LOCATING MULTIPLE GROUND FAULTS THE BLUE CHIP CASINO IN MICHIGAN CITY, IN

Size: px
Start display at page:

Download "LOCATING MULTIPLE GROUND FAULTS THE BLUE CHIP CASINO IN MICHIGAN CITY, IN"

Transcription

1 LOCATING MULTIPLE GROUND FAULTS THE BLUE CHIP CASINO IN MICHIGAN CITY, IN A SUMMARY REVIEW OF THE FINDINGS AND INVESTIGATIVE TECHNIQUES THAT WERE USED TO RESOLVE THE GROUNDING PROBLEMS Page 1

2 The Blue Chip Casino Indiana law states that a casino operation has to take place on a free floating self propelled pleasure craft. A land based operation as in cities like Las Vegas or Atlantic City is prohibited. Boyd gaming had early on discovered that the law can be used to one s advantage by creating a semi land/water based operation, the so called casino ship. This is however no small undertaking. It requires that a body of water be provided that is capable of supporting a ship with cruiseliner dimensions. Hotel Pleasure Craft The casino is shown on the picture to the right. It illustrates nicely the size of the ship. Amazingly enough, a visitor will enter the hotel and step on board without noticing it. The transition is cleverly made via a floating walkway. To the common observer, hotel and casino have become one unit. Page 2

3 Power is supplied from shore via 4160/480VAC transformers. There are five 480/208/120VAC transformers onboard stepping down the power for further distribution. It is important to note that the secondary side of these transformers is solidly grounded. 4160VAC to 480VAC Shore feed into the pleasure craft A typical /120VAC delta/y 750 kva transformer (marked SP200B) is shown below. A total of four similar transformers provide slot power (SP panels) and lighting power (LP panels) across the ship. From the start, the customer experienced ground fault problems with the electrical distribution system. Certain types of ground faults will cause a current to flow through the ship s and back to the transformer neutral via the grounding electrode conductor. An ammeter type ground fault relay (Manufactured by IPS Systems in Florida) with CT that encircles the grounding electrode conductor measures the current that flows through the ship s. More details will be provided later on in this application note. Worthy of notice were two meters that produced humming noises due to to excessive current flow. 750KVA transformer with open front Five ground fault ammeters Note meter 1 at the top left is pegged Page 3

4 Overview After extensive discussions and a review of the electrical drawings, we came to believe that shipboard power distribution was per the diagram below. The loads such as the slot machines are all from the ship s. Thus, ground faults internal to these devices will not flow through the ship s but must eventually flow LIGHTING/SLOT PANELBOARD SB221 MAIN SWITCHBOARD SP200C SUB-PANELBOARD SP200B L O A D Typical Load Six 150 A circuits 42 circuits isolation LIGHTING/SLOT PANELBOARD SB222 SUB-PANELBOARD neutral One 1000 A, one 600 A, and three 150 A circuits 42 circuits main bonding jumper ground bus Six 150 A circuits Total of 15 Slot/Lighting Panelboards LIGHTING/SLOT PANELBOARD 42 circuits through the main bonding jumper back to the transformer supply. Note that the ground busses and neutral bars are all from their respective panel structures. There is currently no ground current detection at the main jumper location. The main switchboard, sub-panelboards, and lighting/slot panelboards enclosures are all bonded to the. What this means is that ground faults internal to these structures will produce currents that flow through the and will be detected by the CT that encircles the grounding electrode conductor. Also picked up by this CT sensor will be some capacitive leakage currents as a result of the proximity of phase conductors to conductive surfaces bonded to the A clamp-on ammeter wrapped around the grounding electrode conductor displayed a whopping current of 76 A. Even with a notch filter with 100 Hz cutoff frequency, the current was still unacceptably high at a level of 45 A. This set the stage for the investigation to follow. Page 4

5 An Initial Hurdle to Overcome Difficulties soon arose as we began to implement what we felt was a methodical approach for pinpointing the source of the ground fault problem. The idea was to determine the residual current at the entrance to each power distribution panel. Encircling all the phase and neutral conductors with a core-balance or window type CT would provide us with this essential information. It soon become evident, however, that such a task was impossible because of physical constraints and the wiring layout. The idea of using individual CTs wired using the Holmgren method proved to be an attractive alternative. The configuration is illustrated in the sketch below. On a short notice we secured four 1000:5 CTs with a window Holmgreen Method 76 A 76 A Zero Sequence 750 kva 76 A Ground Return opening of 4 to 6 each with a burden capacity of 5 VA. Terminating the Holmgreen connection into the current jacks of a digital multimeter proved satisfactory as we were able to duplicate the current reading from the ground fault relay meter in the grounding electrode path. For this hook-up to work, the ammeter section of the digital multimeter must have a low burden voltage. The Model 83 Fluke Meter meets this requirement when set to the 4 A or 10 A range. In the photo at the right, the CTs are bright orange and the test leads are yellow. Applying this technique to the main switchboard indeed confirmed that 76 A of current failed to return to the transformer via the phase and neutral conductors. Page 5

6 Working Our Way Downstream From the Main Switchboard We now applied the previous procedure to the SP200B sub-panelboard. Again, we were able to measure a residual current with magnitude of 62 A, this being a clear indication that a portion of the fault lay downstream of this panel. We proceeded onward with the tedious task of narrowing our search to one or more of the slot/lighting panelboards that derive their supply from the SP200B panel. To our surprise, each one of these panels got a clean bill of health. We now had to turn our attention again to the SP200B panel and question our earlier assumption that the panel itself was clean and free of any defect. A visual inspection revealed that the neutral bar was in fact solidly bonded to the panel which, as was shown on page 4, is also bonded to the. Removing this bond did indeed clear the fault. Not all was well, however, since the ground fault relay meter in the grounding electrode conductor leg now displayed a current of 47 A. SP200B Sub-Panelboard Line Side Current = 62 A No residual current on the Line Side of the adjacent SP (42 branch) Slot/Lighting panelboard. Note the yellow Hioki clamp-on meter. The picture to the right shows a Blue Chip technician removing the neutral-to-panel bonding jumper. Needless-to-say, safety precautions were exercised since this troubleshooting sequence was conducted with the panels in an energized state. Page 6

7 Back to the Main Switchboard The test equipment was moved back to the Line Side of the Main Switchboard. With the four CTs again connected in the Holmgren configuration we were able to confirm the validity of the 47A reading from the ground fault relay meter. The sketch below illustrates the situation. With a suspicious eye toward discounting the obvious we noted as anticipated the existence of the main bonding jumper. The tip-off, as to the most likely source of the problem, was revealed when we noted that the magnitude of the current flowing through the main bonding jumper was the same 47 A displayed on the ground fault relay MAIN SWITCHBOARD SP200C neutral One 1000 A, one 600 A, and three 150 A circuits main bonding jumper ground bus Page 7

8 Getting Closer The type of behavior we observed seemed to indicate that perhaps, even though a visual inspection seemed to indicate otherwise, the ground bus was not after all. If this is the case, some of the neutral current will be re-directed as shown in the sketch to the right. It remained to answer the question: How do we prove this? Working on a live system reduced our options. The idea was to first connect a heavy gauge wire from the ground bus to the grounding electrode conductor as shown in the sketch below, MAIN SWITCHBOARD SP200C MAIN SWITCHBOARD SP200C neutral One 1000 A, one 600 A, and three 150 A circuits neutral main bonding jumper One 1000 A, one 600 A, and three 150 A circuits ground bus main bonding jumper non- ground bus and then to disconnect the main bonding jumper. This precautionary step was necessary in the event a ground fault occured after the main bonding jumper was removed; the temporary connection provides a path back to the supply for the ground fault current. The ground fault current magnitude dropped to 8 A after removing the main bonding jumper thus confirming our suspicion that the ground bus bar was not as intended by the design engineer. Still, the 8 A figure was unacceptably high. Page 8

9 Success at Last After additional tests we were able to determine that the fault was originating in one of the circuits leaving the SP200B sub-panelboard. This particular circuit feeds a distro box with label SP210 that is located underneath the ceiling as shown in the photo at the right. Several quad receptacle boxes, located in the casino gambling area, are fed from this distro box. Each quad receptacle box supplies power to four slot machines. We quickly observed after opening the quad receptacle outlet box that the neutral was grounded. The ground fault current back at the transformer dropped to 1 A after removing this neutral-to-ground connection. The photo below shows the hardware and test equipment. As indicated earlier on page 3, there are a total of five step-down transformers in the casino. The knowledge gained earlier was applied in earnest to the task of clearing ground faults uncovered in various circuits powered by these transformers.. Page 9

10 Future Recommendations Testing the entire system can be a hazardous task. The continuous gambling operation requires testing to be done under power. Shutting down 2300 slots is not an option. It is highly recommended to install a BENDER RCMS Fault Finding System. This will enable technicians to quickly identify and pinpoint the source of ground fault problems without having to open electrical panels and exposing themselves to shock hazards. In addition to increased shock hazard exposure, an arcing ground fault current that is allowed to persist indefinitely is a potential fire hazard that can cause considerable damage and may result in an extended power outage. An insulation failure is one source for an arcing fault. Causes of insulation breakdown include moisture, dirt contamination, foreign objects, insulation deterioration and physical damage from mechanical stresses and insulation puncture. The fault finding process often brought us within inches of live conductors. Undoubtedly, ground fault events will occur repeatedly throughout the life of the facility. As such, again and again the Blue Chip crew will have to navigate around live distribution circuits to resolve these ground fault issues. It would be of great benefit to give them the right tools to identify these circuits automatically without the fear of litigation and personal injury. The BENDER RCMS460 scanning system is the solution. Contact: Torsten Gruhn (800) info@benderrelay.com T hese symbols are important. ISO9001:2000 is a globally renowned standard with certifi cates awarded in over 150 countries. It implies the application of a leading quality management system to product manufacturing. The CE mark is a declaration by the manufacturer that the product meets all the appropriate provisions of the relevant legislation implementing certain European Directives. In particular, amongst other standards, these products meet the Electromagnetic Compatibility (EMC) requirements of IEC 62020: which governs the emissions of the products and their immunity to interference from other sources. Page 10

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56 1. Two Electrical Technicians are discussing markings that are required for AC wiring. Tech A says that AC conductors must be rated for 600 volts and must have their jackets and individual conductors marked

More information

Grounding Recommendations for On Site Power Systems

Grounding Recommendations for On Site Power Systems Grounding Recommendations for On Site Power Systems Revised: February 23, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Explain grounding best practices and code

More information

HAWK5000 Operators Manual

HAWK5000 Operators Manual HAWK5000 Operators Manual Keison Products P.O. Box 2124, Chelmsford CM1 3UP, England Tel: +44 (0) 1245 600560 Fax: +44 (0) 1245 600030 Email: sales@keison.co.uk www.keison.co.uk KANE INTERNATIONAL LIMITED

More information

User's Guide. AC Circuit Load Tester. Model CT70

User's Guide. AC Circuit Load Tester. Model CT70 User's Guide AC Circuit Load Tester Model CT70 Introduction Congratulations on your purchase of the CT70 AC Circuit Load Tester. This device can detect circuit and wiring problems such as: Poor ground

More information

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER GROUNDED ELECTRICAL POWER DISTRIBUTION Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER .0 Conductors for Electrical Power Distribution For single-phase transmission of AC power or

More information

Electrical Wiring: Commercial, Seventh Canadian Edition

Electrical Wiring: Commercial, Seventh Canadian Edition Electrical Wiring Commercial Canadian 7th Edition Mullin SOLUTIONS MANUAL Full download at: https://testbankreal.com/download/electrical-wiring-commercialcanadian-7th-edition-mullin-solutions-manual/ Unit

More information

IMPLEMENTATION OF CABLE HEAD REMOTE SWITCH UNIT TO INCREASE EFFICIENCY AND PRODUCTIVITY OF ONBOARD TESTING IN THE ABSENCE OF LAND INSTALLATIONS

IMPLEMENTATION OF CABLE HEAD REMOTE SWITCH UNIT TO INCREASE EFFICIENCY AND PRODUCTIVITY OF ONBOARD TESTING IN THE ABSENCE OF LAND INSTALLATIONS IMPLEMENTATION OF CABLE HEAD REMOTE SWITCH UNIT TO INCREASE EFFICIENCY AND PRODUCTIVITY OF ONBOARD TESTING IN THE ABSENCE OF LAND INSTALLATIONS Stephen Coy, Jon Elliott (Alcatel-Lucent Submarine Networks)

More information

To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies

To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies Introduction In electrical circuits, voltage is always measured between two points: a point of high potential

More information

Grounding and Bonding of Service Equipment

Grounding and Bonding of Service Equipment Grounding and Bonding of Service Equipment 1. Grounding means: attached to an earth ground. 2. Bonding means: physically connected to insure electrical continuity. NEC 250.4 1. Grounding: Electrical Systems

More information

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

INSTALLATION, OPERATION AND MAINTENANCE GUIDE INSTALLATION, OPERATION AND MAINTENANCE GUIDE FOR INDOOR/OUTDOOR SINGLE PHASE ENCAPSULATED TRANSFORMERS Indoor/Outdoor Encapsulated Transformers The pictures used in this guide are only a representation

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

GFL-1000 User Manual Ground Fault Locator

GFL-1000 User Manual Ground Fault Locator GFL-Series User Manual V1.1 GFL-1000 User Manual Ground Fault Locator Contents Contents... 1 1 Declaration of Conformity... 3 2 Introduction... 3 3 Equipment Information... 3 3.1 Safety Precautions...

More information

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL SINGLE PHASE INSTRUCTION MANUAL DIAGRAM D This manual applies to all single-phase buck & boost transformers sold by Larson Electronics. Please refer to the connection diagram on pages 4-6 for properly

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

White Paper: Electrical Ground Rules

White Paper: Electrical Ground Rules Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment

More information

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009 User s Guide Publication number 34134-90001 April 2009 For Safety information, Warranties, Regulatory information, and publishing information, see the pages at the back of this book. Copyright Agilent

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions conduit? 9/8/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Can branch circuits of different services be installed in the same Yes, see 300.3(C)(1) for conductors of different systems

More information

ELECTRICAL SAFETY TESTERS. Wings for Your Projects. APPLICATION NOTE

ELECTRICAL SAFETY TESTERS. Wings for Your Projects. APPLICATION NOTE APPLICATION NOTE ELECTRICAL SAFETY TESTERS Wings for Your Projects. Four Principal Tests for Evaluating the Safety of Electrical and Electronic Products TOS SERIES ELECTRICAL SAFETY TESTER TOS SERIES SELECTION

More information

Deploying Current Transformers in Applications Greater Than 200 A

Deploying Current Transformers in Applications Greater Than 200 A Deploying Current Transformers in Applications Greater Than 200 A Andrew Schaeffler Step-down Current Transformers (CTs) are common, and useful, in large motor applications. They provide isolation between

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

Upgrading Your Electrical Distribution System To Resistance Grounding

Upgrading Your Electrical Distribution System To Resistance Grounding Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding

More information

IRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors

IRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors IRIS POWER TGA-B Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors We have not found another test method that produces as much decision support data for generator

More information

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I have a 500 KVA generator, with no overcurrent protection

More information

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences

More information

MODEL 421 Over/Under Motor Load Monitor

MODEL 421 Over/Under Motor Load Monitor MODEL 421 Over/Under Motor Load Monitor Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or, Single-phase or 3-phase Built-in Trip and Restart

More information

Panoramic Power System. PAN-10, PAN-12 User Guide

Panoramic Power System. PAN-10, PAN-12 User Guide Panoramic Power System Copyright Notice Copyright 2012-2014 Panoramic Power Ltd. All rights reserved. 2 Contents Overview... 4 Workflow... 4 Unpacking the Hardware... 4 Safety Precautions... 5 Hardware

More information

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL 1.01 SUMMARY: The following technical specification describes the requirements of the high accuracy standalone 3 phase Power

More information

OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM

OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM Version 3.0 (European version 1.3) This is a general manual describing a series of racks receiving Servo Amplifiers having output capability suitable

More information

SE-502 MANUAL GROUND-FAULT GROUND-CONTINUITY DETECTOR

SE-502 MANUAL GROUND-FAULT GROUND-CONTINUITY DETECTOR SE-502 MANUAL GROUND-FAULT GROUND-CONTINUITY DETECTOR March 5, 2002 PRELIMINARY 1 Publication: SE-502-M Document: S95-C502-00000 Printed in Canada. Copyright 2002 by Startco Engineering Ltd. All rights

More information

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102 G e m i n i high RESISTANCE GROUNDING SYSTEM the power to protect Instruction Manual C-102 HIGH RESISTANCE GROUNDING SYSTEM Gemini is a unique, fail safe, all-in-one neutral grounding system, combining

More information

Model 5100F. Advanced Test Equipment Rentals ATEC (2832) OWNER S MANUAL RF POWER AMPLIFIER

Model 5100F. Advanced Test Equipment Rentals ATEC (2832) OWNER S MANUAL RF POWER AMPLIFIER Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) OWNER S MANUAL Model 5100F RF POWER AMPLIFIER 0.8 2.5 GHz, 25 Watts Ophir RF 5300 Beethoven Street Los Angeles, CA 90066

More information

Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada

Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada and Philip Giddings Engineering Harmonics Toronto, Canada The original document and figures

More information

Thank you for your interest in the Electrical Technician program. Following is the application process:

Thank you for your interest in the Electrical Technician program. Following is the application process: Thank you for your interest in the Electrical Technician program. Following is the application process: Information Session: Attendance at an Information Session is a prerequisite to acceptance into EHOVE

More information

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost Adam T. Powell, PE President Emerald Engineering, Inc. Jeffrey L. Small, Sr. Senior

More information

ECM3 EARTH CONTINUITY RELAY

ECM3 EARTH CONTINUITY RELAY TECHNICAL DATASHEET ECM3 EARTH CONTINUITY RELAY Electrical Protection for Hard Rock Mines Application The ECM3 has been designed to provide earth continuity protection for cables containing pilot cores.

More information

Wiring of the Main Distribution Panelboard

Wiring of the Main Distribution Panelboard Job Sheet 4 Wiring of the Main Distribution Panelboard OBJECTIVE To connect the service-entrance conductors. To ground the main distribution panelboard (MDP). To wire a branch circuit supplying a three-phase

More information

Instruction Manual for Digital Grounding Resistance Meter. Table of Contents

Instruction Manual for Digital Grounding Resistance Meter. Table of Contents I. Overview...2 II. Open-case Inspection...3 III. Safety Precautions...4 IV. Work Principle...7 V. Appearance Description...9 VI. Technical Characteristics 10 VII. Resistance Measurement Method..12 VIII.Battery

More information

First Draft Language

First Draft Language 110.16 First Draft Language (B) Service Equipment. In addition to the requirements in (A), service equipment shall contain the following information: (1) Nominal system voltage (2) Arc flash boundary (3)

More information

Immunity Testing for the CE Mark

Immunity Testing for the CE Mark Immunity Testing for the CE Mark Summary The European Union (EU) currently has 25 member countries with 2 additional countries to be added in 2007. The total population at that time will be nearly a half

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

Continued from Part 1 Rules 1 25.

Continued from Part 1 Rules 1 25. Continued from Part 1 Rules 1 25. 26 225.32 Disconnect Location The disconnecting means for a building or structure must be installed at a readily accessible location, either outside the building or structure

More information

Safety Warnings Features Specifications Instrument Layout Operation Preparation AC Current Measurement How to Use Peak Hold Function How to Use The

Safety Warnings Features Specifications Instrument Layout Operation Preparation AC Current Measurement How to Use Peak Hold Function How to Use The Safety Warnings Features Specifications Instrument Layout Operation Preparation AC Current Measurement How to Use Peak Hold Function How to Use The Frequency Selector Switch How to Use Data Hold Function

More information

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016. Title Grounding System Introduction Date October, 2016 Related Products Key words All industrial automation products Grounding, Earthing, TN, TT, IT, Introduction The automation industry of today has adopted

More information

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER OPERATOR S MANUAL DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER Masibus Automation & Instrumentation Pvt. Ltd. B/30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India Web Site: www..com

More information

OPERATING MANUAL SERIES R B F 400 VAC BRUSHLESS RACK SYSTEM

OPERATING MANUAL SERIES R B F 400 VAC BRUSHLESS RACK SYSTEM OPERATING MANUAL SERIES R B F 400 VAC BRUSHLESS RACK SYSTEM Version 1.0 (European 1.0) This is a general manual describing a series of racks receiving Servo Amplifiers having output capability suitable

More information

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Introduction The topic of system grounding is extremely important, as it affects the susceptibility of the system to voltage

More information

SureTest Model ST-1THD & ST-1THDC Instructions

SureTest Model ST-1THD & ST-1THDC Instructions #61-156 #61-157 #61-158 SureTest Model ST-1THD & ST-1THDC Instructions Introduction The SureTest family of Circuit/distortion analyzers identify problems common to electrical circuits and harmonic distortion

More information

INSTRUCTION MANUAL. March 11, 2003, Revision 3

INSTRUCTION MANUAL. March 11, 2003, Revision 3 INSTRUCTION MANUAL Model 701A Stimulator March 11, 2003, Revision 3 Copyright 2003 Aurora Scientific Inc. Aurora Scientific Inc. 360 Industrial Parkway S., Unit 4 Aurora, Ontario, Canada L4G 3V7 Tel: 1-905-727-5161

More information

Broadband Current Probe Series Operation Manual

Broadband Current Probe Series Operation Manual Broadband Current Probe Series Operation Manual 1 TABLE OF CONTENTS INTRODUCTION 3 GENERAL INFORMATION 4 OPERATING INSTRUCTIONS 5 FORMULAS 6 MAINTENANCE 7 WARRANTY 8 2 INTRODUCTION CURRENT PROBE SPECIFICATIONS

More information

2011 / Circuit Tracer

2011 / Circuit Tracer INSTRUCTION MANUAL 2011 / 00521 Circuit Tracer Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. 52044992 2008 Greenlee Textron

More information

User s Manual Current Probe. IM E 1st Edition. Yokogawa Electric Corporation

User s Manual Current Probe. IM E 1st Edition. Yokogawa Electric Corporation User s Manual 701932 Current Probe Yokogawa Electric Corporation 1st Edition Foreword Revisions Thank you for purchasing the 701932 Current Probe. This user's manual contains useful information about the

More information

LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS

LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS Peter Leipold, Klaus-Peter Panzlaff Bewag Aktiengesellschaft, Puschkinallee 52, D-12435 Berlin Tel.: +49 30 267 10 350 - Fax: +49 30 267 10 352 -

More information

AT Advanced Wire Tracer. Users Manual

AT Advanced Wire Tracer. Users Manual AT-1000 Advanced Wire Tracer Users Manual AT-1000 Advanced Wire Tracer English Users Manual AT1000_Rev001 2008 Amprobe Test Tools. All rights reserved. Limited Warranty and Limitation of Liability Your

More information

EPG. by Chris C. Kleronomos

EPG. by Chris C. Kleronomos April 1994 EFFECTIVE EQUIPMENT GROUNDING ECOS Electronics Corporation by Chris C. Kleronomos The quality of the electrical wiring and grounding in a facility containing sensitive electronic equipment is

More information

Earth Fault Indicator EFI-BLZ-50 User Manual

Earth Fault Indicator EFI-BLZ-50 User Manual Earth Fault Indicator EFI-BLZ-50 User Manual CONTENTS SAFETY NOTICE.................................................................................... 3 1 OVERVIEW......................................................................................

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

OPTIMIZING MAINS IMPEDANCE: REAL WORLD EXAMPLES by Judith M. Russell Consulting Electrical Engineer PowerLines

OPTIMIZING MAINS IMPEDANCE: REAL WORLD EXAMPLES by Judith M. Russell Consulting Electrical Engineer PowerLines by Judith M. Russell Consulting Electrical Engineer PowerLines Introduction Power Quality has historically been quantified in terms of voltage. Metering equipment measures RMS voltage level, voltage sags

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING Rev. 01 This specification is property of SEC and subject to change or modification without any notice

More information

American Electrical Institute

American Electrical Institute American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article

More information

Multi range AC current clamps (1000A / 100A / 5A / 0.5A) A 1281 Instruction manual Version 2.0, Code no

Multi range AC current clamps (1000A / 100A / 5A / 0.5A) A 1281 Instruction manual Version 2.0, Code no (1000A / 100A / 5A / 0.5A) A 1281 Instruction manual Version 2.0, Code no. 20 751 696 Distributor: Manufacturer: METREL d.d. Ljubljanska cesta 77 1354 Horjul Slovenia web site: http://www.metrel.si e-mail:

More information

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4 SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: 16.10 Document Number: KUCSH0039 Rev: 4 16.10.1 INTRODUCTION 16.10.1.1 The intent of this standard is to ensure that continuity

More information

Digital Panel Meter K3TE. Model Number Structure. Model Number Legend. Easy-to-use, Low-cost Digital Panel Meter that Accepts DC Input K3TE

Digital Panel Meter K3TE. Model Number Structure. Model Number Legend. Easy-to-use, Low-cost Digital Panel Meter that Accepts DC Input K3TE Digital Panel Meter K3TE Easy-to-use, Low-cost Digital Panel Meter that Accepts DC Input Compact DIN-size (96 x 48 (W x H)) body. Mounting thickness of only 3.5 mm required. Highly visible display with

More information

PREMIER INSTALLATION AND OPERATING INSTRUCTIONS

PREMIER INSTALLATION AND OPERATING INSTRUCTIONS PREMIER INSTALLATION AND OPERATING INSTRUCTIONS Copyright 2002-2006, PRI Ltd. 9600-3003-2 Issue C Information contained within this document is subject to change without notice and does not represent a

More information

Licensed Electricians Practical Assessment (LEP)

Licensed Electricians Practical Assessment (LEP) Licensed Electricians Practical Assessment (LEP) Surname: Given Names: Date: Time: Location: Assessment Time (includes reading and preparation time): At the end of this time you will be asked to stop.

More information

Exercise 10. Transformers EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to transformers

Exercise 10. Transformers EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to transformers Exercise 10 Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the basic operating principles of transformers, as well as with the different ratios of transformers:

More information

LC8 & LC8-15. Single Level Lighting Controller INSTALLATION AND MAINTENANCE MANUAL (IMM) 205_LC8_R4

LC8 & LC8-15. Single Level Lighting Controller INSTALLATION AND MAINTENANCE MANUAL (IMM) 205_LC8_R4 Single Level Lighting Controller INSTALLATION AND MAINTENANCE MANUAL (IMM) 205_LC8_R4 TABLE of CONTENTS 1 INTRODUCTON...3 1.1 GENERAL...3 1.2 OVERVIEW...3 2 INSTALLATION...4 2.1 POWER CONNECTIONS...4 2.2

More information

DT1100 E xx xx (PS) Galvanic Isolators. Operating Instructions

DT1100 E xx xx (PS) Galvanic Isolators. Operating Instructions DT1100 E xx xx (PS) Galvanic Isolators Operating Instructions Contents 1. About this document...4 1.1. Function... 4 1.2. Target group... 4 1.3. Symbolism used... 4 2. For your safety...5 2.1. Authorized

More information

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources Introduction Ground fault sensing detects current that flows between a source and a (faulted) load traveling on other than

More information

NFPA-70E. Electrical Safety in the Workplace. Standard for Edition

NFPA-70E. Electrical Safety in the Workplace. Standard for Edition NFPA-70E Standard for Electrical Safety in the Workplace 2015 Edition NFPA-70E 90.1 Purpose. The purpose of this standard is to provide a practical safe working area for employees relative to the hazards

More information

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com AN EXAMPLE OF A STANDARD ARC

More information

Webinar: An Effective Arc Flash Safety Program

Webinar: An Effective Arc Flash Safety Program Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of

More information

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,

More information

B. Manufacturers: Square-D, G.E. or Westinghosue.

B. Manufacturers: Square-D, G.E. or Westinghosue. SECTION 16470 - PANELBOARDS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION SECTION 16715 COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION PART 1 - GENERAL 1.01 SECTION DESCRIPTION AND BASIC REQUIREMENTS A. The Electrical Power Distribution System provides power distribution from

More information

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1. TECHNICAL SPECIFICATIONS for Single Phase, 1 to 3 KVA Power Conditioner with Regulation and Distribution Constant Power 3 (CP3) CP36508A 7/15/04 1.0 General This specification covers the electrical characteristics

More information

Data Sheet. Summation Current Transformer OMEGA SUMMATION CT : SIGMA SERIES. Page 1 of 5 00 / 1213

Data Sheet. Summation Current Transformer OMEGA SUMMATION CT : SIGMA SERIES. Page 1 of 5 00 / 1213 OMEGA SUMMATION CT : SIGMA SERIES Data Sheet Summation Current Transformer Page 1 of 5 Omega Summation current transformers are designed to summarize several synchronous Alternating Currents of equal phase

More information

Boat Dock Exposure Voltage Mitigation

Boat Dock Exposure Voltage Mitigation Jodie Lane National Conference Boat Dock Exposure Voltage Mitigation Frank C. Lambert December 9, 2013 Problem Statement Swimming or working in the water around docks with customer owned electrical circuits

More information

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes FINAL - ER 70 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.

More information

80i-110s AC/DC CURRENT PROBE

80i-110s AC/DC CURRENT PROBE Table of Contents 3 80i-110s AC/DC CURRENT PROBE Users Manual November 1996 1994, 1996 Fluke Corporation. All rights reserved. All product names are trademarks of their respective companies. Printed in

More information

User s Manual. Ground Resistance Clamp On Tester MODEL

User s Manual. Ground Resistance Clamp On Tester MODEL User s Manual Ground Resistance Clamp On Tester MODEL 382357 Warranty EXTECH INSTRUMENTS CORPORATION warrants the basic instrument to be free of defects in parts and workmanship for one year from date

More information

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions Isolators, Isolator / Power Supplies Operating Instructions EN Contents 1. About this document...4 1.1. Function... 4 1.2. Target group... 4 1.3. Symbolism used... 4 2. For your safety...5 2.1. Authorized

More information

Instruction Manual for Digital Grounding Resistance Meter

Instruction Manual for Digital Grounding Resistance Meter Instruction Manual for Digital Grounding Resistance Meter Instruction Manual for Digital Grounding Resistance Meter Table of Contents I. Overview...2 II. Open-case Inspection...3 III. Safety Precautions...4

More information

The D.C. Scout. Operations Manual. (Available Online) D.C. BATTERY DISTRIBUTION SYSTEM GROUND LOCATOR. When minutes matter. Page 1

The D.C. Scout. Operations Manual. (Available Online) D.C. BATTERY DISTRIBUTION SYSTEM GROUND LOCATOR. When minutes matter. Page 1 The D.C. Scout D.C. BATTERY DISTRIBUTION SYSTEM GROUND LOCATOR When minutes matter Operations Manual (Available Online) Page 1 To order parts or for assistance, call or email: H.J Arnett Industries, L.L.C.

More information

Operator s Manual. PP016 Passive Probe

Operator s Manual. PP016 Passive Probe Operator s Manual PP016 Passive Probe 2017 Teledyne LeCroy, Inc. All rights reserved. Unauthorized duplication of Teledyne LeCroy documentation materials is strictly prohibited. Customers are permitted

More information

AT-4000 Advanced Tracer User s Manual

AT-4000 Advanced Tracer User s Manual AT-4000 Advanced Tracer User s Manual Amprobe thanks you for purchasing the AT-4000 Advanced Tracer. For your safety, please read this instruction manual in its entirety. LIMITED WARRANTY VÉÇzÜtàâÄtà ÉÇá4

More information

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) GENERAL MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) SUBMITTED BY SASHIKUMAR G BHARAT HEAVY ELECTRICALS LIMITED INDUSTRIAL SYSTEMS GROUP Prof. C. N. R. Rao Circle I. I. Sc. POST Malleswaram Bangalore

More information

Wisconsin Contractors Institute Continuing Education

Wisconsin Contractors Institute Continuing Education IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you

More information

Harmonic Distortion Levels Measured at The Enmax Substations

Harmonic Distortion Levels Measured at The Enmax Substations Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned

More information

An American Control Electronics Brand PCM4 SERIES USER MANUAL PCM4.

An American Control Electronics Brand PCM4 SERIES USER MANUAL PCM4. An American Control Electronics Brand PCM4 SERIES PCM4 USER MANUAL www.minarikdrives.com Dear Valued Consumer: Congratulations on your purchase of the PCM4 Series isolation card. This User Manual was created

More information

ULTRA-K Series 600K - he

ULTRA-K Series 600K - he 5 kva 500 kva ULTRA-K Series 600K - he High Efficiency K-Rated Power Conditioning Transformers Designed to be used with linear or non-linear loads. Applications: Audio / Video Recording Equipment IT Systems

More information

Type Nominal voltage (V) Code HSV V

Type Nominal voltage (V) Code HSV V Speed control Speed control relay - mm Control of overspeed, underspeed, operating rate, stopping Measurement via discrete sensors - -wire PNP or NPN, Namur, voltage 0-0V or volt-free contact type Works

More information

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5 Applied Grounding and Bonding Paul Dobrowsky Member NEC Panel 5 1 Introduction This presentation is a representative sample from the following Chapters of Applied Grounding and Bonding. Chapter 1, Introduction

More information

PACSystems* RX3i IC695MDL765

PACSystems* RX3i IC695MDL765 March 2011 PACSystems* RX3i IC695MDL765 Digital Output Module with Diagnostics 16-Channel The 24/125 volt DC 2A Smart Digital Output module, IC695MDL765, provides 16 discrete outputs in two isolated groups

More information

Back to the Basics Current Transformer (CT) Testing

Back to the Basics Current Transformer (CT) Testing Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of

More information

SECTION CABLE TRAYS

SECTION CABLE TRAYS SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Copyright 2014 by Minarik Drives

Copyright 2014 by Minarik Drives Copyright 2014 by Minarik Drives All rights reserved. No part of this document may be reproduced or transmitted in any form without written permission from Minarik Drives. The information and technical

More information

ECET 211 Electrical Machines and Controls

ECET 211 Electrical Machines and Controls ECET 211 Electrical Machines and Controls 2016/4/27 Class Review and Wrapping Up Comprehensive Exam, Friday, 1:00-3:00 PM, May 6, 2016 Close books/allow 1-page (8 x 11 and ½) hand-written review note,

More information

3B SCIENTIFIC PHYSICS

3B SCIENTIFIC PHYSICS 3B SCIENTIFIC PHYSICS Analogue Multimeter Escola 100 1013527 Instruction sheet 12/15 SD/JS 1 Display with mirror scale 2 Slotted screw for zero calibration 3 Calibration trimmer for setting centre zero

More information

Installation Manual DOC R1 Date: 05/27/99. Plug-in Meter Installation Manual

Installation Manual DOC R1 Date: 05/27/99. Plug-in Meter Installation Manual Installation Manual DOC-4004-5015-R1 Date: 05/27/99 Plug-in Meter Installation Manual Document Number: Doc-4004-5015-R1 Document Release Date: 5/99 Copyright 1999 TeCom Inc. All rights reserved. No part

More information