Power Quality in a 110 kv DSO System Measured by Means of Non- Conventional Instrument Transformers

Size: px
Start display at page:

Download "Power Quality in a 110 kv DSO System Measured by Means of Non- Conventional Instrument Transformers"

Transcription

1 Presentation 06.1 Power Quality in a 110 kv DSO System Measured by Means of Non- Conventional Instrument Transformers Dr. Philipp Werdelmann / Christoph German, Westnetz, Germany Abstract This paper presents power quality measurements within a 110 kv substation of WESTNETZ GmbH, Germany. Measurements are performed by making use of an RC voltage divider and a broadband acquisition unit. The intention is to find out the characteristics of both, steady state variations as well as transient disturbances. The obtained measurement results are evaluated and the possible impact on grid operability and the influence on equipment stress are discussed subsequently. 1 Introduction and Motivation Providing a high power quality is becoming more important concerning all stakeholders of energy grids, i.e. consumers, generators and of course operators. The term itself is often characterized by the quality of voltage supply being influenced by different kinds of disturbances or distortion. The analysis of Power Quality is often focused on most in LV and MV grids but only partially in HV grids which is certainly due to the different system impedance and the smaller amount of non-sinusoidal infeeders or consumers which are directly connected to the HV grid. However, this reason may change as the development of modern energy grids provides more decentralized and even more volatile generation of power, e.g. from renewable sources, as well within 110 kv distribution systems. Other effects which are due to more dynamic phenomena like control reaction, fault incidents or operational actions deliver additional impacts on Power Quality as well. 1.1 Today Transition in Distribution Grids and Future Challenges The present transition of energy grids in Germany leads to more decentralized generation with more volatile feed-in. Thus, a bidirectional power flow is challenging the grid infrastructure, which was intentionally planned and designed for a top-down, unidirectional power flow decades ago (Figure 1:). Especially for the distribution grids there are a lot of challenges the operators in Germany have to deal with today as well as in the future. On the one hand, the short-circuit capacity is getting lower as large rotating generators leave market, which again leads to a decrease in robustness and in system flexibility. On the other hand, more dynamic reaction is needed to operate the grid in a stable mode. Figure 1: Today s Development of Energy Grids Leads to Decentralization and Bidirectional Power Flow 1.2 Impacts on Power Quality and Infrastructure Reliability The different kinds of power quality variations can be classified into the following categories [1]: Steady State Variations Transient Disturbances Steady Sate Variations describe harmonic distortion and normal RMS voltage variations and are often evaluated on a larger time basis within days or weeks. Disturbances cover transient phenomena like surge or burst impulses. Transient disturbances can be the consequence of switching events, electric faults or induction phenomena like lightning strikes. These kinds of disturbances are usually detected by triggering on specific criteria, e.g. exceeding a voltage or rate-of-change threshold. Short-time deviations from nominal or rated values do also fall into this category [2]. The intention for investigating Power Quality in this case was to find out about: The level of harmonic distortion on 110 kv Voltage stability and level of unbalance Frequency deviations Criticality of transient effects Possible stress for equipment Any correlation of these effects, if applicable Steady state variations, e.g. harmonic distortion, are able to stress critical equipment like transformers due to increased dissipation losses (eddy currents, saturation effects, etc ). Another impact regarding

2 Presentation 06.2 unbalance and THD can be an overload of the neutral phase. Besides this, transient disturbances bear the risk of spontaneous and unplanned outages due to sudden equipment damage. Effects of damage caused by repetitive transients may also be a reason for advanced ageing and reduction in lifetime. 1.3 Standards and Guidelines In general, Power Quality aspects are described in the international standard IEC Electromagnetic Compatibility (EMC). In this class, specifically IEC holds guidelines and information about power quality measurement methods [3]. For this work, measurement techniques have been chosen according to the mentioned standard. Concerning limits and maximum values for power quality assessment the standard IEC addresses this topic, however, this standard is limited to LV and MV only. The European Standard EN defines characteristics for the usually expected variations and gives reference values which help to assess the detected Power Quality deviations [4]. Furthermore, for HV systems there are Technical Rules for the Assessment of Network Disturbances, which define requirements for consumers and generators connected to the HV network [5]. 2 Measuring System and Setup In order to obtain measurement results which are representative for a specific state of grid operation the location for installing the measurement equipment should be of specific characteristic as well. This could be either a substation located nearby urban areas with high power consumption and distinctive load curves or a more rurally oriented substation location with high amount of volatile power feed-in. In this work, the latter option was taken, which is to be followed by the first one in near future. Measurements were taken during a period of three month beginning in July Substation Location For performing measurements in a rural but windy location the 110 kv substation Büren within the WESTNETZ operated area was chosen (see Figure 2:). In this area there are several wind parks connected directly to 110 kv and 30 kv lines. Figure 2: 110 kv Substation Büren is Operated by WESTNETZ (Blue Area) in the West of Germany 2.2 Equipment and Methodology For 110 kv measurements WESTNETZ mostly operates inductive instrument transformers. These transformers are designed for 50 Hz applications without the need for providing signals in a much wider frequency range. Therefore, for detecting higher harmonics as well as transients a voltage transformer design was needed which shows higher cut-off frequencies [6] [7]. A Pfiffner RC-divider was chosen providing highest accuracy with a maximum amplitude error of 0.2% up to 10 khz. A comparable design has already been used for PQ measurements in higher voltage levels [8]. These devices were mounted in a spare line field within substation Büren (see Figure 3:). The secondary output signals are picked up by a power quality analyzer ( PQBox200, a.eberle) with a sampling rate of 40 khz. The PQBox allows different options for signal data acquisition like oscilloscope, transient recorder and RMS monitor functions. By software parametrization the trigger and threshold values were adjusted during commissioning on site. Measurements are performed during a period of three months: The data acquisition unit continuously captures 10ms RMS values and is triggered by transient events to record the respective data. This storage is read out approximately every 2 weeks and post-processing of the raw data is done via MATLAB. Additionally, data from the grid control system was obtained and incorporated into evaluation, e.g. wind power measurements or grid operation protocols.

3 Presentation 06.3 (higher average value and less deviation) as well as by a lower voltage unbalance in total. It is more difficult to assess the THD values given in the mentioned interval, as not only feed-in of wind power might have a significant influence (due to harmonics caused by inverter units) but also the load characteristics of consumers. The THD value does not allow to separate this from one another clearly. However, the measured THD value is dominated by the 5 th and 7 th harmonic, which can be partially explained by inverter units of wind, photovoltaic or loads. The harmonic distortion has been measured up to the 50 th harmonic, which is presented in Figure 5:. Limit values as given in [4] are 5% for the 5 th and 4% for the 7 th order harmonic. Figure 3: RC Divider (Pfiffner ROF 123) Mounted in a 110 kv Substation for PQ Measurements 3 Measurement Results and Evaluation 3.1 Steady State Variations According to [4], a 7-day-intervall was evaluated and depicted in Figure 4: for RMS values of voltage, unbalance, frequency and THD. As the region around Büren is dominated by wind power generation, the average sum for the nearby wind park power feed-in is given isochronally. Figure 5: 24h Harmonic Distortion Measured in 110 kv Substation Büren on Out of this 7-day period, the (Saturday) is of specific interest, because the load is quite low on this weekend. Furthermore, there was much wind power available at this particular day. Figure 6: gives the 24-h data concerning the mentioned parameters for this day. Figure 4: 7d-Recordings of Voltage, Unbalance, Frequency, THD and Active Wind Power on Figure 4 illustrates, that all the measured values are far below the maximum allowable limits. The maximum average value of the voltage (117 kv) is found approximately 6% higher than the nominal voltage. This value was reached on a Sunday morning (very low electricity demand), as there was also heavy wind presence in that region. This effect is also reflected by the frequency Figure 6: 24h-Recordings of Voltage, Unbalance, Frequency, THD and Active Wind Power on (Sat.)

4 Presentation 06.4 On this day, wind power in total but also regarding the rate of change played a major role. Nevertheless, the Power Quality in the 110 kv distribution system was still in very good condition. On Wednesday, , (see Figure 7:) there was much more electricity demand pointed out by both, the voltage as well as the THD value in the beginning of working time that day (between 05:00 and 09:00 a.m.): voltage drops approximately by 3...4% until voltage regulation actions are activated (stepping of HV transformer OLTC) and total harmonic distortion consistently rises but is still far away from reaching limit values. As THD value decreases again during the afternoon hours, although wind power reaches its maximum in this time. This is shown with load deviations in this region, which have a stronger influence on Power Quality than with inverter operated generating units. qualitatively higher at the voltage zero crossing than at the voltage peak. Thus, if circuit breaker switching would have happened in the voltage maximum, the resulting overvoltage would have been smaller in this example event. Figure 8: Oscilloscope Recording of Circuit Breaker Switching on Another typical and spontaneous phenomena are earth faults. Figure 9: illustrates an oscilloscope recording of a self-extinguishing earth fault with a duration of approximately 20 ms which was initiated on phase L1. The transient consequence of this event was a relative voltage peak of ca. 50 kv on phase L3 as the star-point is shifted. Figure 7: 24h-Recordings of Voltage, Frequency, THD and Active Wind Power on (Wednesday) 3.2 Transient Disturbances During the measurement period there were some transient events triggered by the acquisition unit. Most often these were switching events followed by earth and line faults. Depending on attenuation effects due to distance, impedance and grid status the resulting overvoltage appears in different intensity. Sudden cut-off of inductive currents will additionally result in steep voltage impulses. As an example, Figure 8: shows the triggered voltage recording of a circuit breaker opening event detected in substation Büren. The relative voltage peak on phase L2 is about 45 kv and higher compared to L1 and L3. This voltage, of course, is depending on the inductive component of the current which is Figure 9: Oscilloscope Recording of a Transient Earth Fault Event on A very interesting incident event happened on , when a sustaining earth fault occurred on phase L3 (see Figure 10:). This fault developed to a line-to-line fault between L2 and L3 after 1 second, until 150 ms later a successful automatic reclose cleared the fault event.

5 Presentation 06.5 However, higher electric field stress will cause additional ageing to the devices and the dielectric system which is depending on different parameters, e.g. rate-of-change (du/dt) and duration. The presented work will be carried on in additional substations and regions covering different characteristics like load profiles, urban structures etc. to widen the basis of information about power quality in 110 kv distribution grids and possible impacts on equipment stress and grid planning strategies. Literature [1] Melhorn, Christopher; McGranaghan, Mark: Interpretation and Analysis of Power Quality Measurements; Elektrotek Concepts, Inc.; Knoxville, Tennesee Figure 10: Oscilloscope Recording of Sustaining Earth Fault Turning into a Line-to-Line Short Circuit before Being Successfully Reclosed Again, the earth fault caused a star-point shifting leading to a phase-to-neutral voltage rise of 3 on the healthy phases L1 and L2. The line-to-line fault was detected by the protection relay and a successful reclose could be performed in order to clear the fault. 4 Conclusions and Outlook In general, steady state as well as transient disturbances have the ability to cause damage to electrical equipment including, generators, operators and consumers. The performed measurements were able to show, that harmonic distortion is no crucial issue within the 110 kv system which was subject to investigation. There are trends to be seen in indirect correlation between electricity demand and derivations in frequency, unbalance and THD. Transients disturbances show significant voltage peaks which, however, is not unusual for normal grid operation, as fault events or switching are part of everyday grid operation. The question is, if the need for performing switching actions more often might increase in the future. HV equipment in substations has to be designed and tested for fault events, providing that protection relays will prevent serious damage due to overcurrent for example. Electric stress resulting from occurring higher voltages as shown in this work is surely within the limits of what type and routine tests do have to cover. [2] CIRED: Special Report Session 2: Power Quality and Electromagnetic Compatibility; 23 rd International Conference on Electricity Distribution; Lyon; June 2015 [3] DIN EN Elektromagnetische Verträglichkeit (EMV), Teil 4-30: Prüf- und Messverfahren Verfahren zur Messung der Spannungsqualität, Sept [4] DIN EN Merkmale der Spannung in öffentlichen Elektrizitätsversorgungsnetzen, Feb [5] Forum Netztechnik/Netzbetrieb im VDE (FNN): Technische Regeln zur Beurteilung von Netzrückwirkungen Ergänzungsdokument zur Beurteilung von Anlagen für den Anschluss an Hochspannungsverteilernetze.; 1st Ed [6] EURAMET: Publishable JRP Summary Report for ENG61 FutureGrid: Non-Conventional voltage and current sensors for future power grids; June 2015 [7] Meyer, J.; Stiegeler, R.; Klatt, M.; Elst, M.; Sperling, E.: Accuracy of Harmonic Voltage Measurements in the Frquency Range up to 5 khz using Conventional Instrument Transformers; 21 st International Conference on Electricity Distribution; Frankfurt; 6-9 June 2011 [8] Sperling, Erik; Schegner, Peter: A Possibility to Measure Power Quality with RC-Divider; 22 nd International Conference on Electricity Distribution; Stockholm; June 2013

6 Presentation 06.6 About the Authors Dr. Philipp Werdelmann received his electrical engineering diploma at Technical University Dortmund in After this he gained experience at the chair of High Voltage Engineering and EMC as research assistant until he finished his PhD in In that year he started working for RWE in the field of Power Plant Planning & Approval as project manager and technical expert for generators, transformers and electrical drives in Germany, UK, NL and Eastern Europe. In 2013 he joined WESTNETZ GmbH, RWE s distribution system operator in Germany. He now is responsible as team leader for HV equipment, product management, electrical and structural engineering and technical specification of substation design within the HV Substation Technology department. Christoph German received his electrical engineering diploma at Technische Fachhochschule Bochum in In that year he started working for RWE in Germany in the field of distribution and transmission grids as technical expert for disconnectors and surge arresters in 110 kv substations. He now is the technical product manager for current and voltage instrument transformers in RWE s distribution system operator Westnetz GmbH in Germany. The product management contains the whole lifecycle of the equipment including the technical specification, pre-qualification of suppliers, acceptance test, operation and disposal.

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering

More information

MEASUREMENT OF VOLTAGE INSTABILITIES CAUSED BY INVERTERS IN WEAK GRIDS

MEASUREMENT OF VOLTAGE INSTABILITIES CAUSED BY INVERTERS IN WEAK GRIDS MEASUREMENT OF VOLTAGE INSTABILITIES CAUSED BY INVERTERS IN WEAK GRIDS Michael Höckel Andreas Gut Michel Arnal BFH Switzerland BFH Switzerland BKW Switzerland michael.hoekel@bfh.ch andreas.gut@bfh.ch michel.arnal@bkw.ch

More information

Power Quality Measurements the Importance of Traceable Calibration

Power Quality Measurements the Importance of Traceable Calibration Power Quality Measurements the Importance of Traceable Calibration H.E. van den Brom and D. Hoogenboom VSL Dutch Metrology Institute, Delft, the Netherlands, hvdbrom@vsl.nl Summary: Standardization has

More information

UNIT-4 POWER QUALITY MONITORING

UNIT-4 POWER QUALITY MONITORING UNIT-4 POWER QUALITY MONITORING Terms and Definitions Spectrum analyzer Swept heterodyne technique FFT (or) digital technique tracking generator harmonic analyzer An instrument used for the analysis and

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO Krasimir Marinov Ivanov, Technical University of Gabrovo, Gabrovo, BULGARIA Georgi Tsonev

More information

1. Introduction to Power Quality

1. Introduction to Power Quality 1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and

More information

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks GB Technical data Issue 06/2009 PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks Fault detection Evaluation of voltage quality according to EN50160 and IEC61000-2-2 Fault recorder

More information

Recommendations for Harmonic and Power Measurements in Electrical Networks

Recommendations for Harmonic and Power Measurements in Electrical Networks Recommendations for Harmonic and Power Measurements in Electrical Networks Analysis implementation and reporting requirements regarding grid power quality and equipment loads Power Capacitor Division Recommendations

More information

Power quality report. A Manufacturing Plant

Power quality report. A Manufacturing Plant Power quality report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION... 5 2.1 SITE MONITORED...

More information

Some European experiences with renewable installations

Some European experiences with renewable installations Some European experiences with renewable Waveform distortion Ana Maria Blanco, Jan Meyer, Sascha Müller, Anantaram Varatharajan 08.08.2017 Content 1. Introduction 2. Distributed PV inverters (

More information

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION 23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB

More information

ISLANDED OPERATION OF MODULAR GRIDS

ISLANDED OPERATION OF MODULAR GRIDS ISLANDED OPERATION OF MODULAR RIDS Tobias SCHNELLE Adolf SCHWEER Peter SCHENER Mitteldeutsche Netzgesellschaft Mitteldeutsche Netzgesellschaft Technische Universität Strom mbh - ermany Strom mbh - ermany

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Power Quality under the microscope

Power Quality under the microscope We take care of it. Power Quality Power Quality under the microscope Change in the producer and consumer structure The change in the producer and consumer structure of the Central European power grids

More information

Power Quality in Metering

Power Quality in Metering Power Quality in Metering Ming T. Cheng Directory of Asian Operations 10737 Lexington Drive Knoxville, TN 37932 Phone: (865) 218.5885 PQsynergy2012 www.powermetrix.com Focus of this Presentation How power

More information

Technical Brief: Flow Direction of Harmonics and High- order Harmonics

Technical Brief: Flow Direction of Harmonics and High- order Harmonics Technical Brief: Harmonics Harmonics are generated by semi- conductor controlled devices in the power supply of equipment as a result of distorted voltage and current waveforms. When the harmonic component

More information

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point 2010 MAP Range HV / MV / LV electrical network quality analyzers Class A > Network quality Analyzers PRODUCT ADVANTAGES COMPLIANT with the EN 61000-4-30 standard, Class A DETECTION of the fault LOCATION

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Power Quality Report. A Manufacturing Plant

Power Quality Report. A Manufacturing Plant Power Quality Report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant CHK Power Quality Pty Ltd Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION...

More information

Capacitor protection relay

Capacitor protection relay Capacitor Protection Relay FEATURES Capacitor unbalance protection Line current unbalance protection Overvoltage protection Overheating protection Ground fault protection Overcurrent protection Undercurrent

More information

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Fernando Bastião and Humberto Jorge Department of Electrical Engineering and Computers

More information

Sources of transient electromagnetic disturbance in medium voltage switchgear

Sources of transient electromagnetic disturbance in medium voltage switchgear Sources of transient electromagnetic disturbance in medium voltage switchgear Dennis Burger, Stefan Tenbohlen, Wolfgang Köhler University of Stuttgart Stuttgart, Germany dennis.burger@ieh.uni-stuttgart.de

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

Grid Converters for Photovoltaic

Grid Converters for Photovoltaic Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements

More information

Investigation of data reporting techniques and analysis of continuous power quality data in the Vector distribution network

Investigation of data reporting techniques and analysis of continuous power quality data in the Vector distribution network University of Wollongong Research Online University of Wollongong Thesis Collection 1954-2016 University of Wollongong Thesis Collections 2006 Investigation of data reporting techniques and analysis of

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 9 POWER QUALITY Power quality (PQ) problem = any problem that causes

More information

Modeling insulation in high-voltage substations

Modeling insulation in high-voltage substations 38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other

More information

Power Quality - 1. Introduction to Power Quality. Content. Course. Ljubljana, Slovenia 2013/14. Prof. dr. Igor Papič

Power Quality - 1. Introduction to Power Quality. Content. Course. Ljubljana, Slovenia 2013/14. Prof. dr. Igor Papič Course Power Quality - 1 Ljubljana, Slovenia 2013/14 Prof. dr. Igor Papič igor.papic@fe.uni-lj.si Introduction to Power Quality Content Session 1 Session 2 Session 3 Session 4 1st day 2nd day 3rd day 4th

More information

Non-conventional instrument transformers and power quality aspects an overview

Non-conventional instrument transformers and power quality aspects an overview Representative Meeting / Switzerland June 7 th. 2017 Non-conventional instrument transformers and power quality aspects an overview Erik P. Sperling Presentation overview 1. History 2. Instrument transformer

More information

VOLTAGE DIPS AND SENSITIVITY OF CONSUMERS IN LOW VOLTAGE NETWORKS

VOLTAGE DIPS AND SENSITIVITY OF CONSUMERS IN LOW VOLTAGE NETWORKS VOLTAGE DIPS AND SENSITIVITY OF CONSUMERS IN LOW VOLTAGE NETWORKS Günther Brauner Christian Hennerbichler Vienna University of Technology Vienna University of Technology now: ABB Automation Ltd, Baden,

More information

PQ Monitoring Standards

PQ Monitoring Standards Characterization of Power Quality Events Charles Perry, EPRI Chair, Task Force for PQ Characterization E. R. Randy Collins, Clemson University Chair, Working Group for Monitoring Electric Power Quality

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

Power Quality and Reliablity Centre

Power Quality and Reliablity Centre Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview

More information

Power System Stability. Course Notes PART-1

Power System Stability. Course Notes PART-1 PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed

More information

Emission on the low voltage grid: measurements in an urban area

Emission on the low voltage grid: measurements in an urban area International Conference on Renewable Energies and Power Quality (ICREPQ 4) Cordoba (Spain), 8 th to th April, 4 exçxãtuäx XÇxÜzç tçw céãxü dâtä àç ]ÉâÜÇtÄ (RE&PQJ) ISSN 7-38 X, No., April 4 Emission on

More information

Introduction to Harmonics and Power Quality

Introduction to Harmonics and Power Quality NWEMS Introduction to Harmonics and Power Quality August 20 24, 2018 Seattle, WA Track B Anaisha Jaykumar (SEL) Class Content» Definition of power quality (PQ)» Impact of PQ problems» Sources of poor PQ»

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks. 2CDC 251 048 F0t08 CM-MPS.11 2CDC 251 049 F0t08 CM-MPS.21 2CDC 251 050 F0t08 CM-MPS.31 2CDC 251 051 F0t08 CM-MPS.41 R/T: yellow LED - relay status, timing F1: red LED - fault message F2: red LED - fault

More information

POWER QUALITY REPORT

POWER QUALITY REPORT Power Quality Research Lab., I-7, Wyb. Wyspiaoskiego 27, 50-370 Wrocław, Poland phone +48713202626, fax +48713202006, email: zbigniew.leonowicz@pwr.wroc.pl Facility: XXX POWER QUALITY REPORT Start Monitoring:

More information

An Introduction to Power Quality

An Introduction to Power Quality 1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger

More information

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg Coupling modes Véronique Beauvois, Ir. 2015-2016 General problem in EMC = a trilogy Parameters Amplitude Spectrum Source (disturbing) propagation Coupling modes Victim (disturbed) lightning electrostatic

More information

Končar TMS - Bushing monitoring

Končar TMS - Bushing monitoring Končar TMS - Bushing monitoring Many recent studies have shown that bushing failure is one of the most common causes of transformer failure. Thus need for bushing diagnostic and monitoring system has risen.

More information

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks. 2CDC 251 054 F0t08 CM-MPN.52 2CDC 251 055 F0t08 CM-MPN.62 2CDC 251 056 F0t08 CM-MPN.72 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017 Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the

More information

VOLTAGE OPTIMIZATION FOR INDUSTRY, TRADE, BUSINESS AND LOCAL NETWORKS

VOLTAGE OPTIMIZATION FOR INDUSTRY, TRADE, BUSINESS AND LOCAL NETWORKS VOLTAGE OPTIMIZATION FOR INDUSTRY, TRADE, BUSINESS AND LOCAL NETWORKS Employing a voltage control system in a low-tension network provides independence from network fluctuations. In addition, energy-using

More information

Sensor Accuracy and Data Management Issues

Sensor Accuracy and Data Management Issues 8/2/21 1 Sensor Accuracy and Data Management Issues Panel on Experiences and System Requirements for Power Quality Data Analytics 1PESGM912 Jan Meyer Robert Stiegler Etienne Gasch Max Domagk Technische

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 BACKGROUND The increased use of non-linear loads and the occurrence of fault on the power system have resulted in deterioration in the quality of power supplied to the customers.

More information

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014

More information

Reliability and Power Quality Indices for Premium Power Contracts

Reliability and Power Quality Indices for Premium Power Contracts Mark McGranaghan Daniel Brooks Electrotek Concepts, Inc. Phone 423-470-9222, Fax 423-470-9223, email markm@electrotek.com 408 North Cedar Bluff Road, Suite 500 Knoxville, Tennessee 37923 Abstract Deregulation

More information

FAULT IDENTIFICATION IN TRANSFORMER WINDING

FAULT IDENTIFICATION IN TRANSFORMER WINDING FAULT IDENTIFICATION IN TRANSFORMER WINDING S.Joshibha Ponmalar 1, S.Kavitha 2 1, 2 Department of Electrical and Electronics Engineering, Saveetha Engineering College, (Anna University), Chennai Abstract

More information

PowerMonitor 5000 Family Advanced Metering Functionality

PowerMonitor 5000 Family Advanced Metering Functionality PowerMonitor 5000 Family Advanced Metering Functionality Steve Lombardi, Rockwell Automation The PowerMonitor 5000 is the new generation of high-end electrical power metering products from Rockwell Automation.

More information

POWER QUALITY MONITORING - PLANT INVESTIGATIONS

POWER QUALITY MONITORING - PLANT INVESTIGATIONS Technical Note No. 5 January 2002 POWER QUALITY MONITORING - PLANT INVESTIGATIONS This Technical Note discusses power quality monitoring, what features are required in a power quality monitor and how it

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 5th October 2010 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

Index. b back-flashover 245 biomass 207 breakers 74 buchholz protection 235 busbar sectionalizer 193 business enterprises 18

Index. b back-flashover 245 biomass 207 breakers 74 buchholz protection 235 busbar sectionalizer 193 business enterprises 18 331 Index a activity plan 318 agricultural enterprise 21 annual increase factor 12 annuity factor 44, 156 annuity method 38 ANSI code numbers 237 arrester, protection level 245 assessment of losses 38

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L. /9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala

More information

Overvoltage Protection of Light Railway Transportation Systems

Overvoltage Protection of Light Railway Transportation Systems Overvoltage Protection of Light Railway Transportation Systems F. Delfino, R. Procopio, Student Member, IEEE, and M. Rossi, Student Member, IEEE Abstract In this paper the behavior of the power supply

More information

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC 2CDC 251 048 F0t08 CM-MPS.11 2CDC 251 049 F0t08 CM-MPS.21 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage as well as phase unbalance

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

Fundamentals of Power Quality

Fundamentals of Power Quality NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION Andreas SUMPER sumper@citcea.upc.es Antoni SUDRIÀ sudria@citcea.upc.es Samuel GALCERAN galceran@citcea.upc.es Joan RULL rull@citcea.upc.es

More information

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Maher G. M. Abdolrasol maher_photo@yahoo.com Dept. of Electrical Engineering University of Malaya Lembah Pantai, 50603

More information

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric

More information

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories 2CDC 251 042 F0t08 CM-PVS.31 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage Threshold values for over- and undervoltage are adjustable

More information

Network Analyzer for Low-, Medium- and High-Voltage Networks

Network Analyzer for Low-, Medium- and High-Voltage Networks Technical data Network nalyzer for Low-, Medium- and High-Voltage Networks Model PQ-Box 100 1 Fault detection 1 Evaluation of voltage quality according to EN50160 and IEC61000-2-2 (2-4) 1 Fault recorder

More information

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC 2CDC 251 244 F0t05 Characteristics Monitoring of DC and AC currents: RMS measuring principle One device includes 3 measuring ranges Over- or undercurrent monitoring configurable Hysteresis adjustable from

More information

Motors and drives. Module B- Introduction to input measurements

Motors and drives. Module B- Introduction to input measurements Motors and drives Module B- Introduction to input measurements Introduction to input measurements There are a number of locations where input measurements may be made Which is the most important location

More information

Electric Power Quality: Voltage Sags Momentary Interruptions

Electric Power Quality: Voltage Sags Momentary Interruptions Slide 1 Electric Power Quality: Voltage Sags Momentary Interruptions Ward Jewell Wichita State University ward.jewell@wichita.edu Slide 2 Power Quality Events Voltage sags Outages/interruptions Voltage

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

NIC Project Medium Voltage Direct Current Link Technical Specification

NIC Project Medium Voltage Direct Current Link Technical Specification 1 SCOPE This Specification details SP Energy Networks (SPEN) requirements for a bidirectional Medium Voltage Direct Current (MVDC) Link for the Angle-DC project, being carried out in conjunction with Ofgem

More information

Harmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients.

Harmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients. Power Quality Standards in India Power Quality is a measure of an ideal power supply system. It can be defined as any power problem manifested in voltage, current and frequency deviations that result in

More information

I -limiter The world s fastest switching device

I -limiter The world s fastest switching device I S -limiter 2 I S -limiter The world s fastest switching device Reduces substation cost Solves short-circuit problems in new substations and substation extensions Optimum solution for interconnection

More information

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Power Quality and Circuit Imbalances 2015 Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Summary of IEEE 1159 Terms Category Types Typical Duration

More information

SIEMOS PQ The Multi-Functional Power Quality Analyzer for Low and Medium-Voltage Networks

SIEMOS PQ The Multi-Functional Power Quality Analyzer for Low and Medium-Voltage Networks www.reinhausen.com SIEMOS PQ The Multi-Functional Power Quality Analyzer for Low and Medium-Voltage Networks SIEMOS PQ the power quality analyzer for every application The SIEMOS PQ three-phase network

More information

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM GIC grid stability and harmonics mitigation

More information

HARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE

HARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE HARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE Ibrahim ABDULHADI Federico COFFELE Power Networks Demonstration Centre - UK ibrahim.f.abdulhadi@strath.ac.uk federico.coffele@strath.ac.uk

More information

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks. 2CDC 251 052 F0t08 CM-MPS.23 2CDC 251 053 F0t08 CM-MPS.43 - relay status, timing - fault message - fault message Adjustment of the tripping delay t V Adjustment of the threshold value for overvoltage 6

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

Three-phase monitoring relays

Three-phase monitoring relays 2CDC 251 046 F0t08 Features Monitoring of three-phase mains for phase sequence, phase failure, phase unbalance Threshold value for phase unbalance adjustable as absolute value Tripping delay can be adjusted

More information

Dynamic MotorAnalyzer

Dynamic MotorAnalyzer Top-Innovator 2014 Online Monitoring of electric motors Made in Germany Expect more. EN Winding testers The Motor monitoring without special know-how The allows the testing of a running motor in its operational

More information

Power Quality Summary

Power Quality Summary Power Quality Summary This article provides an overview of how voltage harmonic distortion is managed on the distribution network and focuses on the current at future issues surround the connection of

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

We take care of it. Special Publication. Power Quality PQ-Box 100/200. Expert opinions: Emergency power supply for hospitals and computer centres.

We take care of it. Special Publication. Power Quality PQ-Box 100/200. Expert opinions: Emergency power supply for hospitals and computer centres. We take care of it. Special Publication Power Quality PQ-Box 100/200 Expert opinions: Emergency power supply for hospitals and computer centres. Power Quality PQ-Box 100/200 Emergency power supply for

More information

Network Analyzer for Low-, Medium- and High-Voltage Networks

Network Analyzer for Low-, Medium- and High-Voltage Networks Technical data Network nalyzer for Low-, Medium- and High-Voltage Networks Model PQ-Box 150 1 Fault detection 1 Evaluation of voltage quality according to EN50160 and IEC61000-2-2 (2-4) 1 FFT nalysis up

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,

More information

Quality of supply regulation in Norway c

Quality of supply regulation in Norway c Quality of supply regulation in Norway c Kjell Sand, Gerd H. Kjølle SINTEF Energy Research Oct. 2005/ Aug. 2006 updated April 2009 SINTEF Energy Research 1 Electrical energy consumption per capita x 1

More information

Protection against unacceptable voltages in railway systems

Protection against unacceptable voltages in railway systems Bernhard Richter*, Alexander Bernhard*, Nick Milutinovic** SUMMERY Based on the system voltages for AC and DC railway systems the required voltage ratings for modern gapless MO surge arresters are given.

More information

Potential Impacts of khz Harmonic Emissions on Smart Grid Communications in the United States

Potential Impacts of khz Harmonic Emissions on Smart Grid Communications in the United States Potential Impacts of 9-150 khz Harmonic Emissions on Smart Grid Communications in the United States Maria Arechavaleta, S. Mark Halpin, Adam Birchfield, Wendy Pittman, W. Eric Griffin, Michael Mitchell

More information