Importance of Grounding in Power System. Presented by Mr. H Jayakumar Ex- Joint Director CPRI

Size: px
Start display at page:

Download "Importance of Grounding in Power System. Presented by Mr. H Jayakumar Ex- Joint Director CPRI"

Transcription

1 Importance of Grounding in Power System Presented by Mr. H Jayakumar Ex- Joint Director CPRI

2 OBJECT OF EARTHING Prime Object of Earthing is to Provide a Zero Potential Surface in and around and under the area where the electrical equipment is installed. Earthing is essential at every stage of electricity generation, transmission and utilization

3 IMPORTANCE OF EARTHING Personal Safety Protection of Equipment : Prevent or at least minimize damage to equipment as a result of heavy fault current and lightning thus improve the reliability of equipment Protection of System : Improve the reliability of power supply.

4 STANDARDS FOLLOWED IS: 3043 : 1966, 1987 reaffirmed 2006 Code of Practice for Earthing. Indian Electricity rules 1956 ( as ammended up to 2000) IS: ( reaffirmed 2005 )Protection of Buildings and allied Structures against lightning Code of Practice. Manual on Earthing of AC Power Systems : CBIP Publication No.302 : 2007 BS: 7430 : 1991, Code of Practice for Earthing.( formerly CP 1013: 1966) British Standard Institution London 1992 IEEE :80 : 2000( Revision of IEEE Std 80: 1986) Guide for Safety in AC Substation Grounding IEEE :142 :2007(Revision of IEEE Std 142 :1991) Grounding of Industrial and Commercial Power System. IEEE 1100 : 2005 (Revision of IEEE Std 1100 : 1999) Powering and Grounding Electronic Equipment

5 1. Plate Earthing TYPE OF EARTHING R g = ρ A π A ohms 2. Pipe / Rod Earthing R g = 100ρ log 2πl e 4l d ohms Doubling the Diameter Decrease the Resistance by 10 to 12% Doubling the Length Decrease the Resistance by 40%

6 3. Strip Earthing TYPE OF EARTHING R g = 100ρ log 2πl e 2 2l wt ohms 4. Combination of 1 & 3 and 2 & 3 5. Mat Earthing R g ρ = + 4 r ρ L ohms

7 TYPE OF EARTHING R = Station ground resistance in ohms r = is the radius of a circle having the same area or that occupied by grid in meters L = Total buried length of conductors in meters ρ = Resistivity of the soil (assumed uniform) in ohm-m A = Area of both sides of the plates in m² L = Length of the rod or pipe (in cm) d = diameter of rod or pipe (in cm) l = length of the strip (in cm) w = depth of burial of the electrode in cm t = width (in the case of strip) or twice the diameter (for round conductor) in cm In the above formula no where type of material used for grounding is mentioned. So, as far as grounding is concerned material is immaterial since the ground resistance is the resistance offered to the nearest ground hence, ground (Soil Resistivity) plays a very important role.

8 Type of Earth Tester Which type of earth tester should be used for measuring the Soil Resistivity and Ground Resistance Digital meter or Analog meter? Digital meter of reputed make. Ground resistance is directly proportional to the soil resistivity, hence measurement of soil resistivity by accurate meter of reputed make is very important. In grounding the value of soil resistivity is most important for estimating the ground resistance and surface potentials (mesh, step and touch). Make Model Megger DET 2/2 UK Fluke 1623 & 1625 USA / UK Chauvin Arnoux 6460, 6462 & 6470 FRANCE / UK Kew (Kyoritsu) 4106 JAPAN

9 Comparison of Analog & Digital Earth Tester Why there is always a difference in the measured resistance values if measured with different earth testers even if all are calibrated ones? This is not true in case of reputed make digital earth testers. This may be true when compared with analog to digital earth testers of reputed make. PARAMETERS ANALOG METER DIGITAL METER Accuracy 5% of full scale and shall be effective 2% of reading in entire range hence above 25% of full scale. At 25% of very accurate and high resolution reading absolute error is 20%. Not accurate and low resolution Voltage 250V hand cranking Micro processor based 30 to 50 V automatic reading Frequency Fixed (60 to 90 HZ) Variable. In automode it selects test frequency with least amount of noise High Spike resistance Do not indicate Displays the high spike resistance. Open circuit Do not indicate Displays current circuit open/potential circuit open

10 Measurement of Soil Resistivity How to check the soil resistivity? Minimum how may readings should be taken and at what points for a correct measurement of soil resistivity value? a) Equally spaced or Dr. F.Wenner Arrangement Ρ = 2 Π AR Ω-M

11 Measurement of Soil Resistivity b) Unequally spaced or Schelumberger Palmer Arrangement Ρ = Π C ( C+d) * R / d Ω-M

12 Measurement of Soil Resistivity A set of readings taken with various probe spacings (2m, 5 m, 10 m, 25 m, 50m) gives a set of resistivity which, when plotted against spacing, indicates whether there are distinct layers of different soil or rock and gives an idea of their respective resistivities and depth. This has to be repeated in all directions of the site i.e., horizontal, vertical and diagonal. The mean value is calculated. In case the values lies within +/- 30% of mean value (70% to 130%) the soil is considered to be uniform (Homogenous soil).

13 CASE STUDY Ρ = 2 Π AR Ω-M A= Distance between adjacent electrode (M), R = Earth tester reading SL.NO a R ρ Meters Ω Ohm-Meters min max ρ Average % of ρ Ave = 1.3 x = % of ρ Ave = 0.7 x = Minimum & Maximum value lies within and The Soil is Homogeneous.

14 Measurement of Ground Resistance What is the principle for measuring the earth resistance value? The fall of potential method: Consisting of injecting a known alternating current through the electrode under test and an auxiliary current probe and plotting the ratio of V/I = R as a function of probe spacing x. The potential electrode is moved away from the ground under test in steps of 10%. A value of resistance is obtained at each step. The resistance is plotted as a function of distance in ohms at which this plotted curve appears to level out is taken as the resistance value of the ground under test. This level out will be potential electrode at 61.8% of distance between ground electrode under test and auxiliary electrode. This was established by E.B.Curdt s for small hemispherical electrode

15 Measurement of Ground Resistance

16 Measurement of Ground Resistance

17 Measurement of Ground Resistance Distance between station earth (P1C1) and potential electrode (P2) mtrs Earthing tester reading Ω Earth Pit No 1 Earth Pit No:2 Earth Pit No (20% R1) (40%R2) (60%R3) (61.8%of30) Remote Electrode(C2) from station ground (C1P1) 30m 30m 30m Result: Fall of Potential Method Ave. Of = Ave. Of =6.242 Average of =

18 Measurement of Ground Resistance E.B Curd s Method (R3-R2) (R3-R2) (R3-R2) Slope Method µ= (R2-R1) (R2-R1) (R2-R1) From the chart Value = Remote electrode (RE)30m = 60.13% of RE(30) 57.85% of RE(30) m m Value = 8.69Ω 6.40Ω - Analysis of Result Fall of Potential 8.545Ω 6.242Ω 17.46Ω E.B Curd ts 8.780Ω 6.470Ω 17.40Ω Slope Method 8.690Ω 6.400Ω - Remote electrode (C2) at 30 mtrs from earth pit (C1P1). Earth Pits are conventional type back filled 2Ft all around the electrodes. Earth Pit No1: Located at A & B colony 50mm dia 3mtrs Long GI Pipe. Earth Pit No2: Located in 33KV Substation 100mm dia 3mts Long GI Pipe. Earth Pit No3: Near DG Set New 60mm dia 2mtrs Long GI pipe.

19 Calculation of Earth Resistance of Multiple Electrodes How to calculate the resultant earth resistance value of the earth electrodes if more than one pits are required to be installed? Multiple electrodes in parallel yield lower resistance to ground than a single electrode. Multiple rods are commonly used to provide the low grounding resistance required by high capacity installations. Adding a second rod does not however provide a total resistance of half that of a single rod, unless the two are several rod length apart. A useful rule is that grounding systems of 2-24 rods placed one rod length apart in a line, hollow triangle, circle or square will provide a grounding resistance divided by number of rods and multiplied by the factor F. Multiplying Factors for Multiple Rods: No.of Rods F

20 Current carrying Capacity of Earth Electrode How to calculate current carrying capacity of an earth electrode? Current caring capacity of an earth electrode depends on 1. The total surface area of the electrode in contact with earth 2. Resistivity of the soil and 3. Duration of fault in seconds. The formula for current caring capacity (Current density) is: Current density = 7.57 X 10³ ρt Amp / Sq-m ρ = Resistivity of the soil (assumed uniform) in ohm-m. t = Duration of fault in seconds.

21 Geometry & No. of Electrodes Required 7. How does earth electrode geometry affects the earthing system? The total surface area coming in contact with earth is the criteria. 8. How to calculate the number of earth electrodes required for any particular application? This depends on the fault level the calculation is as follows: Calculation of No.of Plates required: For Example: The total surface area = 0.6 x 0.6 x 2 sq.m = 0.72 sq.m Fault current = 6 kilo amperes Duration of Fault = 1 sec. Soil Resisitivity = 100 ohm - m Current density = 7.57 X 10³ Amp / Sq-m ρt = 7.57 X 10³ = 757 Amp /Sq-m 100X1 One Plate will carry 757 X 0.72 = Amperes

22 Geometry & No. of Electrodes Required To carry 6 kilo amperes No.of plates required = 6000 / = 11 Nos. Calculation of No.of Pipes required: For Example: The total surface area of a 3 mtr long 80 mm dia = π x 0.08 x 3 sq.m = sq.m Fault current = 6 kilo amperes Duration of Fault = 1 sec. Soil Resisitivity = 100 ohm - m Current density = 7.57 X 10³ ρt Amp / Sq-m = 7.57 X 10³ = 757 Amp /Sq-m 100X1 One Pipe will carry 757 X = Amperes To carry 6 kilo amperes No.of plates required = 6000 / = 10.5 = 11 nos.

23 Minimum Accepted Earth Resistance What is the minimum accepted earth resistance value for different applications? Are these resistance values mentioned in any standard? References: US AID INDIA Book The earth resistance shall be as low as possible and shall not exceed the following limits Power stations (generating station) 0.5 ohms EHT Sub-station 1.0 ohms 33 KV Stations 2.0 ohms D/t Structure 5.0 ohms Tower Foot resistance 10.0 ohms Page 92 Modernisation of power distributions Same as above. IEEE standard chapter 4 page 164 Resistance in the 1 ohm to 5 ohms range are generally found suitable for industrial plant sub-station and buildings and large commercial installations. Lightning arrestors ground resistance for protection of buildings and allied structures Less than 10 ohms Clause Page 32 IS 2309 : 1989.

24 Precaution to Be Taken For Measuring Ground Resistance 10.Precaution to be taken while measuring ground resistance. Precautions to be taken during resistance measurement. a. Avoid taking measurement during cloudy day. b. There is a possibility of lethal potential existing between a station ground & a remote Ground. If a system fault involving the station ground occurs while ground resistance is being measured. The use of Rubber gloves is advisable while making connections to the test electrode. Under no circumstances should the two hands or other part of the body of the testing personal should be allowed to complete the circuit between the points of possible high potential difference. c. An isolated lightening arrester ground should never be tested with the arrester in service, because of the possible high potential gradients around the ground connection. d. Since the resistivity of the upper soil layers is greatly influenced by weather, a day test should be chosen which is free from extreme weather conditions. 11.How many times is year we have to check the Earthing point. IS: 3043: Clause (page76): Normally annual measurement of earth resistance of substations shall be carried out but local circumstances in the light of experience may justify increase or decrease in this interval but it should not be less than once in two years. This shall be compared with the internal record. Allthough resistance to ground will change seasonally and over time any increase of the resistance > 20% or more should be investigated and corrective action taken to lower the resistance.

AC Voltage- Pipeline Safety and Corrosion MEA 2015

AC Voltage- Pipeline Safety and Corrosion MEA 2015 AC Voltage- Pipeline Safety and Corrosion MEA 2015 WHAT ARE THE CONCERNS ASSOCIATED WITH AC VOLTAGES ON PIPELINES? AC concerns Induced AC Faults Lightning Capacitive coupling Safety Code Induced AC Corrosion

More information

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor Safety earthing Sector Energy PTI NC Theodor Connor Copyright Siemens AG 2008. All rights reserved. Content Introduction Theoretical background Soil Analysis Design of earthing system Measurements on earthing

More information

UNDERSTANDING. Ground Resistance Testing. Soil Resistivity. Ground Resistance. 3-Point Measurements. 4-Point Measurements. Clamp-On Measurements

UNDERSTANDING. Ground Resistance Testing. Soil Resistivity. Ground Resistance. 3-Point Measurements. 4-Point Measurements. Clamp-On Measurements UNDERSTANDING Ground Resistance Testing Current supply E Ammeter (I) I Voltmeter (E) Ground electrode under test X Auxiliary potential electrode Y Auxiliary current electrode Z R Rx R1 R2 Rn-1 Rn EARTH

More information

High Voltage Pylon Earth Measurements

High Voltage Pylon Earth Measurements High Voltage Pylon Earth Measurements Speaker: Gavin van Rooy Authors: Frank Barnes and Gavin van Rooy Tycom (Pty) Ltd PO Box 3546, Randburg, 2125, South Africa E-mail: frank@tycom.co.za Phone: 011 787

More information

Industrial and Commercial Power Systems Topic 7 EARTHING

Industrial and Commercial Power Systems Topic 7 EARTHING The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 7 EARTHING 1 INTRODUCTION Advantages of earthing (grounding): Limitation

More information

Understanding Soil Resistivity Testing

Understanding Soil Resistivity Testing Technical Hotline: (0) -9 Technical Hotline: (0) -9 www.aemc.com www.aemc.com Understanding Testing Effects of on Ground Electrode Resistance Factors Affecting APPLICATION NOTES OCTOBER Understanding Testing

More information

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA Rajat Verma Project Engineer BHEL EDN, BANGALURU, MYSORE ROAD, KARNATAKA 560024, India ABSTRACT

More information

Evaluation of Soil Resistivity Characteristics forsubstation Grounding: a Case Study of a University Campus in South-West Zone, Nigeria

Evaluation of Soil Resistivity Characteristics forsubstation Grounding: a Case Study of a University Campus in South-West Zone, Nigeria Evaluation of Soil Resistivity Characteristics forsubstation Grounding: a Case Study of a University Campus in South-West Zone, Nigeria Adegboyega Gabriel A Bells University of Technology, Ota, Nigeria

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD GROUNDING RESISTANCE MEASUREMENTS AND IMPROVEMENT

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD GROUNDING RESISTANCE MEASUREMENTS AND IMPROVEMENT SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-III) REV-01 GROUNDING RESISTANCE MEASUREMENTS AND IMPROVEMENT This specification is property of SEC

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING Rev. 01 This specification is property of SEC and subject to change or modification without any notice

More information

Attendee Announcements

Attendee Announcements Attendee Announcements Seminar Raffle Be sure to drop your raffle ticket in the drum at today s Keynote located in the Mile High Ballroom. You have a chance to win a $250 American Express Gift Card. One

More information

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid 1 Arpan K. Rathod, 2 Chaitanya H. Madhekar Students Electrical Engineering, VJTI, Mumbai, India

More information

ABSTRACT 1 INTRODUCTION

ABSTRACT 1 INTRODUCTION ELECTROMAGNETIC ANALYSIS OF WIND TURBINE GROUNDING SYSTEMS Maria Lorentzou*, Ian Cotton**, Nikos Hatziargyriou*, Nick Jenkins** * National Technical University of Athens, 42 Patission Street, 1682 Athens,

More information

Instruction Manual for Digital Grounding Resistance Meter

Instruction Manual for Digital Grounding Resistance Meter Instruction Manual for Digital Grounding Resistance Meter Instruction Manual for Digital Grounding Resistance Meter Table of Contents I. Overview...2 II. Open-case Inspection...3 III. Safety Precautions...4

More information

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation Marcos Telló Department of Electrical Engineering Pontifical Catholic University of Rio Grande

More information

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments Thomas Szollossy Senior Technical Support Engineer Power Quality Thailand PQSynergy 2017, Chiang Mai, Thailand Introduction

More information

Fall-Of-Potential Calculations Using MALZ

Fall-Of-Potential Calculations Using MALZ Fall-Of-Potential Calculations Using MALZ by Greg Chang Pacific Gas & Electric Company, California, USA As a means to check the validity of the soil and ground grid model used in a grounding analysis study,

More information

FALL-OF-POTENTIAL GROUND RESISTANCE TESTER

FALL-OF-POTENTIAL GROUND RESISTANCE TESTER FALL-OF-POTENTIAL GROUND RESISTANCE TESTER Models 3620, 3640 & 4610 Call toll free (800) 537-0351 or visit www.allspec.com Measures soil resistivity (4-Point) (Model 4610) Measures ground resistance (2-

More information

ANALOG RESISTANCE METER

ANALOG RESISTANCE METER 1 P a g e M A N 1 6 0 MILLER 400A ANALOG RESISTANCE METER USER S MANUAL Revised Aug 22, 2018 2 P a g e M A N 1 6 0 CONTENTS Page Description.. 3 Operating Instructions 4 Applications 5 4-Electrode Applications..

More information

Examples of Design for Cathodic Protection Systems

Examples of Design for Cathodic Protection Systems Examples of Design for Cathodic Protection Systems CURRENT REQUIREMENTS From Estimated Exposed Surface Area Estimating current requirements from expected exposed surface is always subject to error. There

More information

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy High Voltage Pylon earth Measurements Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy Abstract The earth connection of high voltage electrical power line pylons is obviously

More information

GROUND TESTERS For all of your Ground Testing needs...

GROUND TESTERS For all of your Ground Testing needs... GROUND TESTERS For all of your Ground Testing needs... An array of Ground Testers to choose from Whether you are doing a simplified 2-Point, a more complete 3- or 4-Point Fall-of-Potential test, a soil

More information

LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE

LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE International Lightning Protection Association 1 st Symposium Valencia Spain 24th 25th of November, 2011 LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE Alain Rousseau SEFTIM (France) ABSTRACT To make a

More information

HV Substation Earthing Design for Mines

HV Substation Earthing Design for Mines International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 4, Issue 6 (October 2012), PP. 100-107 HV Substation Earthing Design for Mines M.

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

FAQ ON EARTHING STANDARDS 16/08/2018

FAQ ON EARTHING STANDARDS 16/08/2018 FAQ ON EARTHING STANDARDS 16/08/2018 This document has been updated to include changes made to substation earthing layouts that have been made necessary due to copper theft. The main changes to be aware

More information

DESIGN OF SUBSTATION GROUNDING IN A TWO LAYER EARTH STRUCTURE (A CASE STUDY OF 132KV SUBSTATION)

DESIGN OF SUBSTATION GROUNDING IN A TWO LAYER EARTH STRUCTURE (A CASE STUDY OF 132KV SUBSTATION) DESIGN OF SUBSTATION GROUNDING IN A TWO LAYER EARTH STRUCTURE (A CASE STUDY OF 132KV SUBSTATION) Prakash K Makhijani 1, Chirag J Soni 2, Riya B Agarwal 3 1 Director, 2 Design Engineer, 3 Design Engineer,

More information

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

Form-IV. Form of Inspection/Test Report. (Under Regulation 43) Form-IV Form of Inspection/Test Report (Under Regulation 43) 1. Name and address of the Chartered Electrical Safety Engineer 2. Name and address of the consumer (or) Owner(or) supplier: Contact No: E-Mail:

More information

ENGINEERING REPORT PHASES I & II MITIGATOR PERFORMANCE TESTS

ENGINEERING REPORT PHASES I & II MITIGATOR PERFORMANCE TESTS ENGINEERING REPORT PHASES I & II MITIGATOR PERFORMANCE TESTS INDUCED AC MITIGATION PERFORMANCE ON A STEEL GAS TRANSMISSION PIPELINE REPORT OF JANUARY 29, 2014 Copyright MATCOR, Inc. 2014 MITIGATOR TM VS.

More information

Earth Mat Design for a 66kv Substation

Earth Mat Design for a 66kv Substation Earth Mat Design for a 66kv Substation Abija Baby 1, Jeswin James 2, Sharanya Vinod 3, Vyshnavy Sobhan 4, Asst.Pro. Thomas George 5, Dept. of EEE, Mar Baselios Institute of Technology and Science, Nellimatom,

More information

Appendix. Appendix. Getting Down to Earth. AVO, International NJATC 07

Appendix. Appendix. Getting Down to Earth. AVO, International NJATC 07 IBEW NECA Appendix ATTITUDE SKILL KNOWLEDGE FOR APPRENTICESHIP & TRAINING THE ELECTRICAL INDUSTRY Appendix Getting Down to Earth AVO, International Appendix IBEW NECA ATTITUDE SKILL KNOWLEDGE FOR APPRENTICESHIP

More information

Understand the importance of Ground Resistance Testing & much more! (800) (508)

Understand the importance of Ground Resistance Testing & much more! (800) (508) Soil Resistivity Ground Resistance 3-Point Measurements 4-Point Measurements Clamp-On Measurements Understand the importance of Ground Resistance Testing & much more! (800) 343-1391 (508) 698-2115 www.aemc.com

More information

ANALOG RESISTANCE METER USER S MANUAL

ANALOG RESISTANCE METER USER S MANUAL Page 1 of 14 MILLER 400A ANALOG RESISTANCE METER USER S MANUAL Page 2 of 14 CONTENTS Page Description.. 3 Operating Instructions 4 Applications 5 4-Electrode Applications.. 5 Earth Resistivity Measurement...

More information

MEGGER DET2/2 Digital Earth Tester

MEGGER DET2/2 Digital Earth Tester MEGGER DET2/2 Digital Earth Tester User Guide MEGGER MeterCenter +1 480 659 8351 or (800) 230-6008 SAFETY WARNINGS Special precautions are necessary when live earths may be encountered, and isolation switches

More information

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING 1 PRACTICAL PROBLEMS WITH SUBSTATION EARTHING Dr Hendri Geldenhuys Craig Clark Eskom Distribution Technology This paper considers the issues around substation sites where the soil resistivity is of particularly

More information

THE EFFECTS OF INCREASED FAULT CURRENT ON THE EXISTING SUBSTATION GROUNDING SYSTEM a Case Study

THE EFFECTS OF INCREASED FAULT CURRENT ON THE EXISTING SUBSTATION GROUNDING SYSTEM a Case Study THE EFFECTS OF INCREASED FAULT CURRENT ON THE EXISTING SUBSTATION GROUNDING SYSTEM a Case Study Research Project By MOHAU MAPANE 689839 Submitted for the partial fulfilment of the requirements for the

More information

UNDERSTANDING. Ground Resistance Testing. I Voltmeter (E) Grounding. electrode. under test. Ground rod and clamp

UNDERSTANDING. Ground Resistance Testing. I Voltmeter (E) Grounding. electrode. under test. Ground rod and clamp UNDERSTANDING Ground Resistance Testing Current supply E Ammeter (I) I Voltmeter (E) Grounding electrode under test X Auxiliary potential electrode Y Auxiliary current electrode Z R Rx R1 R2 Rn-1 Rn EARTH

More information

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING Y. Rajotte J. Fortin G. Lessard Hydro-Québec, Canada Hydro-Québec, Canada Hydro-Québec, Canada e-mails: rajotte.yves@ireq.ca fortin.jacques@ireq.ca

More information

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 10), Cairo University, Egypt, December 19-21, 2010, Paper ID 111. Parameters Affecting the Back Flashover across the

More information

Instruction Manual for Digital Grounding Resistance Meter. Table of Contents

Instruction Manual for Digital Grounding Resistance Meter. Table of Contents I. Overview...2 II. Open-case Inspection...3 III. Safety Precautions...4 IV. Work Principle...7 V. Appearance Description...9 VI. Technical Characteristics 10 VII. Resistance Measurement Method..12 VIII.Battery

More information

GROUND RESISTANCE TESTERS

GROUND RESISTANCE TESTERS GROUND RESISTANCE TESTERS For all of your Ground Integrity Testing needs... An array of Ground Resistance Testers to choose from... Whether you are doing a simplified 2-Point, a more complete - or 4-Point

More information

Digital Ground Resistance Tester. Model 4610 & 4610 Kits

Digital Ground Resistance Tester. Model 4610 & 4610 Kits Digital Ground Resistance Tester Model 4610 & 4610 Kits Model 4610 shown in standard soft carrying case Catalog #2114.94 Digital Ground Resistance Tester Model 4610 performs ground resistance and soil

More information

MODEL 3620 GROUND RESISTANCE TESTER. User Manual. Shop for AEMC products online at: Press To Measure C1 P2 C2

MODEL 3620 GROUND RESISTANCE TESTER. User Manual. Shop for AEMC products online at: Press To Measure C1 P2 C2 GROUND RESISTANCE TESTER 3620 X C1 P2 C2 Y Z GROUND RESISTANCE TESTER MODEL 3620 25 X-Z Fault X-Y Hi Resistance X-Y Hi Noise 0.5 Ω 1k Press To Measure! REFER TO USER MANUAL FOR FAULT WARNING LIGHT EXPLANATIONS

More information

The Potential Gradient of Ground Surface according to Shapes of Mesh Grid Grounding Electrode using Reduced Scale Model

The Potential Gradient of Ground Surface according to Shapes of Mesh Grid Grounding Electrode using Reduced Scale Model Paper The Potential Gradient of Ground Surface according to Shapes of Mesh Grid Grounding Electrode using Reduced Scale Model Chung-Seog Choi Hyang-Kon Kim Hyoung-Jun Gil Woon-Ki Han Ki-Yeon Lee Member

More information

Soil Resistivity Ground Resistance 3-Point Measurements 4-Point Measurements Clamp-On Measurements

Soil Resistivity Ground Resistance 3-Point Measurements 4-Point Measurements Clamp-On Measurements Soil Resistivity Ground Resistance 3-Point Measurements 4-Point Measurements Clamp-On Measurements 200 Foxborough Blvd. Foxborough, MA 02035 (800) 343-1391 (508) 698-2115 FAX (508) 698-2118 sales@aemc.com

More information

Asset Protection Cathodic Protection Soil Resistivity Measurement. Work Instruction No.:

Asset Protection Cathodic Protection Soil Resistivity Measurement. Work Instruction No.: Asset Protection Cathodic Protection Soil Resistivity Measurement Approved by: Manager Pipeline Standards 1 PURPOSE This work instruction describes the processes to be followed when measuring soil resistivity.

More information

Agenda. Earthing of Telecom Installations using Single Point Earthing. Reference Documents. How many earths? Earthing Issue...

Agenda. Earthing of Telecom Installations using Single Point Earthing. Reference Documents. How many earths? Earthing Issue... Earthing of Telecom Installations using Single Point Earthing R. Saji Kumar DGM (IT) O/o The Chief General Manager Trivandrum Agenda Reference Documents Earthing Issue & the Problems Earthing Principle

More information

from ocean to cloud LAND CABLE INTERFERENCE MODEL AND CABLE CROSSINGS WITH POWER INTERCONNECTS

from ocean to cloud LAND CABLE INTERFERENCE MODEL AND CABLE CROSSINGS WITH POWER INTERCONNECTS LAND CABLE INTERFERENCE MODEL AND CABLE CROSSINGS WITH POWER INTERCONNECTS Mr. Ritesh Dass (Cable&Wireless Worldwide) Email: ritesh.dass@cw.com Cable&Wireless Worldwide, 32-43 Chart Street, London, N1

More information

Stake-less earth / ground testing

Stake-less earth / ground testing APPLICATION NOTE Stake-less earth / ground testing NEW DET14C and DET24C CLAMPS GETTING-AROUND ANY CHALLENGE What is stake-less testing? How does it work? Where and how can it be used? What are the potential

More information

DESIGN OF A 45 CIRCUIT DUCT BANK

DESIGN OF A 45 CIRCUIT DUCT BANK DESIGN OF A 45 CIRCUIT DUCT BANK Mark COATES, ERA Technology Ltd, (UK), mark.coates@era.co.uk Liam G O SULLIVAN, EDF Energy Networks, (UK), liam.o sullivan@edfenergy.com ABSTRACT Bankside power station

More information

What Are We Protecting? Over-Voltage Protection for CP Systems. Personnel (primary) Equipment (secondary)

What Are We Protecting? Over-Voltage Protection for CP Systems. Personnel (primary) Equipment (secondary) What Are We Protecting? Personnel (primary) Equipment (secondary) Over-Voltage Protection for CP Systems Personnel Protection: Touch Potential Personnel Protection: Step Potential Equipment Protection

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

PIPELINE CORROSION RISKS ASSOCIATED WITH AC VOLTAGES

PIPELINE CORROSION RISKS ASSOCIATED WITH AC VOLTAGES Fact File No 1 PIPELINE CORROSION RISKS ASSOCIATED WITH AC VOLTAGES Cathodic Protection Co Ltd INTRODUCTION This document discusses corrosion that is believed to be caused by AC current flowing from (i.e.

More information

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit Current will always try to return to its source In order for there to be current, there must be a complete circuit Current will take as many paths or circuits available to it to return to the source The

More information

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Analysis of lightning performance of 132KV transmission line by application of surge arresters Analysis of lightning performance of 132KV transmission line by application of surge arresters S. Mohajer yami *, A. Shayegani akmal, A.Mohseni, A.Majzoobi High Voltage Institute,Tehran University,Iran

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM Technical Specification of Back Clamp for LT Cross Arm (MS) Back clamp for LT Cross Arm made out of 50 x 6mm MS Flat suitable for 8m X 300 Kg PSC poles. After fabrication the cross arm shall be painted

More information

IEC Standard Caledonian Offshore & Marine Cables

IEC Standard Caledonian Offshore & Marine Cables Power Copper s According to IEC 60228 Tinned conductors Cross section cl.2 cl.5 Cross section cl.2 cl.5 mm² Ohm/km Ohm/km mm² Ohm/km Ohm/km 1.0 18.2 20 70 0.270 0.277 1.5 12.2 13.7 95 0.195 0.210 2.5 7.56

More information

Assessment of Step and Touch Voltages for Different Multilayer Soil Models of Complex Grounding Grid

Assessment of Step and Touch Voltages for Different Multilayer Soil Models of Complex Grounding Grid International Journal of Electrical and Computer Engineering (IJECE) Vol. 6, No. 4, August 016, pp. 1441~1455 ISSN: 088-8708, DOI: 10.11591/ijece.v6i4.10637 1441 Assessment of Step and Touch Voltages for

More information

The Variable Threshold Neutral Isolator (VTNI)

The Variable Threshold Neutral Isolator (VTNI) The Variable Threshold Isolator (VTNI) Installation Instructions INTRODUCTION The is designed specifically for installation between the primary neutral of a power utility distribution system and the secondary

More information

Grounding and Lightning arrestors

Grounding and Lightning arrestors CHAPTER - Four Grounding and Lightning arrestors 4.1. Introduction Electrical connection of neutral point of a supply system or the non current carrying part of electrical equipments to the general mass

More information

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4 SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: 16.10 Document Number: KUCSH0039 Rev: 4 16.10.1 INTRODUCTION 16.10.1.1 The intent of this standard is to ensure that continuity

More information

A New Technology. for Measuring Overhead Line and Cable Impedance Values and the Ground Impedance of Large Substations. Feature

A New Technology. for Measuring Overhead Line and Cable Impedance Values and the Ground Impedance of Large Substations. Feature Feature A New Technology for Measuring Overhead Line and Cable Impedance Values and the Ground Impedance of Large Substations Introduction The knowledge of overhead line and cable impedances is very important

More information

Keywords: Absolute potential, grounding system software, ETAP , Ground potential rise (GPR), Step and Touch Potentials

Keywords: Absolute potential, grounding system software, ETAP , Ground potential rise (GPR), Step and Touch Potentials ISSN XXXX XXXX 2018 IJESC Research Article Volume 8 Issue No.4 Design of Grounding System at 150 kv Krapyak Substation by Grounding System Software Omar Abouzeid 1, Abdul Syakur 2, Hermawan 3 Department

More information

Analysis of the Electromagnetic Interferences between Overhead Power Lines and Buried Pipelines

Analysis of the Electromagnetic Interferences between Overhead Power Lines and Buried Pipelines Mediterranean Journal of Modeling and Simulation MJMS 1 (214) 13 23 Analysis of the Electromagnetic Interferences between Overhead Power Lines and Buried Pipelines M hamed Ouadah a*, Mourad Zergoug b a

More information

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual. Manual Title: 5502E Getting Started Supplement Issue: 3 Part Number: 4155211 Issue Date: 9/18 Print Date: November 2012 Page Count: 12 Revision/Date: This supplement contains information necessary to ensure

More information

EPR Safety Mat Modelling & Field Testing Summary Report

EPR Safety Mat Modelling & Field Testing Summary Report EPR Safety Mat Modelling & Field Testing Summary Report 15 April 2014 1. Purpose This document present a summary of the calculations and field testing used to prove the efficacy of the new EPR Safety Mat

More information

Outdoor Installation 2: Lightning Protection and Grounding

Outdoor Installation 2: Lightning Protection and Grounding Outdoor Installation 2: Lightning Protection and Grounding Training materials for wireless trainers This one hour talk covers lightning protection, grounding techniques and problems, and electrolytic incompatibility.

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

Tools of Algebra. Chapter 1:

Tools of Algebra. Chapter 1: Chapter 1: Tools of Algebra Using algebraic formulas requires skill with all types of numbers (negatives, fractions and decimals), an understanding of measurements for lengths and angles, familiarity with

More information

Units 1,2,3,9,12 Delmars Standard Textbook of Electricity

Units 1,2,3,9,12 Delmars Standard Textbook of Electricity Units 1,2,3,9,12 Delmars Standard Textbook of Electricity 1. What are the two basic types of electric sources? 2. What is the effect of unlike charges on each other? 3. What is the effect of like charges

More information

ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment)

ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment) ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment) 1. In an A.C. circuit A ; the current leads the voltage by 30 0 and in circuit B, the current lags behind the voltage by 30 0. What is the

More information

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING J. Ma and F. P. Dawalibi Safe Engineering Services & technologies ltd. 1544 Viel, Montreal, Quebec, Canada, H3M 1G4 Tel.:

More information

ECDA to assess possibility of AC Corrosion. Mark Yunovich Honeywell Corrosion Solutions January 27 th, 2009

ECDA to assess possibility of AC Corrosion. Mark Yunovich Honeywell Corrosion Solutions January 27 th, 2009 ECDA to assess possibility of AC Corrosion Mark Yunovich Honeywell Corrosion Solutions January 27 th, 2009 What are we talking about today? Assessing the degree of AC interference at the pipeline level

More information

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual. Manual Title: 550A Getting Started Supplement Issue: Part Number: 415509 Issue Date: 9/18 Print Date: November 01 Page Count: 19 Revision/Date: This supplement contains information necessary to ensure

More information

Comparison of a Southern Avionics Diamond Portable Antenna with a New Design Proposed by Nautel

Comparison of a Southern Avionics Diamond Portable Antenna with a New Design Proposed by Nautel Comparison of a Southern Avionics Diamond Portable Antenna with a New Design Proposed by Nautel John Pinks Chief Engineer Emeritus January 2004 Nautel Limited 10089 Peggy's Cove Road, Hackett's Cove, NS,

More information

DIGITAL RESISTANCE METER

DIGITAL RESISTANCE METER 1 P a g e M A N 1 7 0 MILLER 400D DIGITAL RESISTANCE METER USER S MANUAL Revised May 19, 2014 2 P a g e M A N 1 7 0 CONTENTS Page Section 1: Description 3 Section 2: How to Take Resistance Readings Manually

More information

ELECTRIC CURRENT VERY SHORT ANSWER QUESTIONS

ELECTRIC CURRENT VERY SHORT ANSWER QUESTIONS ELECTRIC CURRENT VERY SHORT ANSWER QUESTIONS 1. Give the equivalent of V A -1. 2. Ten identical wires, each having a resistance of one ohm, are joined in parallel. What is the equivalent resistance of

More information

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES Jinxi Ma and Farid P. Dawalibi Safe Engineering Services & technologies ltd. 1544 Viel, Montreal, Quebec, Canada, H3M 1G4 Tel.: (514) 336-2511

More information

Generation of Sub-nanosecond Pulses

Generation of Sub-nanosecond Pulses Chapter - 6 Generation of Sub-nanosecond Pulses 6.1 Introduction principle of peaking circuit In certain applications like high power microwaves (HPM), pulsed laser drivers, etc., very fast rise times

More information

QUANTITY SURVEYS. Introduction

QUANTITY SURVEYS. Introduction QUANTITY SURVEYS Introduction In engineering surveying, we often consider a route (road, sewer pipeline, channel, etc.) from three distinct perspectives. The plan view of route location is the same as

More information

South Pasadena A.P. Physics Chapter Electric Current & DC Circuits Date / / Period Electricity Practice Test

South Pasadena A.P. Physics Chapter Electric Current & DC Circuits Date / / Period Electricity Practice Test South Pasadena A.P. Physics Name Chapter 18-19 Electric Current & DC Circuits Date / / Period 1 2 3 4 Electricity Practice Test Electric Current I = Q/t 1. A charge of 30 Coulombs passes through a 24-ohm

More information

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object U. S. Gudmundsdottir, C. F. Mieritz Abstract-- When a lightning discharge strikes a tall object, the lightning current

More information

Company Directive STANDARD TECHNIQUE: TP21D/2. 11kV, 6.6kV and LV Earthing

Company Directive STANDARD TECHNIQUE: TP21D/2. 11kV, 6.6kV and LV Earthing Company Directive STANDARD TECHNIQUE: TP21D/2 11kV, 6.6kV and LV Earthing Policy Summary This document specifies requirements for earthing 11kV and 6.6kV and LV equipment and systems. NOTE: The current

More information

Eaton s Cooper Power Series DEADFRONT ARRESTERS

Eaton s Cooper Power Series DEADFRONT ARRESTERS File Ref: 235-65, 235-68, 235-97, 235-101 Effective June 2015 CT235001EN Supersedes CP9314 May 2011 CERTIFIED TEST REPORT Eaton s Cooper Power Series DEADFRONT ARRESTERS CT235001EN Supersedes CP9314 May

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard NSW Category Electrical Title Reference Number PDS 05 (RIC Standard: EP 12 10 00 11 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

DIGITAL GROUND RESISTANCE TESTERS

DIGITAL GROUND RESISTANCE TESTERS DIGITAL GROUND RESISTANCE TESTERS 3640 4610 X Y Z C1 P2 C2 GROUND RESISTANCE TESTER MODEL 3640 Press To Measure! X-Z Fault Xv-Y Hi Resistance Xv-Y Hi Noise REFER TO USER MANUAL FOR FAULT WARNING LIGHT

More information

Power System Protection Where Are We Today?

Power System Protection Where Are We Today? 1 Power System Protection Where Are We Today? Meliha B. Selak Power System Protection & Control IEEE PES Distinguished Lecturer Program Preceding IEEE PES Vice President for Chapters melihas@ieee.org PES

More information

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design IEEE PES Transmission and Distribution Conference 2008 Panel Session Large Wind Plant Collector Design Wind Farm Collector System Grounding by Steven W. Saylors, P.E. Chief Electrical Engineer Vestas Americas

More information

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published

More information

High Voltage Earthing System Testing : An Investigation into The Effects of Test Lead Coupling on Test Results

High Voltage Earthing System Testing : An Investigation into The Effects of Test Lead Coupling on Test Results i University of Southern Queensland Faculty of Engineering and Surveying High Voltage Earthing System Testing : An Investigation into The Effects of Test Lead Coupling on Test Results A dissertation submitted

More information

Power Sensors Ltd. PQube 3 AC Analyzer IEC Class 0,2 S Accuracy Compliance Report

Power Sensors Ltd. PQube 3 AC Analyzer IEC Class 0,2 S Accuracy Compliance Report PSL Standards Lab 980 Atlantic Avenue Alameda, CA 94501 USA TEL ++1-510-522-4400 FAX ++1-510-522-4455 www.standards.com Sensors Ltd. PQube 3 AC Analyzer IEC Class 0,2 S Accuracy Compliance Report IEC 62053-22

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV

More information

PERFORMANCE ASSESSMENT OF SUBSTATION SITE EARTHING USING FLUKE 1625 GROUND TESTER

PERFORMANCE ASSESSMENT OF SUBSTATION SITE EARTHING USING FLUKE 1625 GROUND TESTER Nigerian Journal of Technology (NIJOTECH) Vol. 32, No. 1, March, 2013, pp. 49 53. Copyright 2013 Faculty of Engineering, University of Nigeria. ISSN 1115-8443 PERFORMANCE ASSESSMENT OF SUBSTATION SITE

More information

kg per litre

kg per litre AS Physics - Experiment Questions for Unit 2 1. Explain what is meant by the term polarisation when referring to light............. Sugar is produced from plants such as sugar cane. The stems are crushed

More information

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14)

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14) Advances in UHV Transmission and Distribution Prof. B Subba Reddy Department of High Voltage Engg (Electrical Engineering) Indian Institute of Science, Bangalore Lecture 36 Measurements of High Voltages

More information

Grounding for Power Quality

Grounding for Power Quality Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states

More information

Earth Grounding Resistance

Earth Grounding Resistance Earth Grounding Resistance Principles, testing methods and applications DIAGSE intermittent electrical problems AVOID unnecessary downtime LEARN earth ground safety principles Why ground, why test? Why

More information

13-3The The Unit Unit Circle

13-3The The Unit Unit Circle 13-3The The Unit Unit Circle Warm Up Lesson Presentation Lesson Quiz 2 Warm Up Find the measure of the reference angle for each given angle. 1. 120 60 2. 225 45 3. 150 30 4. 315 45 Find the exact value

More information

American Electrical Institute

American Electrical Institute American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article

More information