figure 4. Surface plot of the magnitude of Va0, relative to its magnitude for the symmetrical P = 5% case, as a function of x and y. The reader should bear in mind that Equation (13) neglects the PV plant s contribution to the fault current. If for a particular inverter that assumption is questionable, the inverter s fault current contribution should be added to I g, but in most cases that should be unnecessary. C. Example grounding transformer sizing results Table 2 shows the calculated X 0, I g, and I g for three sizes of PV plant and two planning levels of phase-phase voltage imbalance. The interconnection voltage is assumed to be 480 V LL, RMS. For the I g and I g results, the ±10% tolerance band on the transformer impedances has been taken into account (i.e., the currents were calculated using 90% of the transformer impedance shown in Table 2 in Equations (12) and (13)). Table 2. Example grounding transformer sizing results, assuming a 480 V interconnect voltage and 10% tolerance on the transformer impedance. PV plant size (kw) Expected imbalance Z0 (ohms) j j j % Ig' (A) Ig (A) Z0 (ohms) j j j % Ig' (A) Ig (A) Figure 5. Plot of the magnitude of V a0, normalized to the case of P = 5% at normal phase shifts (±120 o ), as a function of b and c. If P is the expected percent imbalance expressed as a fraction, V a1 is the pre-fault positive sequence voltage (V RMS,LN), and Z g is the complex impedance (R 0 + jx 0) of the grounding transformer expressed in ohms, then I g will be the circulating current in amps. Comparison against simulation results indicates that Equation (12) consistently overpredicts the value of I g, thereby providing a conservative design. 2) Calculation of the fault current withstand rating The fault current withstand capability of the grounding transformer can be calculated using a procedure similar to that used to find the circulating current. Because the zerosequence impedance is known, if the zero-sequence voltage during a fault were known, then Ohm s Law gives the fault current withstand requirement. The key lies in determining a reasonable value for the zero-sequence voltage during a fault. We know from Figure 2 that the sequence networks create an impedance divider such that the zero-sequence voltage will be some fraction of V a1. Examples in the literature [3] and from simulation results suggest that V a0 values can be as high as A. Procedure IV. GROUND POTENTIAL RISE Once the decision is made to include a grounding transformer at a DG installation site, it may become necessary to ensure that ground potential rise (GPR) does not become a problem, particularly if there are conductive (i.e., not fiber or microwave) communications channels to the PV site. The GPR at the site is the product of the impedance to remote earth and the current that flows through it. The impedance that should be used in this calculation is typically calculated using the procedure described in IEEE-367 [9]. However, it is fairly common that engineers will use the utility s calculated single-phase fault current in this calculation, along with a fault current division factor that accounts for the division of current among the various grounding paths in the circuit (also from [9]). The problem with this practice is that the utility s fault current calculation is normally done with the fault impedance and grounding electrode impedances all set to zero. This leads to a contradiction, because the resistances that are set to zero in this calculation are part of the physical mechanism that creates GPR in the first place. Thus, using the utility s single-phase fault current as the starting point leads to GPR values that are too high. The purpose of this section is to propose a more accurate symmetrical component model for calculating the

6 6 fault current to be used in the GPR calculation, in cases involving a PV plant grounding transformer. Figure 6 shows a circuit diagram of a distribution feeder including the substation source, feeder impedance, a singlephase fault applied to Phase A on the MV side of the distribution transformer, a Yg-Yg generator step-up transformer, and a grounding transformer, shown here as a zigzag transformer. The phases are color-coded to make the diagram easier to read. Fault current flows from Phase A to ground through the fault, and re-enters the system via the grounding electrodes as shown. The sequence networks that correspond to this situation are shown in Figure 7. The fault impedance, Z F, and the grounding impedance seen by the fault, R Fgnd, are shown separately. For present purposes, the fault impedance Z F can be neglected because in most cases it is much less than R Fgnd. The sequence network in Figure 7 can now be solved to determine the single phase to ground fault current that can be used as a starting point in a GPR calculation. Figure 8 shows the sequence networks for the situation in which the fault is on the LV side of the distribution transformer. In general, it will be easiest to solve these sequence network circuits using a circuit simulator like PSpice. The reason is because the zero-sequence networks in Figures 7 and 8 form the Wheatstone bridge configuration, and this causes the closed-form solution of this circuit to be cumbersome for byhand calculations. Figure 9 demonstrates how the zerosequence network in Figure 7 can be redrawn as a Wheatstone bridge. Figure 7. Sequence networks for an SLG fault on the MV bus, including the impedances to remote earth. Figure 6. Distribution feeder with a Yg-Yg distribution transformer, grounding transformer, and an SLG fault on Phase A. In addition, it is important to realize that when the distribution transformer s H-side and X-side neutrals share the same grounding electrode, which is commonly the case, the zero-sequence impedance of the distribution transformer, Z adisttx0, as seen from the MV side, is given by [10]: (13) where Z adisttx1 is the positive-sequence impedance of the transformer referred to the MV side, N is the turns ratio, and Z G is the impedance to remote earth along with any deliberately-added grounding impedance. Figure 8. Sequence networks for an SLG fault on the LV bus, including the impedances to remote earth. Equation (13) is obviously not a new result [10], but many of the newer reference books used today, especially by younger power engineers trying to understand transformers and symmetrical components, do not cover this case of a Yg-Yg transformer with a common H-X neutral. If the inverter-side voltage of the PV distribution transformer is 480 V and the feeder-side voltage is kv, then N 26, so that (14)

7 7 Because Z G will have a value of several ohms in most cases and is multiplied by 3, neglecting this term can introduce a significant error into the calculated zero-sequence impedance. The yellow block at the far right end of the feeder contains a PV plant and grounding transformer. The contents of that yellow block are shown in Figure 11, in which the orange block at the center is the Yg-Yg generator step-up transformer, the yellow blocks at the upper left are the PV inverter modules, and the solid green block is the grounding transformer. Using switches and the red blocks at the bottom of Figure 11, an SLG fault can be applied directly to the MV or LV bus of the distribution transformer. Figure 11. Contents of the yellow block at the right in Figure 10. Table 3 compares the results obtained using the two models, using the detailed model as the reference. Results are shown for a fault on the LV side of the Yg-Yg distribution transformer, and on the MV side. According to these results, the symmetrical component model produces essentially the same results as the highly detailed model, and thus is a reasonable representation of the situation. Figure 9. Demonstration that the zero-sequence network in Figure 7 can be redrawn as a Wheatstone bridge, where Z a = Z asource0 + Z aline0 + Z adisttx0. B. Testing via simulation The use of the sequence networks to determine GPR was tested by building the sequence network model in MATLAB/SimPowerSystems, and comparing it against a highly detailed model of the feeder in Reference [11], also in SimPowerSystems. The feeder in [11] was designed to test TOV and GPR situations, and [11] includes validation data for the feeder model, so this selection of test system makes sense for present purposes. In the symmetrical component model, the GPR at the PV plant is the voltage that appears across R PVgrid in Figures 7 and 8. The detailed MATLAB/Simulink model is shown in Figure 10. The green block is the substation, and the separate feeder segments are the black and white blocks. The red-outlined blocks are locations at which faults can be applied. The solid blue blocks are measurement blocks. Table 3. RMS GPR predicted by detailed and sequence network models of the feeder model described in [11]. Case Detailed model Seq net model Percent description result (Vrms) result (Vrms) error LV-side fault % MV side fault % V. CONCLUSIONS Until there is a resolution to the ongoing debate over whether inverter-based DG requires effective grounding, there is a need for: a) a simple, robust design procedure for electrically specifying grounding transformers that does not involve excessive overdesign but still meets safety and reliability needs; and b) a means for calculating the correct current for determining GPR, especially when the GSU transformer H and X neutrals share the same ground electrodes with the grounding transformer. This paper has presented recommendations and suggestions intended to meet both of these needs, and it is hoped that these procedures will help in removing a barrier to deployment of PV in distribution systems while maintaining system safety and security. Figure 10. Model of the distribution feeder described in [11], with a PV plant and grounding transformer added in the yellow block at the far right (see Figure 11).

8 8 VI. ACKNOWLEDGMENTS The authors gratefully acknowledge a) the financial support of Advanced Energy and Gerlicher Solar, and b) the invaluable technical assistance of Tom Yohn, Michael Beanland, Marc Johnson, Matthew Charles, and Lou Gasper. VII. REFERENCES [1] H. B-L. Lee, S. Chase, R. Dugan, Overvoltage Considerations for Interconnecting Dispersed Generators With Wye-Grounded Distribution Feeders, IEEE Transactions on Power Apparatus and Systems, vol. PAS-103 No. 12, December 1984, p [2] M.E. Ropp, M. Johnson, D. Schutz, S. Cozine, Effective Grounding of Distributed Generation Inverters May Not Mitigate Transient and Temporary Overvoltage, Proceedings of the 2012 Western Protective Relay Conference, September [3] P. M. Anderson, Analysis of Faulted Power Systems, originally published by Iowa State University Press 1973, republished by IEEE Press 1995, ISBN (This book is now available online free of charge from the IEEE.) [4] J. Blackburn, Symmetrical Components for Power Systems Engineering, CRC Press 1995, ISBN [5] J. Glover, M. Sarma, T. Overbye, Power System Analysis and Design, 5 th ed., Cengage Learning 2012, ISBN [6] Microgrids: Architectures and Control, ed. N. Hatziargyriou, pub. IEEE Press 2014, ISBN See page 123. [7] IEEE Std , IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems (the Green Book). [8] See IEEE , Draft 2.0, November 2011, Appendix C, pg 147. [9] IEEE Standard : IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault. [10] Electrical Transmission and Distribution Reference Book, pub. Westinghouse Electric Corporation, See Table 7, page 804, entry A-2. [11] J. Acharya, Y. Wang, W. Xu, Temporary Overvoltage and GPR Characteristics of Distribution Feeders with Multigrounded Neutral, IEEE Transactions on Power Delivery 25(2), April 2010, p Michael Ropp (M 1999) received the BS in Music from the University of Nebraska in 1992, and the MS and PhD in EE from the Georgia Institute of Technology in 1996 and 1998 respectively. He is the President and Principal Engineer of Northern Plains Power Technologies, and is a registered Professional Engineer in SD and HI. He has 17 years experience and >50 publications in power engineering, power electronics, and photovoltaics. Dustin Schutz (M 2010) received the BS in Electrical Engineering in 2006 and MS in Electrical Engineering in 2011, both from South Dakota State University. Mr. Schutz has wide-ranging experience in power electronics, embedded control systems, and power electronics and power system simulation. His current work focuses on multi-inverter islanding scenarios and microgrid controls. Chris Mouw received the BSEE from South Dakota State University in Mr. Mouw is presently with Northern Plains Power Technologies, Brookings, SD, where he works on all aspects of modeling of electric power systems with power electronics, automation of modeling, and many types of studies for utilities.

Babak Enayati National Grid Thursday, April 17

Babak Enayati National Grid Thursday, April 17 2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April

More information

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System

More information

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection Engineered Solutions for Power System Protection, Automaton and Control APPLICATION NOTE Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection 180622 Abstract This

More information

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations A.R. Sultan, M.W. Mustafa, M.Saini Faculty of Electrical Engineering Universiti Teknologi Malaysia (UTM)

More information

ANALYSIS OF LIGHTNING ARRESTER OVERLOADING IN FUTURE DISTRIBUTION SYSTEMS WITH DISTRIBUTED GENERATION. A Thesis JONATHAN MICHAEL SNODGRASS

ANALYSIS OF LIGHTNING ARRESTER OVERLOADING IN FUTURE DISTRIBUTION SYSTEMS WITH DISTRIBUTED GENERATION. A Thesis JONATHAN MICHAEL SNODGRASS ANALYSIS OF LIGHTNING ARRESTER OVERLOADING IN FUTURE DISTRIBUTION SYSTEMS WITH DISTRIBUTED GENERATION A Thesis by JONATHAN MICHAEL SNODGRASS Submitted to the Office of Graduate and Professional Studies

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Short-Circuit Apparent Power of System Survey Comments

Short-Circuit Apparent Power of System Survey Comments WG Item 87 Short-Circuit Apparent Power of System Survey Comments Again, the values given in Table 18 are totally unrealistic of system conditions. I do not know any systems for which the short-circuit

More information

EMERGING distributed generation technologies make it

EMERGING distributed generation technologies make it IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, NOVEMBER 2005 1757 Fault Analysis on Distribution Feeders With Distributed Generators Mesut E. Baran, Member, IEEE, and Ismail El-Markaby, Student Member,

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Evaluating the Response of Surge Arresters

Evaluating the Response of Surge Arresters 1 Jens Schoene Chandra Pallem Tom McDermott Reigh Walling Evaluating the Response of Surge Arresters to Temporary Overvoltages Panel Session of the IEEE Wind and Solar Collector Design Working Group 2014

More information

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2012 Grid of the Future Symposium Impacts of the Decentralized Photovoltaic Energy Resources on the Grid B. ENAYATI, C.

More information

Voltage-based limits on PV hosting capacity of distribution circuits

Voltage-based limits on PV hosting capacity of distribution circuits Voltage-based limits on PV hosting capacity of distribution circuits Michael Ropp, Ph.D., P.E. Northern Plains Power Technologies Brookings, SD 57006 USA Brief description of NPPT What we do Simulation

More information

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Introduction The topic of system grounding is extremely important, as it affects the susceptibility of the system to voltage

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

Protective Relaying for DER

Protective Relaying for DER Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed

More information

Catastrophic Relay Misoperations and Successful Relay Operation

Catastrophic Relay Misoperations and Successful Relay Operation Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

Tutorial on Symmetrical Components

Tutorial on Symmetrical Components Tutorial on Symmetrical Components Part : Examples Ariana Amberg and Alex Rangel, Schweitzer Engineering Laboratories, nc. Abstract Symmetrical components and the per-unit system are two of the most fundamental

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Table of Contents. Introduction... 1

Table of Contents. Introduction... 1 Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

FERRORESONANCE SIMULATION STUDIES USING EMTP

FERRORESONANCE SIMULATION STUDIES USING EMTP FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in

More information

Power Plant and Transmission System Protection Coordination Fundamentals

Power Plant and Transmission System Protection Coordination Fundamentals Power Plant and Transmission System Protection Coordination Fundamentals NERC Protection Coordination Webinar Series June 2, 2010 Jon Gardell Agenda 2 Objective Introduction to Protection Generator and

More information

This document covers common questions concerning the design of an effectively grounded system.

This document covers common questions concerning the design of an effectively grounded system. This document covers common questions concerning the design of an effectively grounded system. To prevent against temporary overvoltage conditions when a line-to-ground fault occurs on the power grid.

More information

Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System

Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System Dhruvita Mandaliya 1, Ajay M. Patel 2, Tarang Thakkar 3 1 PG Student, Electrical Engineering Department, Birla Vishvakarma

More information

Safety through proper system Grounding and Ground Fault Protection

Safety through proper system Grounding and Ground Fault Protection Safety through proper system Grounding and Ground Fault Protection November 4 th, 2015 Presenter: Mr. John Nelson, PE, FIEEE, NEI Electric Power Engineering, Inc. Event to start shortly Scheduled time:

More information

ECE 528 Understanding Power Quality

ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 22 1 Today Homework 5 questions Homework 6 discussion More on

More information

Chapter # : 17 Symmetrical Fault Calculations

Chapter # : 17 Symmetrical Fault Calculations Chapter # : 17 Symmetrical Fault Calculations Introduction Most of the faults on the power system lead to a short-circuit condition. The short circuit current flows through the equipment, causing considerable

More information

MODELING THE EFFECTIVENESS OF POWER ELECTRONICS BASED VOLTAGE REGULATORS ON DISTRIBUTION VOLTAGE DISTURBANCES

MODELING THE EFFECTIVENESS OF POWER ELECTRONICS BASED VOLTAGE REGULATORS ON DISTRIBUTION VOLTAGE DISTURBANCES MODELING THE EFFECTIVENESS OF POWER ELECTRONICS BASED VOLTAGE REGULATORS ON DISTRIBUTION VOLTAGE DISTURBANCES James SIMONELLI Olivia LEITERMANN Jing HUANG Gridco Systems USA Gridco Systems USA Gridco Systems

More information

LOW-RESISTANCE grounding resistors (LRGs) appear

LOW-RESISTANCE grounding resistors (LRGs) appear IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 44, NO. 5, SEPTEMBER/OCTOBER 2008 1311 Grounding the Neutral of Electrical Systems Through Low-Resistance Grounding Resistors: An Application Case Massimo

More information

Improving Power Quality in Low Voltage Networks Containing Distributed Energy Resources

Improving Power Quality in Low Voltage Networks Containing Distributed Energy Resources Improving Power Quality in Low Voltage Networks Containing Distributed Energy Resources Sumit Mazumder, Arindam Ghosh, Firuz Zare and Gerard Ledwich ABSTRACT: Severe power quality problem can arise when

More information

Grounding for Power Quality

Grounding for Power Quality Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

Rarely used, problems with unbalanced loads.

Rarely used, problems with unbalanced loads. THREE-PHASE TRANSFORMERS Transformers used in three-phase systems may consist of a bank of three single-phase transformers or a single three-phase transformer which is wound on a common magnetic core.

More information

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web: Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation

More information

AGN 005 Fault Currents and Short Circuit Decrement Curves

AGN 005 Fault Currents and Short Circuit Decrement Curves Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 005 Fault Currents and Short Circuit Decrement Curves DESCRIPTION To facilitate the correct design of an electrical

More information

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application General Application Information Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application Hydro One Remote Communities Inc. Lori.Rice@hydroone.com 1-807-474-2828 This Application

More information

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:

More information

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1) Dynamics and Control of Distributed Power Systems Fuel cell power system connection Ian A. Hiskens University of Wisconsin-Madison ACC Workshop June 12, 2006 This topology is fairly standard, though there

More information

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,

More information

BED INTERCONNECTION TECHNICAL REQUIREMENTS

BED INTERCONNECTION TECHNICAL REQUIREMENTS BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D Electricity Ten Year Statement November 2017 01 Electricity Ten Year Statement November 2017 001 Appendix D 1 Short-circuit currents 02 2 Short-circuit current terminology 04 3 Data requirements 07 4 Fault

More information

ESB National Grid Transmission Planning Criteria

ESB National Grid Transmission Planning Criteria ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star. Summary Of Interconnection Technical Guidelines for Renewable Energy Systems 0-100 kw under Standard Offer Contract (Extract from JPS Guide to Interconnection of Distributed Generation) This document is

More information

Power Factor & Harmonics

Power Factor & Harmonics Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics

More information

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) PATTI.RANADHEER Assistant Professor, E.E.E., PACE Institute

More information

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit CHAPTER 2 Basic Concepts, Three-Phase Review, and Per Unit 1 AC power versus DC power DC system: - Power delivered to the load does not fluctuate. - If the transmission line is long power is lost in the

More information

Aggregated Rooftop PV Sizing in Distribution Feeder Considering Harmonic Distortion Limit

Aggregated Rooftop PV Sizing in Distribution Feeder Considering Harmonic Distortion Limit Aggregated Rooftop PV Sizing in Distribution Feeder Considering Harmonic Distortion Limit Mrutyunjay Mohanty Power Research & Development Consultant Pvt. Ltd., Bangalore, India Student member, IEEE mrutyunjay187@gmail.com

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:

More information

Short-circuits in ES Short-circuit: cross fault, quick emergency change in ES the most often fault in ES transient events occur during short-circuits

Short-circuits in ES Short-circuit: cross fault, quick emergency change in ES the most often fault in ES transient events occur during short-circuits Short-circuits in ES Short-circuit: cross fault, quick emergency change in ES the most often fault in ES transient eents occur during short-circuits Short-circuit formation: fault connection between phases

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Electrical Power Systems

Electrical Power Systems Electrical Power Systems CONCEPT, THEORY AND PRACTICE SECOND EDITION SUBIR RAY Professor MVJ College of Engineering Bangalore PHI Learning Pfcte tofm Delhi-110092 2014 Preface xv Preface to the First Edition

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES Authors: Joe Perez, P.E.: SynchroGrid, College Station, Texas Hung Ming Chou, SynchroGrid, College Station, Texas Mike McMillan, Bryan

More information

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME Donald M. MACGREGOR Electrocon Int l, Inc. USA eii@electrocon.com Venkat TIRUPATI Electrocon Int l, Inc. USA eii@electrocon.com Russell

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE

Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE Experiment 45 Three-Phase Circuits OBJECTIVE To study the relationship between voltage and current in three-phase circuits. To learn how to make delta and wye connections. To calculate the power in three-phase

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels

More information

Visualization and Animation of Protective Relay Operation

Visualization and Animation of Protective Relay Operation Visualization and Animation of Protective Relay Operation A. P. Sakis Meliopoulos School of Electrical and Computer Engineering Georgia Institute of Technology Atlanta, Georgia 30332 George J. Cokkinides

More information

Substation Testing and Commissioning: Power Transformer Through Fault Test

Substation Testing and Commissioning: Power Transformer Through Fault Test 1 Substation Testing and Commissioning: Power Transformer Through Fault Test M. Talebi, Member, IEEE, Power Grid Engineering Y. Unludag Electric Power System Abstract This paper reviews the advantage of

More information

The Analysis of Voltage Increase Phenomena in a Distribution Network with High Penetration of Distributed Generation

The Analysis of Voltage Increase Phenomena in a Distribution Network with High Penetration of Distributed Generation The Analysis of Voltage Increase Phenomena in a Distribution Network with High Penetration of Distributed Generation Insu Kim, Ronald G. Harley, and Raeey Regassa Georgia Institute of Technology Atlanta,

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Modelling Parameters. Affect on DER Impact Study Results

Modelling Parameters. Affect on DER Impact Study Results Modelling Parameters Affect on DER Impact Study Results Agenda Distributed Energy Resources (DER) Impact Studies DER Challenge Study Steps Lessons Learned Modeling Reverse Power Transformer Configuration

More information

AS the power distribution networks become more and more

AS the power distribution networks become more and more IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 21, NO. 1, FEBRUARY 2006 153 A Unified Three-Phase Transformer Model for Distribution Load Flow Calculations Peng Xiao, Student Member, IEEE, David C. Yu, Member,

More information

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21 Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

THE EFFECTS OF NEUTRAL SHIFTS ON PROTECTIVE RELAYS. Authors: Joe Perez P.E., SynchroGrid, College Station, Texas 77845

THE EFFECTS OF NEUTRAL SHIFTS ON PROTECTIVE RELAYS. Authors: Joe Perez P.E., SynchroGrid, College Station, Texas 77845 THE EFFECTS OF NEUTRAL SHIFTS ON PROTECTIVE RELAYS Authors: Joe Perez P.E., SynchroGrid, College Station, Texas 77845 Amir Makki Ph.D, Softstuf, Philadelphia, PA 19106 Shijia Zhao, Texas A&M University,

More information

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System,

More information

Distance Protection of Cross-Bonded Transmission Cable-Systems

Distance Protection of Cross-Bonded Transmission Cable-Systems Downloaded from vbn.aau.dk on: April 19, 2019 Aalborg Universitet Distance Protection of Cross-Bonded Transmission Cable-Systems Bak, Claus Leth; F. Jensen, Christian Published in: Proceedings of the 12th

More information

Experiences in Integrating PV and Other DG to the Power System

Experiences in Integrating PV and Other DG to the Power System Experiences in Integrating PV and Other DG to the Power System (Radial Distribution Systems) Prepared by: Philip Barker Founder and Principal Engineer Nova Energy Specialists, LLC Schenectady, NY Phone

More information

PRAOGEN, A TOOL FOR STUDYING CONNECTION OF GENERATING PLANT ONTO THE MEDIUM- VOLTAGE NETWORK

PRAOGEN, A TOOL FOR STUDYING CONNECTION OF GENERATING PLANT ONTO THE MEDIUM- VOLTAGE NETWORK PRAOGEN, A TOOL FOR STUDYING CONNECTION OF GENERATING PLANT ONTO THE MEDIUM- VOLTAGE NETWORK J.L. Fraisse, F. Boulanger, Ph. Juston, P. Lemerle, O. Jeannin EDF-DEGS; EDF-R&D, France Since early in 1990

More information

Short-Circuit Current Calculations

Short-Circuit Current Calculations Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Multiplier = 00 *% Z transformer Step 2.

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

AC Power Instructor Notes

AC Power Instructor Notes Chapter 7: AC Power Instructor Notes Chapter 7 surveys important aspects of electric power. Coverage of Chapter 7 can take place immediately following Chapter 4, or as part of a later course on energy

More information

IEEE sion/1547revision_index.html

IEEE sion/1547revision_index.html IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html

More information

Solving Customer Power Quality Problems Due to Voltage Magnification

Solving Customer Power Quality Problems Due to Voltage Magnification PE-384-PWRD-0-11-1997 Solving Customer Power Quality Problems Due to Voltage Magnification R. A. Adams, Senior Member S. W. Middlekauff, Member Duke Power Company Charlotte, NC 28201 USA E. H. Camm, Member

More information

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,

More information

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Single Phase

More information

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority S. Songsiri * and S. Sirisumrannukul Abstract This paper presents an application

More information

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit

More information

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Tripping of circuit breakers in PV installations due to zero sequence field impedance Tripping of circuit breakers in PV installations due to zero sequence field impedance B. Verhelst 1,2, C. Debruyne 1,2, J. Desmet 1,2 1 dept. Electrical Engineering - Lemcko HoWest Kortrijk, Belgium bart.verhelst@howest.be

More information

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions

More information

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations Journal of International Council on Electrical Engineering ISSN: (Print) 2234-8972 (Online) Journal homepage: http://www.tandfonline.com/loi/tjee20 Optimal neutral ground resistor rating of the medium

More information

Coordination of protective relays in MV transformer stations using EasyPower Protector software

Coordination of protective relays in MV transformer stations using EasyPower Protector software Coordination of protective relays in MV transformer stations using EasyPower Protector software S. Nikolovski, Member, IEEE, I. Provci and D. Sljivac In this paper, the analysis of digital protection relays

More information

Harmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems

Harmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems University of Wollongong Research Online University of Wollongong Thesis Collection 1954-2016 University of Wollongong Thesis Collections 2006 Harmonic impact of photovoltaic inverter systems on low and

More information

Effects of Transformer Connection on Voltage Sag Characterization

Effects of Transformer Connection on Voltage Sag Characterization Effects of Transformer Connection on Voltage Sag Characterization Parijat Deb 1, Amit Gupta 2 ¹PG Scholar, Gyan Ganga College of Technology, Jabalpur, M.P (India) 2 Asst.Professor, Gyan Ganga College of

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information