1 Page 1 of 6 Description The measuring system is designed for flow measurement. Gas flow through the sensing section passes two PT 100 RTD transducers; one is used as a temperature sensing device whilst the other is used as a heater. The temperature sensor monitors the actual process value whilst the heater is maintained at a constant differential temperature above this by varying the power consumed by the sensor. The greater the mass flow, the greater the cooling effect and power required to maintain the differential temperature. The measured heater power is therefore a measure of the gas flow rate and is evaluated as a measuring signal using the transmitter electronics. The measuring systems consists of a transmitter and a sensor which can be mounted together (compact version) or separate (remote version). The electronic of the transmitter (type T-mass 6*) mounted inside the enclosure Proline G02. Type designation: T-MASS 6 * F ** - * * * * * * * * * * * * T-MASS 6 * I -* * * * * * * * * * * * * * Signal output A, B, C, D, E, H, J, K, L, M, N, P, Q, V, W, 0, 2, 3, 4, 5, 6, 7, 8, 9 = non-intrinsically safe outputs F = Ex ia PROFIBUS PA G = Ex ia Foundation Fieldbus R = Ex ia HART current output, active S = Ex ia HART current output, frequency output, active T = Ex ia HART current output, frequency output, passive U = Ex ia HART current output, passive Software Power supply Cable entry Housing A = Compact version 1 = Compact version, Ta -40 C G = Remote version 7 = Remote version, Ta -40 C Approvals B = Ex d [ia] IIC, Ex td A21 D = Ex de [ia] IIC, Ex td A21 N = Ex d [ia] IIC, Ex td A21 U = Ex d [ia] IIC, Ex td A21 3 = Ex d [ia] IIC, Ex td A21 5 = Ex de [ia] IIC, Ex td A21 Certificate Calibration Surface finishing Seal Process connection Material of tube / sensor Nominal diameter (type of sensor = F) or Insertion tube length (type of sensor = I) Type of electronic

2 Page 2 of 6 Parameters 1 Power supply (terminals no. 1 (L/+) and 2 (N/-) Nominal Voltage pure AC version AC 85 to 260 V DC/AC version DC 16 to 62 V or AC 20 to 55 V max. voltage Um AC 260 V 2 Signal circuits 2.1 Non-intrinsically safe signal circuits Type Terminal No. Safety parameters ***********p *************p with p = A, B, C, D, E, H, J, K, L, M, N, P, Q, V, W, 0, 2, 3, 4, 5, 6, 7, 8 or U m = 260 V, I max = 0.5A The service connector is limited for use with Endress+Hauser interfaces only, Um = 15 VDC. 2.2 Intrinsically safe signal circuits Type ***********F *************G Terminal No. Safety parameters Ex ia IIC Ii = 600 ma Pi = 8.5 W Ci 5 nf Li 10 µh

3 Page 3 of 6 Type ***********R *************R ***********S *************S ***********T *************T ***********U *************U Terminal No. Safety parameters Ex ia IIC Co = 0.16 µf Lo = 4.1 mh Co = 0.16 µf Lo = 4.1 mh Ex ia IIB Uo = 21.8 V Io = 90 ma Po = 491 mw Co = 1.16 µf Lo = 15 mh Ii = 10 ma Pi = 300 mw Ii = 500 ma Pi = 600 mw Uo = 21.8 V Io = 90 ma Po = 491 mw Co = 1.16 µf Lo = 15 mh Ii = 10 ma Pi = 300 mw Ii = 500 ma Pi = 600 mw Ii = 100 ma Pi = 1.25 W Ii = 100 ma Pi = 1.25 W

4 Page 4 of Intrinsically safe sensor circuits Terminals / Plugs for remote version 41, 42, 43, 44 = Sensor circuit For the connection of the remote sensor a cable with a max. length of 100 m and the following max values has to be used: Cable Inductance 0.9 µh per meter Cable capacitance 1 nf per meter 2.4 Medium and ambient temperatures The relationship between maximum ambient, medium temperatures and temperature class are as follows (for compact versions and sensor remote versions): max. medium temperature [ C] Temp. Class T4 T3 T2 T1 Ta max = 55 C T-mass 6*F**-************ Ta max = 60 C T-mass 6*F**-************ T-mass 6*I-************** Max. ambient temperature transmitter remote version type T-mass 6*F**-*******(G,7)**** and type T-mass 6*I-*********(G,7)**** 60 C Min. ambient temperature T-mass 6*F**-*******A**** T-mass 6*F**-*******G**** T-mass 6*I-*********A**** T-mass 6*I-*********G**** T-mass 6*F**-*******1**** T-mass 6*F**-*******7**** T-mass 6*I-*********1**** T-mass 6*I-*********7**** -20 C -40 C

5 Page 5 of 6 Marking Name of the manufacturer or its trademark Serial number Certificate number Ambient temperature range Warning: For the transmitter a delay time of 10 minutes after switching off the power before opening the enclosure has to be regarded. Compact versions Type/Order code Marking Gas Marking Dust ****** 2)1) **** Ex d[ia] IIC T1-T4 ******** 2)1) **** ****** 3)1) **** Ex de[ia] IIC T1-T4 ******** 3)1) **** ********3 1) **** Ga/Gb Ex d[ia] IIC T1-T4 4) ********5 1) **** Ga/Gb Ex de[ia] IIC T1-T4 4) 1) 2) 3) 4) At this place A or 1 will be inserted At this place B, N, U or 3 will be inserted At this place D or 5 will be inserted Comment: Sensor mounted in the wall to Zone 0 For types ***********F, *************F, ***********G and *************G additional marking with: Fisco Field device Remote Versions Transmitter Type/Order code Marking Gas Marking Dust ****** 2)1) **** Ex d[ia] IIC T1-T4 ******** 2)1) **** ****** 3)1) **** ******** 3)1) **** Ex de[ia] IIC T1-T4 1) 2) 3) At this place G or 7 will be inserted At this place B, N, U or 3 will be inserted At this place D or 5 will be inserted

6 Page 6 of 6 Sensor Type/Order code Marking Gas Marking Dust ****** 2)1) **** Ex ia IIC T1-T4 ******** 2)1) **** ****** 3)1) **** ******** 3)1) **** Ga/Gb Ex ia IIC T1-T4 4) 1) 2) 3) 4) At this place G or 7 will be inserted At this place B, N, U or D will be inserted At this place 3 or 5 will be inserted Comment: Sensor mounted in the wall to Zone 0

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12 EB-20023139 Revision: AA Number of Pages: 13 Comments: Originator: RCS 10/05/12 Approved: RCS 10/05/12 Rev ECN Description Approval Date AA 1049085 Release to Approvals RCS 10/9/12 Micro Motion, Inc. Page

More information

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12 EB-20023137 Revision: AA Number of Pages: 13 Comments: Originator: RCS 10/05/12 Approved: RCS 10/05/12 Rev ECN Description Approval Date AA 1049085 Release to Approvals RCS 10/9/12 Micro Motion, Inc. Page

More information

TÜV NORD CERT. TÜV NORD CERT GmbH & Co. KG Am TÜV 1 D Hannover. Annexe to IECEx TUN , issue No. 0 Page 1 of 5.

TÜV NORD CERT. TÜV NORD CERT GmbH & Co. KG Am TÜV 1 D Hannover. Annexe to IECEx TUN , issue No. 0 Page 1 of 5. GmbH & Co. KG Page 1 of 5 Electrical data: Base devices for 6DR50**-*****-**** Motherboard L250 Power supply / control current 4-20 ma... series connection (terminals 6+ and 7/8) 2-wire circuit with Hart

More information

Annex 1 to Certificate of Conformity IECEx KEM X Issue No. 8 Rota Yokogawa Rotamass 3 Series Coriolis Mass Flowmeter

Annex 1 to Certificate of Conformity IECEx KEM X Issue No. 8 Rota Yokogawa Rotamass 3 Series Coriolis Mass Flowmeter Description RotaMass 3 Series Coriolis Mass Flow Meter; - Integral Transmitter, Model RCCx; - Remote Converter, Model RCCF31; - Remote Converter, Model RCCR31; - Remote Detector Model RCCS3xxxx The Coriolis

More information

Micro Motion Model 5700 Transmitter IECEx Zone 2/22 Installation Instructions EPL Gc and EPL Dc

Micro Motion Model 5700 Transmitter IECEx Zone 2/22 Installation Instructions EPL Gc and EPL Dc IECEx Installation Instructions EB-20025744 Rev. AC December 2015 Micro Motion Model 5700 Transmitter IECEx Zone 2/22 Installation Instructions EPL Gc and EPL Dc 5700 IECEx Installation Instructions EB-20025744

More information

Attachment to Certificate IECEx PTB X

Attachment to Certificate IECEx PTB X Applicant: Electrical Apparatus: KROHNE Ltd. Measuring converter, type MFC400F Description of equipment The measuring converter, type MFC400F is used as part of a mass flow measuring system to determine

More information

Proline Promass 40. Safety Instructions. NEPSI Zone 1, Zone 21

Proline Promass 40. Safety Instructions. NEPSI Zone 1, Zone 21 Safety Instructions Proline Promass 40 NEPSI Zone 1, Zone 21 This document is an integral part of the following Operating Instructions: BA00061D, Proline Promass 40 HART Contents General warnings.......................................................................

More information

Micro Motion Model 5700 Transmitter ATEX Zone 2/22 Installation Instructions II 3 G or II 3 (2) G/EPL Gc & II 3 D/EPL Dc

Micro Motion Model 5700 Transmitter ATEX Zone 2/22 Installation Instructions II 3 G or II 3 (2) G/EPL Gc & II 3 D/EPL Dc ATEX Installation Instructions EB-20025742 Rev. AC December 2015 Micro Motion Model 5700 Transmitter ATEX Zone 2/22 Installation Instructions II 3 G or II 3 (2) G/EPL Gc & II 3 D/EPL Dc 5700 ATEX Installation

More information

Certificate of Conformity

Certificate of Conformity Certificate Holder: ABB Automation Products GmbH Schillerstrasse 72 D-32425 Minden GERMANY Electrical Apparatus: Type of Protection: 2600T Pressure Transmitter Models 265../267../269.. Communication protocol:

More information

IECEx Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

IECEx Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers Instruction Manual Supplement DVC6200 Digital Valve Controllers IECEx Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers SIS Hazardous Area Approvals and Special Instructions

More information

ATEX Installation Drawings and Instructions

ATEX Installation Drawings and Instructions Installation Instructions P/N 20004414, Rev. C September 2008 ATEX Installation Drawings and Instructions For ATEX-approved transmitter installations Note: For hazardous installations in Europe, refer

More information

Proline Promass 83, 84

Proline Promass 83, 84 Safety Instructions Proline Promass 83, 84 NEPSI Zone 1, Zone 21 This document is an integral part of the following Operating Instructions: BA00059D, Proline Promass 83 BA00109D, Proline Promass 84 BA00063D,

More information

2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER

2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER SAFE INSTALLATION MANUAL (FM APPROVAL) -WIRE UNIVERSAL TEMPERATURE TRANSMITTER (HART communication, intrinsically safe/explosion-proof) MODEL B6U/B6U-B BEFORE USE... SAFETY PRECAUTIONS This manual describes

More information

DPharp Differential Pressure and Pressure Transmitters

DPharp Differential Pressure and Pressure Transmitters User s Manual DPharp Differential Pressure and Pressure s Manual Change No. 12-021-2 For the products of EJX and EJA-E series with any of the following option codes, please refer to this manual change

More information

Intrinsic Safety Control Drawing

Intrinsic Safety Control Drawing s Intrinsic Safety Control Drawing A5E00455287 system in total "No revision to drawing without prior Approval by FM Approvals!" PLC PC Non hazardous area PROFIBUS DP RS 485-IS Coupler PROFIBUS RS 485-IS

More information

CERTIFICATE OF COMPLIANCE

CERTIFICATE OF COMPLIANCE FM Approvals 1151 Boston Providence Turnpike P.O. Box 9102 Norwood, MA 0202 USA T: 781 72 400 F: 781-72-975 www.fmapprovals.com CERTIFICATE OF COMPLIANCE HAZARDOUS (CLASSIFIED) LOCATION ELECTRICAL EQUIPMENT

More information

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C 34-TT-03-07 3/06 PRODUCT SPECIFICATION SHEET OVERVIEW The Honeywell STT170 series of programmable temperature

More information

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C 6/07 PRODUCT SPECIFICATION SHEET OVERVIEW The Honeywell STT170 series of programmable temperature transmitters

More information

CSA Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

CSA Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers Instruction Manual Supplement DVC6200 Digital Valve Controllers CSA Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers SIS Hazardous Area Approvals and Special Instructions

More information

Description. Annexe to: IECEx CML X Issue 1. Isolating Amplifier D461

Description. Annexe to: IECEx CML X Issue 1. Isolating Amplifier D461 October 13, 2017 Annexe to: IECEx CML 15.0063X Issue 1 Applicant: Apparatus: Braun GmbH Isolating Amplifier D461 Description The Isolating Amplifier D461 is an intrinsic safety associated apparatus

More information

IECEx Certificate of Conformity Annexe

IECEx Certificate of Conformity Annexe for Certificate No.: IECEx TSA 13.0023X Issue No.: 0 Description: The Measuring Gauge of type series SMALL * / / / / / / / / / / * / * is an intrinsically safe supplied apparatus providing different electronic

More information

ATEX Installation Instructions for Micro Motion CMF400 Sensors with Booster Amplifier

ATEX Installation Instructions for Micro Motion CMF400 Sensors with Booster Amplifier Installation Instructions P/N MMI-20010152, Rev. A June 2007 for Micro Motion CMF400 Sensors with Booster Amplifier For ATEX-approved sensor installations Note: For hazardous installations in Europe, refer

More information

CSA Hazardous Area Approvals Fisher FIELDVUE DVC6005 Series Remote Mount Digital Valve Controllers

CSA Hazardous Area Approvals Fisher FIELDVUE DVC6005 Series Remote Mount Digital Valve Controllers Instruction Manual Supplement DVC6005 Digital Valve Controllers CSA Hazardous Area Approvals Fisher FIELDVUE DVC6005 Series Remote Mount Digital Valve Controllers Hazardous Area Approvals and Special Instructions

More information

Ex instruction manual. Rotamass Coriolis mass flow meter. IECEx. IM 01U10X02-00EN-R_002, 2nd edition,

Ex instruction manual. Rotamass Coriolis mass flow meter. IECEx. IM 01U10X02-00EN-R_002, 2nd edition, Ex instruction manual Rotamass Coriolis mass flow meter IM 01U10X02-00EN-R_002, 2nd edition, 2016-09-22 Table of contents Table of contents 1 Introduction... 4 1.1 Scope of application... 4 1.2 Applicable

More information

Safety Instructions Proline Promass 300

Safety Instructions Proline Promass 300 XA01507D/06/EN/01.16 71327925 Products Solutions Services Safety Instructions Proline Promass 300 Class I, Zone 2 AEx/Ex na ic IIC Class I, Zone 2, AEx/Ex na nc ic IIC Class I Division 2 C US Document:

More information

R88000 T (including ATEX)

R88000 T (including ATEX) INSTRUCTION MANUAL R88000 T88000 (including ATEX) Factory set transmitters are ready to use. Connect according the labels. Otherwise follow the calibration instructions. Input signals ṮC RTD CONTENTS:

More information

FM Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

FM Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers Instruction Manual Supplement DVC6200 Digital Valve Controllers FM Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers SIS Hazardous Area Approvals and Special Instructions

More information

Installation Instructions P/N MMI , Rev. AA July ATEX Installation Instructions for Micro Motion Model 3500 Transmitters

Installation Instructions P/N MMI , Rev. AA July ATEX Installation Instructions for Micro Motion Model 3500 Transmitters Installation Instructions P/N MMI-20011707, Rev. AA July 2009 ATEX Installation Instructions for Micro Motion Model 3500 Transmitters Note: For hazardous installations in Europe, refer to standard EN 60079-14

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance Certificate: 70163240 (166720) Issued to: WIKA Alexander Wiegand SE & Co. KG Alexander-Wiegand-Str 30 Klingenberg, Bayern 63911 GERMANY Attention: Harald Gollas The products listed

More information

Safety Instructions Proline Promag 500

Safety Instructions Proline Promag 500 XA01524D/06/EN/01.16 71327947 Products Solutions Services Safety Instructions Proline Promag 500 Cl.I, II, III Div.1 for XP (Ex d Flameproofed version) C US Document: XA01524D Safety instructions for electrical

More information

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/ > 4 channels for 2-wire HART transmitters and 4 channels for 4-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

Certificate of Conformity

Certificate of Conformity Applicant: Moore Industries International Inc. 16650 Schoenborn Street North Hills CA 91343-6196 U.S.A Electrical Apparatus: Fully Encapsulated PC-Programmable Temperature Transmitters (TRX: nonisolated;

More information

Temperature Input Module for Zone 1 Series 9482/32

Temperature Input Module for Zone 1 Series 9482/32 www.stahl.de > 8 channels for temperature sensors > Intrinsically safe inputs Ex ia > For Pt-, Ni- and Cu-resistance temperature detectors according to DIN, IEC and GOST in 2-, 3- and 4-wire circuits >

More information

User's Manual. ROTAMASS Total Insight Coriolis Mass Flow and Density Meter Explosion Proof Type Manual IECEx IM 01U10X02-00EN-R

User's Manual. ROTAMASS Total Insight Coriolis Mass Flow and Density Meter Explosion Proof Type Manual IECEx IM 01U10X02-00EN-R User's Manual ROTAMASS Total Insight Coriolis Mass Flow and Density Meter Explosion Proof Type Manual IECEx IM 01U10X02-00EN-R IM 01U10X02-00EN-R, 3rd edition, 2017-11-16 Table of contents Table of contents

More information

IP26 Series Current to Pneumatic Converter

IP26 Series Current to Pneumatic Converter Product Specifications 06.2016 PSS EVE0403 A-(en) IP26 Series Current to Pneumatic Converter The IP26 (current to pressure) transducer converts a 4 20mA electrical current signal to a proportional linear

More information

STT 3000 Smart Temperature Transmitter Series STT170 Specifications

STT 3000 Smart Temperature Transmitter Series STT170 Specifications STT 3000 Smart Temperature Transmitter Series STT170 Specifications Model STT171, STT173, STT17H, STT17F, STT17C 34-TT-03-07 November 2010 Overview STT17H Features The Honeywell STT170 series of programmable

More information

Ex instruction manual. Rotamass Coriolis mass flow meter ATEX. IM 01U10X01-00EN-R_002, 2nd edition,

Ex instruction manual. Rotamass Coriolis mass flow meter ATEX. IM 01U10X01-00EN-R_002, 2nd edition, Ex instruction manual Rotamass Coriolis mass flow meter ATEX IM 01U10X01-00EN-R_002, 2nd edition, 2016-09-22 Table of contents Table of contents 1 Language variants of ATEX documentation... 4 2 Introduction...

More information

Emerson (Appleton Group ATX)

Emerson (Appleton Group ATX) These assemblies are available in AC-powered and DC-powered versions. They have space to land 48 or 96 CHARM I/O depending on the model chosen. The field I/O can be specified as either IS or NON-IS I/O.

More information

OPTIMASS / 300 / 010 Guidelines for the use of Coriolis meters in hazardous areas

OPTIMASS / 300 / 010 Guidelines for the use of Coriolis meters in hazardous areas OPTIMASS / 300 / 010 Guidelines for the use of Coriolis meters in hazardous areas 1000 Series Twin Straight Tube Coriolis Mass Flowmeter 2000 Series Twin Straight Tube Coriolis Mass Flowmeter 3000 Series

More information

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters ll 2G EEx ia llc T6 As our products are continuously improved, we reserve the right to make any change in the stated specifications

More information

Universal Intelligent 2-wire In-head Transmitters

Universal Intelligent 2-wire In-head Transmitters Universal Intelligent 2-wire In-head Transmitters Actual size IPAQ-H is a universal and intelligent 2-wire In-head transmitter for temperature and other measurement applications. IPAQ-HX is the Intrinsic

More information

Safety Instructions Nivotester FTC625, FTC325

Safety Instructions Nivotester FTC625, FTC325 XA01351F-A/00/EN/01.14 71273077 Products Solutions Services Safety Instructions FTC625, FTC325 [Ex ia Ga] IIC/IIB TÜV 13.0903 X Segurança TÜV INMETRO OCP 0004 Document: XA01351F-A Safety instructions for

More information

Product manual wire programmable RTD transmitter

Product manual wire programmable RTD transmitter Product manual 5332 2-wire programmable RTD transmitter PERFORMANCE MADE SMARTER TEMPERATURE I.S. INTERFACES COMMUNICATION INTERFACES MULTIFUNCTIONAL ISOLATION DISPLAY No. 5332V100-UK From serial no: 181903001

More information

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With Field-mounted Two-wire Signal Conditioners B6-UNIT 8: TIIS flameproof (CE not available) Confirm selectable combinations of approval and wiring conduit types in the table. 2-WIRE UNIVERSAL TEMPERATURE

More information

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5. Ex i Isolators Temperature Transmitter with Output 0/4... 20 ma, without Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

Two-channel safety barriers Series 9002

Two-channel safety barriers Series 9002 Two-channel safety s Series 00 > Wide product range for all standard applications of the automation > Flexible and space-saving available in single and double channel versions > Time-saving installation

More information

CERTIFICATE OF COMPLIANCE

CERTIFICATE OF COMPLIANCE FM Approvals 1151 Boston Providence Turnpike P.O. Box 9102 Norwood, MA 02062 USA T: 781 762 4300 F: 781-762-9375 www.fmapprovals.com CERTIFICATE OF COMPLIANCE HAZARDOUS (CLASSIFIED) LOCATION ELECTRICAL

More information

Isolators A3/1. Vibration Transducer Supply Unit Series

Isolators A3/1. Vibration Transducer Supply Unit Series > For vibration, acceleration and speed sensors in 2- and 3-wire design > Space-saving dual-channel version > Signal frequencies up to 50 khz > Easy setting by means of front-side rotary switch > Galvanic

More information

Thie. Automation Products Rev. Chang Date Name Supersedes Dwg. : Part Class:

Thie. Automation Products Rev. Chang Date Name Supersedes Dwg. : Part Class: Page: 1 of 3 - - 2003 Date Name Name 27.03.03 Thiem. Title FM/CSA-Control-Document Appr. / 5 08.07.11 Thie. Std. 4 07.10.09 Lasa. 3 26.06.06 Thie. Drwg.-No. (Part-No.) 2 22.05.06 Thie. 901265 1 27.03.

More information

Intrinsically Safe Compact Controller CTR 210i. Intrinsically Safe Bargraph Indicator. BGI 210i

Intrinsically Safe Compact Controller CTR 210i. Intrinsically Safe Bargraph Indicator. BGI 210i Intrinsically Safe Compact Controller CTR 210i Intrinsically Safe Bargraph Indicator BGI 210i DMT 02 ATEX E 148 2. Supplement also grahics display Revision 4 IBS BatchControl GmbH Im Sträßchen 2 4 Tel.:

More information

Temperature Transmitters TMT 136, TMT 137

Temperature Transmitters TMT 136, TMT 137 Technical Information TI 066R/09/en Part No. 51000855 Temperature Transmitters TMT 136, TMT 137 For Pt100 Resistance Thermometers 2-wire head transmitter Standard- and instrinsically safe versions Head

More information

Analog Universal Module HART for Zone 2 Series 9468/33

Analog Universal Module HART for Zone 2 Series 9468/33 > 8 channels can be adjusted individually as analog inputs or outputs > Intrinsically safe inputs/outputs Ex ia > For 0/4 20 ma + HART signals > Line fault monitoring per channel > Diagnostics based on

More information

MCR-FL-TS-LP-I-EX SIL IEC Programmable Intrinsically Safe Loop-Powered Temperature Measuring Transducer With HART Protocol

MCR-FL-TS-LP-I-EX SIL IEC Programmable Intrinsically Safe Loop-Powered Temperature Measuring Transducer With HART Protocol SIL IEC 6 508 Programmable Intrinsically Safe Loop-Powered Temperature Measuring Transducer With HART Protocol Data Sheet 0068_en_03 PHOENIX CONTACT 0-07-09 Description Temperature FL ϑ Universal PC programmable

More information

A9000Px Power/Signal Adapter Installation Drawing for Emerson Transmitters

A9000Px Power/Signal Adapter Installation Drawing for Emerson Transmitters THIS DRAWING IS PROPERTY OF AND PROPRIETARY TO EMERSON. THIS DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED NOR DISCLOSED TO ANYONE EXCEPT THOSE REQUIRING ITS USE FOR EMERSON AUTHORIZED

More information

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater DS INSTRUCTI MANUAL RS/RS Fieldbus Isolating Repeater Din-Rail Model DS D - RS / RS Fieldbus Isolating Repeater ISM00- Characteristics General Description: The single channel DIN Rail RS / RS Fieldbus

More information

General Specifications

General Specifications General Specifications FN310 Field Wireless Multi-Protocol Module GENERAL This General Specification (GS) describes the specifications for Field Wireless Multi-Protocol Module. Combined with Field Wireless

More information

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels TF 0 / TF 0-Ex Head mounted temperature transmitters, FOUNDATION Fieldbus (H), Pt 00 (RTD), thermocouples, or independent channels 0/-8.5 EN Input Resistance thermometer (,, wire circuit) Thermocouples

More information

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique Operator Manual Transmitters Series KAT-... Analog transmitters in 2-wire technique Important Safety Notes! In the case of non-observance of the installation and safety notes or improper use of the transmitter

More information

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/. Ex i Isolators Temperature Transmitter without Output 0/4... 20 ma, with Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

General Specifications

General Specifications General Specifications EJX Series FOUNDATION TM Fieldbus Communication FOUNDATION fieldbus is the digital communication line for the field instruments, whose signal is internationally standardized by Fieldbus

More information

Two-channel safety barriers Series 9002

Two-channel safety barriers Series 9002 Two-channel safety s Series 00 > Wide product range for all standard applications of the automation > Flexible and space-saving available in single and double channel versions > Time-saving installation

More information

Specifications. Specifications. Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift

Specifications. Specifications. Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift Appendix A Specifications 1797-IE8 and -IE8NF Input Modules Specifications Number of Inputs IS Input Type IS Module Type Resolution Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift Functional

More information

PROline promag 53 Division 1

PROline promag 53 Division 1 XA 040D/06/en/05.01 50099923 FM+SGML 6.0 PROline promag 53 Division 1 Ex Ex documentation for the BA 053D and BA 054D operating instructions according to FACTORY MUTUAL standards documentation for the

More information

D1035S INSTRUCTION MANUAL. Frequency-Pulse Isolating Repeater DIN Rail Model D1035S. D Frequency-Pulse Isolating Repeater

D1035S INSTRUCTION MANUAL. Frequency-Pulse Isolating Repeater DIN Rail Model D1035S. D Frequency-Pulse Isolating Repeater D1035S INSTRUCTION MANUAL FrequencyPulse Isolating Repeater DIN Rail Model D1035S D1035 FrequencyPulse Isolating Repeater ISM007910 Characteristics General Description: The single channel DIN Rail FrequencyPulse

More information

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits RHE12 Hazardous Area Coriolis Mass Flow Transmitter Features Field mounting Compact, pressure safe housing ATEX and CSA approvals for installation in hazardous areas 24 VDC power supply Configurable analog

More information

MODEL: B3HU. Space-saving Two-wire Signal Conditioners B3-UNIT

MODEL: B3HU. Space-saving Two-wire Signal Conditioners B3-UNIT Space-saving Two-wire Signal Conditioners B3-UNIT 2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER (HART communication, intrinsically safe) Functions & Features Universal input: mv, V, T/C, RTD, resistance, potentiometer

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

Installation Instructions P/N MMI , Rev. AA July ATEX Installation Instructions for Micro Motion Model RFT9739 Transmitters

Installation Instructions P/N MMI , Rev. AA July ATEX Installation Instructions for Micro Motion Model RFT9739 Transmitters Installation Instructions P/N MMI-20011709, Rev. AA July 2009 ATEX Installation Instructions for Micro Motion Model RFT9739 Transmitters Note: For hazardous installations in Europe, refer to standard EN

More information

General Specifications

General Specifications General Specifications FN510 Field Wireless Multi-Function Module GENERAL This General Specification (GS) describes the specifications for Field Wireless Multi-Function Module. Combined with Field Wireless

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i Temperature Transmitter Series 9182 www.stahl.de > One unit for nearly all temperature sensors indivdually configurable > Intrinsically safe input [Ex ia] IIC > Signal duplication possible > Galvanic isolation

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series Transmitter Supply Unit Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring and messaging for input

More information

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted Electrical temperature measurement Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted WIKA data sheet TE 60.34 Applications Machine building, plant and vessel construction

More information

Universal Intelligent 2-wire DIN Rail Transmitters

Universal Intelligent 2-wire DIN Rail Transmitters Universal Intelligent 2-wire DIN Rail Transmitters IPAQ-L is a universal and intelligent 2-wire DIN rail transmitter for temperature and other measurement applications. IPAQ-LX is the Intrinsic Safe version

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F Series 9160 Rev. F > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

Coriolis Massflowmeter

Coriolis Massflowmeter Coriolis Massflowmeter for liquids and gas measuring monitoring analysing Measuring range: 0-60 kg/h 0-60 000 kg/h water Accuracy: ±0,15 of reading ±zero-point stability pmax: PN40 tmax: -40 +180 C Connection:

More information

Digital Input Module 24 V Ex n Inputs, 16 Channels Series 9471

Digital Input Module 24 V Ex n Inputs, 16 Channels Series 9471 > 16 channels for active 0 / 24 V signals > Zone 2 / Division 2 version for connection of circuits acc. to Ex nl, Ex na, Nonincendive and Non-Ex > Galvanic separation between inputs and system > Two channels

More information

Coriolis Massflowmeter

Coriolis Massflowmeter Coriolis Massflowmeter for liquids and gas measuring monitoring analysing Measuring range: 0-0.8 kg / h 0-65 000 kg / h water Accuracy: ± 0.1 of reading ±zero-point stability (liquids) pmax: PN40 tmax:

More information

Head mounted Temperature Transmitter TF02/TF02-Ex

Head mounted Temperature Transmitter TF02/TF02-Ex Data Sheet Head mounted Temperature Transmitter TF0/TF0-Ex FOUNDATION Fieldbus H, Pt 00 (RTD), thermocouples, or independent channels Input Resistance thermometer (-, -, -wire circuit) Thermocouples Resistance

More information

Single-Channel Safety Barriers Series 9001

Single-Channel Safety Barriers Series 9001 Single-Channel Safety Barriers Series 9001 > Broad product range for all standard applications in the world of automation > Flexible and space saving single and dual channel versions available > Time saving

More information

HART Compatible Intelligent 2-wire In-head Transmitters

HART Compatible Intelligent 2-wire In-head Transmitters HART Compatible Intelligent 2-wire In-head Transmitters Actual size MESO-H is a Smart and universal 2-wire Inhead transmitter for temperature and other measurement applications. MESO-HX is the Intrinsic

More information

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22 www.stahl.de > 16 channels for contacts and NAMUR proximity switches (EN 60947-5-6) > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

... for hydraulic and general applications in hazardous areas

... for hydraulic and general applications in hazardous areas ATEX Approved Inductive... for hydraulic and general applications in hazardous areas Inductive Namur sensors Explosion protected Ignition class "intrinsically safe" when used together a suitable certified

More information

Trendmaster * Dynamic Scanning Module

Trendmaster * Dynamic Scanning Module 149744 Trendmaster * Dynamic Scanning Module Product Datasheet Bently Nevada * Asset Condition Monitoring Description The 149744 Trendmaster* Dynamic Scanning Module (DSM) is a compact rack-based data

More information

Resistance thermometer Model TR30, compact design

Resistance thermometer Model TR30, compact design Electrical temperature measurement Resistance thermometer Model TR30, compact design WIKA data sheet TE 60.30 Applications Machine building, plant and vessel construction Propulsion technology, hydraulics

More information

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex Data Sheet 10/-8.54 EN Level 0: Information FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Resistance thermometer (2,

More information

SET Installation and Operating Instructions. Level switch for two sensors

SET Installation and Operating Instructions. Level switch for two sensors Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 20.2.2013 Internet: www.labkotec.fi 1/14 SET-2000 Level switch for two sensors Copyright 2013 Labkotec

More information

Safety Instructions Proline Promass 100

Safety Instructions Proline Promass 100 XA00160D/06/EN/03.14 71261250 Products Solutions Services Safety Instructions Proline Promass 100 Modbus RS485 Cl.I Div.1, Zone 1 for IS (Ex i Intrinsically safe version) C US Document: XA00160D Safety

More information

Process transmitter Model UPT-20, with pressure port Model UPT-21, with flush diaphragm

Process transmitter Model UPT-20, with pressure port Model UPT-21, with flush diaphragm Electronic pressure measurement Process transmitter Model UPT-20, with pressure port Model UPT-21, with flush diaphragm WIKA data sheet PE 86.05 Applications Process technology Machine building and plant

More information

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version Temperature Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 for further approvals see page 10 Applications

More information

Isolators A3/1.

Isolators A3/1. > Compact limit value switch with 2 configurable limiting values and 4... 20 ma output > Suitable for 2-, 3-wire transmitters, 2-wire HART transmitters and ma sources > Intrinsically safe input [Ex ia]

More information

RHE11. Hazardous Area Multifunction Coriolis Flow Transmitter. Features. Applications. Benefits

RHE11. Hazardous Area Multifunction Coriolis Flow Transmitter. Features. Applications. Benefits RHE11 Hazardous Area Multifunction Coriolis Flow Transmitter Features Wall or Pipe Bracket Mount Built in safety barriers allow operation with RHM sensor in hazardous area Selectable Metric and English

More information

TMU. Coriolis Mass Flow Meter. for liquids and gas

TMU. Coriolis Mass Flow Meter. for liquids and gas Coriolis Mass Flow Meter for liquids and gas measuring monitoring analysing TMU S5 OO Measuring range: 0-60 kg/h 0-2200 t/h water OO Accuracy: ± 0.1% of reading ±zero point stability (from liquids up to

More information

ProcessMaster, HygienicMaster FEX300, FEX500

ProcessMaster, HygienicMaster FEX300, FEX500 SM/FEX300/FEX500/FM/CSA-EN ProcessMaster, HygienicMaster FEX300, FEX500 FM / cfm Div. 1, Div. 2 Safety information for electrical equipment for potentially explosive areas in accordance with Factory Mutual

More information

Product Manual wire HART transmitter

Product Manual wire HART transmitter Product Manual 6335 2wire HART transmitter PERFORMANCE MADE SMARTER TEMPERATURE I.S. INTERFACES COMMUNICATION INTERFACES MULTIFUNCTIONAL ISOLATION DISPLAY No. 6335V111UK From serial no.: 150951186 6 Product

More information

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater DS INSTRUCTI MANUAL RS/RS Fieldbus Isolating Repeater Din-Rail Model DS D - RS / RS Fieldbus Isolating Repeater ISM00- Characteristics General Description: The single channel DIN Rail RS / RS Fieldbus

More information

SEM210 SERIES. Programmable In-head Universal Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.

SEM210 SERIES. Programmable In-head Universal Temperature Transmitter INDEX SECTION CONTENTS PAGE NO. INDEX SECTION CONTENTS PAGE NO. SEM210 SERIES 1.0 DESCRIPTION 1 2.0 SPECIFICATION 15 3.0 INSTALLATION 67 Programmable Inhead Universal Temperature Transmitter Status Instruments Ltd, Green Lane Business

More information

Loop Powered Indicator

Loop Powered Indicator Instruction Manual Model PD686 Loop Powered Indicator M397 January 3, 2019 JOWA USA, Inc. 59 Porter Road Littleton, MA 01460-1431 USA Tel: 978-486-9800 Fax: 978-486-0170 PD686 I.S. and N.I. NEMA 4X, IP67

More information

User manual. Load cell with one built in amplifier KOSD-FA KIMD-FA KEND-FA Load cell with two built in amplifiers KOSD-FAD KIMD-FAD KEND-FAD

User manual. Load cell with one built in amplifier KOSD-FA KIMD-FA KEND-FA Load cell with two built in amplifiers KOSD-FAD KIMD-FAD KEND-FAD User manual Load cell with one built in amplifier KOSD-FA KIMD-FA KEND-FA Load cell with two built in amplifiers KOSD-FAD KIMD-FAD KEND-FAD Contents Precautions Intended use General 1 Specification 3

More information