Plug-in module SIRAX TV 808, 1 channel Isolating Amplifier, output Ex or non-ex

Size: px
Start display at page:

Download "Plug-in module SIRAX TV 808, 1 channel Isolating Amplifier, output Ex or non-ex"

Transcription

1 for electrically insulating, amplifying and converting DC signals, also designed for FSK 002 II () G pplication The purpose of the isolating amplifi er SIRX TV 808 (Fig. ) is to electrically insulate input and output signals, respectively to amplify and/or change the signal level or type (current or voltage) of the input signals. The instrument version SIRX type 808- has an intrinsically safe and an FSK continuity function and is used to control smart I/P valve positioner in explosion hazard areas. The valve positioner adjust, for example, a pressure or the position of a valve in relation to the impressed output current ( 20 m). The RT bypass permits bi-directional FSK signals to pass according to the RT protocol. green LD on the front plate indicates device standing by. The power supply and the inputs and outputs are electrically insulated. Fig.. Plug-in module SIRX TV 808 for plugging onto backplane BP 902. Variants and non-x isolating amplifiers Designed or not designed for FSK communication User-specific input ranges Power supply 2 0 V DC/C or V DC/C Features / Benefits Isolating amplifi er plugs onto backplane (mechanically latched by fasterners), all electrical connections made to the backplane and not to the SIRX TV 808 / Thus no wiring when replacing devices Designed for FSK communication, hand-held terminal connected to separate terminals. This facilitates operation in conjunction with a smart I/P valve positioner designed for FSK and with a RT or userspecific protocol lectric insulation between input, output (2.3 kv) and power supply (3.7 kv) / Prevents measurement errors due to potential leakage Burden voltage 20 V for not x versions or V for x instruments Non-standard user-specific ranges available C/DC power supply / Universal vailable in type of protection Intrinsic safety [x ia] IIC (see Table 3: Data on explosion protection ) Technical data Measuring input DC current: DC voltage: FSK = Frequency Shift Keying Standard range 20 m Limit value 0 0. to 0 0 m also live-zero, to m max. span: 0 m also bipolar asymmetrical R i = Ω Limit values to 0 0 also live-zero, to V, max. span: 0 V R i = 00 kω Camille Bauer Data sheet TV 808-//7/8 Le 0.09

2 Overload capacity: Measuring output DC current: DC current continuously 2-fold DC voltage continuously 2-fold Standard ranges 20 m, 0 20 m 20 m, 20 0 m Burden voltage: Non-x version 20 V, x version V xternal resistance: Non-x version 000 Ω, x version 70 Ω Current limiter at R ext max.: Voltage limiter at R ext = : Residual ripple in output current: Response time: Power supply pprox.. I N pprox. 2 V 0.% p.p. < 0 ms C/DC power pack (DC and...00 z) Table : Nominal voltages and tolerances Nominal voltage U N Tolerance Instrument version 2 0 V DC/C V DC/C DC 33% C ± % 2 0 V DC/C DC 33% C ± % V C ± 0% 8 0 V DC 0% Power input:.2 W resp. 3 V Standard (non-x) Type of protection Intrinsically safe [x ia] IIC ccuracy data (acc. to DIN/IC 770) Basic accuracy: Limit error ± 0.2% Including linearity and reproducibility errors Reference conditions: mbient temperature Power supply Output burden Influencing factors: Temperature 23 C, ± 2 K 2 V DC ± 0% and 230 V C ± 0% Current: 0. R ext max. < ± 0.% per 0 K For power supplies > 2 V, the auxiliary circuits should include an external fuse with a rating 20 DC. Burden infl uence < ± 0.% Longtime drift < ± 0.3% / 2 months Switch-on drift < ± 0.2% Common and transverse mode infl uence < ± 0.2% Output or connected to ground < ± 0.2% Installation data ousing: Material of housing: Designation: SIRX TV 808 Mounting position: lectrical connections: Coding: Weight: lectrical insulation: Regulations lectromagnetic compatibility: Isolating amplifi er in housing B7 for plugging onto backplane BP 902. Refer to Section Dimensional drawing for dimensions Lexan 90 (polycarbonate) fl ammability class V-0 acc. to UL 9, self-extinguishing, non-dripping, free of halogen ny 9-pin connector acc. to DIN 2, pattern C Layout see Section lectrical connections Isolating amplifi er supplied already coded. The rack is coded by the user by fi tting the coding inserts supplied pprox. 0. kg ll circuits (measuring input/measuring output/power supply) are electrically insulated The standards DIN N and DIN N are observed Intrinsically safe: cc. to N 0 020: 99 ousing protection (acc. to IC 29 resp. N 0 29): ousing IP 0 Terminals IP 00 lectrical standards: cc. to IC 00 resp. N 00 Operating voltages: < 300 V between all insulated circuits Contamination level: 2 Overvoltage category acc. to IC : Double insulation: III for power supply II for measuring input and measuring output Power supply versus all circuits Measuring input versus measuring output 2 Data sheet TV 808-//7/8 Le 0.09 Camille Bauer

3 Test voltage: nvironmental conditions Climatic rating: Measuring input versus: Measuring output 2.3 kv, 0 z, min. Power supply 3.7 kv, 0 z, min. Measuring output versus: Power supply 3.7 kv, 0 z, min. Climate class 3Z acc. to VDI/VD 30 Commissioning temperature: 0 to C Operating temperature: 2 to C, x* 20 to C Storage temperature: 0 to 70 C nnual mean relative humidity: 7% ltitude: Indoor use statement! 2000 m max. * The data of the C-Type xamination Certifi cate for backplane SIRX BP 902 with admission PTB 97 TX 23 should be noted. Table 2: Ordering Informations Description Marking. Mechanical design ousing B7 (for plugging onto backplane BP 902, see data sheet BP 902) Number of channels channel 3. Version / Power supply [x ia] IIC, 2 0 V DC/C (output intrinsically safe) [x ia] IIC, 8 0 V DC / 230 V C (output intrinsically safe) Standard, 2 0 V DC/C 7 Standard, V DC/C 8. Function input, electrically insulated output input, electrically insulated output, designed for FSK communication (RT) (Condition: Input and output 20 m). Input signal 20 m Input [V] 9 [V] to 0 0, also live-zero, [V] to , max. span 0 V also bipolar asymmetrical Input [m] Z [m] 0 0. to 0 0, also live-zero, [m] to max. span 0 m also bipolar asymmetrical. Output signal 20 m 0 20 m B 20 m C 20 0 m D With FSK communication (RT) only possible with 20 m Possible special versions, e.g. increased climatic rating on inquiry. Table 3: Data on explosion protection II () G Order code Type of protection Output Input/Power supply Type xamination Certifi cate Mounting location [x ia] IIC U o = 27.3 V I o = 99 m P o = 7 mw IIC IIB L o. m m U m = 23 V C resp. 2 V DC PTB 98 TX 200 Outside the hazardous area C o 82 nf 77 nf Camille Bauer Data sheet TV 808-//7/8 Le

4 Compatibility Most of the usual smart valve positioners (current-to-pneumatic converter) on the market with IS approval are compatible with the intrinsically safe output of the TV 808 (see Table ). On inquiry, we will verify if other valve positioners can be used. Table : Manufacturer Type x designation Neles Jamesbury lsag Bailey- & B ND820 TZID Samson 3780 Foxboro ckhart Fisher Controls Siemens x ia IIC T, T Demko 9D, 209 x ia IIC T, T, T PTB Nr. -9.C.233 X x ia IIC T PTB Nr. x-9.c.09 U i [V] I i [m] P i [mw] L i [m] C i [nf] SRD99 x ia IIC (T) Fieldvue DVC 000 SIPRT PS x ia IIC T LCI 9.D x ib IIC T, T, T PTB Nr. x-9, C, 238, Zone Burden voltage [V] Burden [Ω] 2. V 30 Ω 0.8 V 0 Ω 0.8 V 0 Ω 2.0 V 00 Ω 2.0 V 00 Ω.0 V 0 Ω lectrical connections SIRX TV 808 Front SIRX TV 808 Rear Fastener c b a 2 3 B C 8 7 Camille Bauer G C-0 Wohlen Switzerland SIRX TV 808 Without function Green LD for indicating device standing by D F G I K L M FSK () ~ () ~ T Plug-in module SIRX TV 808 a a3 c27 c29 a2 a28 a20 c Backplane Connecting allocation see Operating Instructions of backplanes = Input = Output = Power supply T = and-eld-terminal T () ~ () ~ Data sheet TV 808-//7/8 Le 0.09 Camille Bauer

5 Plug allocations Instruments version Wiring diagram / Plug allocation Types Input non-x 808- or 808- Output intrinsically safe, Burden voltage V, c 2 8 a Safe area () () 20 m azardous area X e.g. I/P-converter designed for FSK FSK 20 m T Fig. 2 Safe area Types or Input and output non-x, Burden voltage 20 V, FSK (option) c 2 8 a () () Fig FSK T T = and-eld-terminal Camille Bauer Data sheet TV 808-//7/8 Le 0.09

6 Table : ccessories and spare parts Description Coding comb with 2 sets of codes (for coding the backplane BP 902) Operating Instructions V 808-//7/8 B d-f-e Order No Standard accessories Operating Instructions for SIRX TV 808 in three languages: German, French, nglish Codieng comb with 2 sets of codes Type examination certifi cate (for instruments in type of protection Intrinsically safe only) Dimensional drawing Fig.. SIRX TV 808 in housing B7. Rely on us. Camille Bauer Ltd argauerstrasse 7 C-0 Wohlen / Switzerland Phone: 8 2 Fax: info@camillebauer.com Subect to change without notice dition 0.09 Data sheet TV 808-//7/8 Le

Plug-in module SIRAX TV 808, 1 channel Isolating Amplifier unipolar/bipolar

Plug-in module SIRAX TV 808, 1 channel Isolating Amplifier unipolar/bipolar for electrically insulating, amplifying and converting DC signals 0102 II (1) G pplication The purpose of the isolating amplifi er SIRX T 808 (Fig. 1) is to electrically insulate input and output signals,

More information

SINEAX TV 808, 1 channel Isolating Amplifier, output Ex or non-ex

SINEAX TV 808, 1 channel Isolating Amplifier, output Ex or non-ex for electrically insulating, amplifying and converting DC signals, also designed for FSK 1 0102 II (1) G Application The purpose of the isolating amplifi er SINEAX TV 808 (Fig. 1) is to electrically insulate

More information

Plug-in module SIRAX TI 807 Passive DC signal isolator

Plug-in module SIRAX TI 807 Passive DC signal isolator without power supply, x- and non-x version 0102 II (1) resp. II (2) pplication The signal isolator SIRX TI 807 (Fig. 1) serves to electrically insulate the analogue DC signal in the range 0 20 m which

More information

SINEAX TV 808, 1 channel Isolating Amplifier unipolar/bipolar

SINEAX TV 808, 1 channel Isolating Amplifier unipolar/bipolar For electrically insulating, amplifying and converting DC signals 0102 II (1) G Application The purpose of the isolating amplifi er SINEAX TV 808 (Fig. 1 and 2) is to electrically insulate input and output

More information

SINEAX TV 808, 2 channels Isolating Amplifier Unipolar/Bipolar

SINEAX TV 808, 2 channels Isolating Amplifier Unipolar/Bipolar SINEAX TV 808, channels For electrically insulating, amplifying and converting DC signals Application The purpose of the isolating amplifi er SINEAX TV 808 (Fig. ) is to electrically insulate input and

More information

SINEAX G 537 Transducer for Phase Angle Difference

SINEAX G 537 Transducer for Phase Angle Difference Carrying rail housing P/0 pplication The transducer SINX G 5 (Fig. ) converts the phase angle difference of two synchronised supplies into a load independent DC current or a load independent DC voltage

More information

SINEAX TV809, 1 channel Programmable Isolating Amplifier

SINEAX TV809, 1 channel Programmable Isolating Amplifier For electrically insulating, ampliflying and converting DC signals 0102 II (1) Ga II (1) Da Application The purpose of the isolating amplifi er SINEAX TV809 (Fig. 1) is to electrically insulate input and

More information

Plug-in module SIRAX V 606, 1 or 2 channels Programmable Temp. Transmitter for RTD and TC inputs

Plug-in module SIRAX V 606, 1 or 2 channels Programmable Temp. Transmitter for RTD and TC inputs Plug-in module, or channels Application The programmable transmitter (Fig. ) is designed for measuring temperature in combination with thermocouples or resistance thermometers. Thermocouple non-linearities

More information

SINEAX B 811 Power Pack with additional Functions

SINEAX B 811 Power Pack with additional Functions SINEA B 8 for intelligent and conventional s, in housing S7 for rail and wall mounting 002 II () G Application The power supply unit SINEA B 8 (Figure ) provides the DC power supply for s and transfers

More information

SINEAX TI 807 Passive DC signal isolator

SINEAX TI 807 Passive DC signal isolator without power supply, Ex- and non-ex version, in housing N17 or S17 for rail and wall mounting 0102 II (1) G resp. II (2) G Application The signal isolator SINEAX TI 807 serves to electrically insulate

More information

SINEAX TI 807 Passive DC signal isolator. SINEAX TI 807 Passive DC signal isolator

SINEAX TI 807 Passive DC signal isolator. SINEAX TI 807 Passive DC signal isolator SINEAX TI 807 without power supply, Ex- and non-ex version, in housing N17 or S17 for rail and wall mounting 0102 II (1) G resp. II (2) G Application The signal isolator SINEAX TI 807 serves to electrically

More information

SINEAX G 536 Phase Angle or Power Factor Transducer

SINEAX G 536 Phase Angle or Power Factor Transducer SIEAX G Carrying rail housing P/0 Application The transducer SIEAX G (Fig. ) measures the phase angle or power factor between current and voltage of a single or -phase balanced network having a sine wave

More information

RISH Ducer TV 808, 2 channels Isolating amplifier unipolar / bipolar

RISH Ducer TV 808, 2 channels Isolating amplifier unipolar / bipolar Fig. 1. Isolating amplifier RISH Ducer TV 808 in housing S 17 clipped onto a top - hat rail or screw hole mounting brackets pulled out. Features and Benefits Electric Isolation between input, and power

More information

SINEAX U 553 Transducer for AC Voltage

SINEAX U 553 Transducer for AC Voltage With power supply RMS value measurement Carrying rail housing P/0 Application he transducer SINEAX U 55 (Fig. ) converts a sinusoidal or a distorted AC voltage into a load independent DC current or a load

More information

SINEAX I 552 Transducer for AC current

SINEAX I 552 Transducer for AC current SNEAX 55 With power supply RMS value measurement, with measuring ranges Carrying rail housing P/0 Application he transducer SNEAX 55 (Fig. ) converts a sinusoidal or a distorted AC current into a load

More information

KINAX WT 707 Transmitter for angular position

KINAX WT 707 Transmitter for angular position Ruggedized version pplication The KINX WT 707 (Figs. 1 to 6) converts the angular position of a shaft into a load-independent direct current signal, proportional to the angular position. The unit is contact

More information

SINEAX V 624 Programmable Temperature Transmitter for RTD and TC inputs

SINEAX V 624 Programmable Temperature Transmitter for RTD and TC inputs SINEAX V 6 for rail mounting in housing P/7 or P/7 St 00 II () GD Application SINEAX V 6 (Figs. and ) is designed for measuring temperature in combination with thermocouples or resistance thermometers.

More information

KINAX 2W2 Programmable Transmitter for Angular Position

KINAX 2W2 Programmable Transmitter for Angular Position Application The KINAX 2W2 (Figs. 2 and 3) converts the angular position of a shaft into a load independent direct current signal, proportional to the angular position. The unit is contact free and has

More information

KINAX WT 717 Programmable Transmitter for Angular Position

KINAX WT 717 Programmable Transmitter for Angular Position Ruggedized version Application The KINAX WT 717 (Fig. 1) converts the angular position of a shaft into a load-independent direct current signal, proportional to the angular position. The unit is contact

More information

SINEAX / EURAX 2I1 Passive DC signal isolator

SINEAX / EURAX 2I1 Passive DC signal isolator SINEAX / EURAX I without power supply 0 II () G resp. II () G Application The DC signal isolator SINEAX/EURAX I (Figs. and ) serve to isolate load-independent DC current signals. It suppressed noise voltages

More information

KINAX 3W2 Transmitter for angular position

KINAX 3W2 Transmitter for angular position KINX 3W2 For installation KINX 3W2 is a compact transmitter for angular position for installation in devices and apparatus. Due to its unique capacitive measuring principle, it acquires the angular position

More information

SINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage

SINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage Application The transducers SINEAX I 503/U 504 (Figs. 1 and 2) are designed to convert a sinusoidal AC current or voltage into a load independent DC signal proportional to the measured value. This output

More information

EMBSIN 281 G Power factor transducer

EMBSIN 281 G Power factor transducer EMBSI 8 G Carrying rail housing MBS/SP Application The transducer EMBSI 8 G (Fig. ) measures the power factor between current and voltage of a single or 3-phase balanced network having a sine wave form.

More information

RISH Ducer E15 TRANSDUCER FOR AC CURRENT OR AC VOLTAGE WITH DIFFERENT CHARACTERISTICS

RISH Ducer E15 TRANSDUCER FOR AC CURRENT OR AC VOLTAGE WITH DIFFERENT CHARACTERISTICS RISH Ducer 5 TRNSDUCR FOR C CURRNT OR C VOLTG WITH DIFFRNT CHRCTRISTICS The RISH Ducer 5 transducer (Fig and ) is used where a sine-wave C current or voltage is to be converted into a DC signal proportional

More information

RISH Ducer E13 3 channel transducer for AC current and voltage

RISH Ducer E13 3 channel transducer for AC current and voltage RISH Ducer E13 3 channel transducer for C current and voltage The RISH Ducer E13 ( Fig. 1) converts 3 sine wave C current or C voltage into 3 output signals that can serve several receiving instruments

More information

SINEAX V604s Programmable multifunctional transmitter

SINEAX V604s Programmable multifunctional transmitter SINAX V60s for direct currents, direct voltages, temperature sensors, teletransmitters or potentiometers SINAX V60s is a multifunctional transmitter for tophat rail assembly with the following main characteristics:

More information

KINAX SR 719 Programmable Transmitter for Position Feedback

KINAX SR 719 Programmable Transmitter for Position Feedback Position transmitter with NAMUR valve fitting Application The position feedback transmitter KINAX SR 719 (Figs. 1 and 2) is used to measure and transmit linear displacement (stroke) on various types of

More information

SINEAX V 604s Programmable multifunctional transmitter

SINEAX V 604s Programmable multifunctional transmitter SINEAX V 60s f direct currents, direct voltages, temperature senss, teletransmitters potentiometers 00 SINEAX V60s is a multifunctional transmitter f top-hat rail assembly with the following main characteristics:

More information

Theta 60R. Technical Data Sheet. Special Features. Fig. 2 Theta R, 2 channel version, in housing S17 hole mounting brackets pulled out.

Theta 60R. Technical Data Sheet. Special Features. Fig. 2 Theta R, 2 channel version, in housing S17 hole mounting brackets pulled out. Technical Data Sheet Theta 60R 60 R 60 R Fig. Theta R, channel version, in housing S7 clipped on to a top - hat rail. Fig. Theta R, channel version, in housing S7 hole mounting brackets pulled out. Theta

More information

EURAX VC 603 Programmable combined transmitter/alarm unit

EURAX VC 603 Programmable combined transmitter/alarm unit EURX VC 603 for DC currents or voltages, temperature sensors, remote sensors or potentiometers 010 II (1) GD pplication The combined transmitter/alarm unit EURX VC 603 (Fig. 1) converts the input variable

More information

EURAX UI 505, Combined Transducer for AC current and AC voltage

EURAX UI 505, Combined Transducer for AC current and AC voltage Plug-in module in Euro-format Application The transducers EURAX UI 505 (Fig. 1) are intended to simultaneous converts of up to 3 sinusoidal AC currents or voltages. Output signals available are load-independent

More information

for DC currents or voltages, temperature sensors, remote sensors or potentiometers II (1) G Application Features / Benefits

for DC currents or voltages, temperature sensors, remote sensors or potentiometers II (1) G Application Features / Benefits SINEAX VC 603, Programmable for DC currents or voltages, temperature sensors, remote sensors or potentiometers 0102 II (1) G Application The SINEAX VC 603 (Figs. 1 and 2) converts the input variable a

More information

RISH Ducer E13 Transducer For Ac Current Or Ac Voltage With Different Characteristics

RISH Ducer E13 Transducer For Ac Current Or Ac Voltage With Different Characteristics RISH Ducer E13 Transducer For c Current Or c Voltage With Different Characteristics Data Sheet For Measurement of C Current or C Voltage Fig. 1. RISH Ducer E13 clipped onto a top - hat rail. Fig. 2. RISH

More information

Rudder or propeller angular position transmitter KINAX WT720

Rudder or propeller angular position transmitter KINAX WT720 Description The is a robust, absolute angular position transmitter, which is particularly suitable for use in marine applications such as the detection of rudder or propeller positions. In contrast to

More information

SINEAX VC 603, Programmable combined transmitter/alarm unit

SINEAX VC 603, Programmable combined transmitter/alarm unit for DC currents or voltages, temperature sensors, remote sensors or potentiometers 0102 II (1) G Application The SINEAX VC 603 (Fig. 1) converts the input variable a DC current or voltage, or a signal

More information

for DC currents or voltages, temperature sensors, remote sensors or potentiometers Application Principle of operation (Fig. 3) Features / Benefits

for DC currents or voltages, temperature sensors, remote sensors or potentiometers Application Principle of operation (Fig. 3) Features / Benefits for s or voltages, temperature sensors, remote sensors or potentiometers pplication The universal transmitter RISH Ducer V 604 (Figures 1 and 2) convert the input variable a or voltage, or a signal from

More information

SINEAX V 604 Programmable universal transmitter

SINEAX V 604 Programmable universal transmitter for DC currents or voltages, temperature sensors, remote sensors or potentiometers 0102 II (1) G Application The universal transmitter SINEAX V 604 (Figures 1 and 2) converts the input variable a DC current

More information

2 Safety Barriers. Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

2 Safety Barriers. Single-Channel Safety Barriers with Electronic Current Limitation Series 9004 2 Safety Barriers Single-Channel Safety Barriers with Electronic Current Limitation Series 9004 Broad product range for all standard applications in the world of automation Flexible and space saving Time

More information

Contrans T TEU 471, TEU 471-Ex. Intelligent four-wire temperature transmitters EN

Contrans T TEU 471, TEU 471-Ex. Intelligent four-wire temperature transmitters EN Contrans T TEU 471, TEU 471-Ex Intelligent four-wire temperature transmitters Input/sensor connection: Resistance thermometers (2-, 3-, 4-wire circuit) Thermocouples (without, with internal/external reference

More information

Connection. Input EEx ia IIC. Sense. Fine tuning adjustment. Fine tuning amplifying. Amplifying. Adjustment. Output. Composition

Connection. Input EEx ia IIC. Sense. Fine tuning adjustment. Fine tuning amplifying. Amplifying. Adjustment. Output. Composition Converter Connection 1-channel EEx ia IIC for 4-wire and 6-wire bridges Analogue output 0/4 ma... 20 ma or 4mA...-12mA Full bridge load cells and strain gauges circuit for resistance bridges up to 17 Ω

More information

Theta Hz. Technical Data Sheet. Special Features

Theta Hz. Technical Data Sheet. Special Features Technical Data Sheet Theta Hz Theta Hz the transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent

More information

Assembly. Front view. Power Rail

Assembly. Front view. Power Rail Thermometer Resistance Repeater Features Assembly 1-channel isolated barrier 24 V DC supply (Power Rail) RTD/resistance input Resistance output Accuracy 0.1 % Front view Removable terminals blue Function

More information

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004 Single-Channel Safety Barriers with Electronic Current Limitation > Broad product range for all standard applications in the world of automation > Flexible and space saving > Time saving installation due

More information

3 Ex i Isolators. Switching Repeater with Power Relay (250 V / 4 A) Type 9170/ Type 9170/

3 Ex i Isolators. Switching Repeater with Power Relay (250 V / 4 A) Type 9170/ Type 9170/ 3 Ex i Isolators Switching Repeater with Power Relay Intrinsically safe input [Ex ia] IIC Galvanic isolation between input, output and power supply Open-circuit / short-circuit monitoring and messaging

More information

Isolators A3/1. Vibration Transducer Supply Unit Series

Isolators A3/1. Vibration Transducer Supply Unit Series > For vibration, acceleration and speed sensors in 2- and 3-wire design > Space-saving dual-channel version > Signal frequencies up to 50 khz > Easy setting by means of front-side rotary switch > Galvanic

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

Transmitter for temperature and direct current variables in four-wire circuit. Contrans T TEU 315, TEU 315-Ex, TEU 325, TEU 325-Ex 11-3.

Transmitter for temperature and direct current variables in four-wire circuit. Contrans T TEU 315, TEU 315-Ex, TEU 325, TEU 325-Ex 11-3. TEU 315, TEU 315-Ex, TEU 325, TEU 325-Ex Transmitter for temperature and direct current variables in four-wire circuit Transmitters TEU 315 and TEU 325 are designed for direct and alternating voltage measurement

More information

ZIEGLER PRO-P Power / Phase Angle / Power Factor Transducer

ZIEGLER PRO-P Power / Phase Angle / Power Factor Transducer nalogue Meters With Moving - Iron Movement pplication IEGER PR-P The iegler PR-P transducer is used to measure and convert active, reactive, apparent power, Phase angle & Power Factor of a Single-phase

More information

Analog Universal Module HART for Zone 2 Series 9468/33

Analog Universal Module HART for Zone 2 Series 9468/33 > 8 channels can be adjusted individually as analog inputs or outputs > Intrinsically safe inputs/outputs Ex ia > For 0/4 20 ma + HART signals > Line fault monitoring per channel > Diagnostics based on

More information

... for hydraulic and general applications in hazardous areas

... for hydraulic and general applications in hazardous areas ATEX Approved Inductive... for hydraulic and general applications in hazardous areas Inductive Namur sensors Explosion protected Ignition class "intrinsically safe" when used together a suitable certified

More information

Binary Output without Power Supply Series 9176

Binary Output without Power Supply Series 9176 Binary Output without Power Supply Series 9176 > For intrinsically safe operation of Ex i solenoid valves, indicators and horns > Power supply by control circuit, loop powered > Intrinsically safe output

More information

Binary Output Series 9175

Binary Output Series 9175 Binary Output > Intrinsically safe output [Ex ia] IIC / [Ex ib] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring (can be switched off) > For use

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F Series 9160 Rev. F > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

Indicomp 2, Indicomp 2-Ex. Indicator and alarm signalling unit 10/ EN

Indicomp 2, Indicomp 2-Ex. Indicator and alarm signalling unit 10/ EN Indicator and alarm signalling unit 10/30-2.10 EN Dimensions 36 mm x 144 mm Can either stand vertically or lie horizontally Comprehensively explosion-protected Robust moving-coil system Contactless alarm

More information

Theta 20A / 20V. Technical Data Sheet. Special Features

Theta 20A / 20V. Technical Data Sheet. Special Features Technical Data Sheet Theta 20A / 20V Theta 20A / 20V is used to measure and convert AC Voltage or Current input into a load independent DC current or voltage output signal. Special Features Available in

More information

TR 104, TR 104-Ex Rail mounted Temperature Transmitters

TR 104, TR 104-Ex Rail mounted Temperature Transmitters Data Sheet 10/-8.48-EN Rev. A TR 104, TR 104-Ex Rail mounted Temperature Transmitters Analog, Pt 100 (RTD), fixed measuring ranges Input Resistance thermometer (two-wire and three-wire circuit) Optionally

More information

Remote I/O. 74 Remote I/O. Remote I/O System

Remote I/O. 74 Remote I/O. Remote I/O System System Overview of the System Components IS1+ 76 General Information IS1+ 77 CPU & Power Modules CPU & Power Modules for Zone 1 / Div. 1 IS1+ 9440/22 78 Sockets for CPU & Power Module IS1+ 9490 78 CPU

More information

Isolators Isolating Repeater Field Circuit Ex i ISpac 9165/ s Art. No

Isolators Isolating Repeater Field Circuit Ex i ISpac 9165/ s Art. No 9165/16-11-10s 207909 Compact one- and two-channel Ex i output isolating repeater wire-breakage and short-circuit monitoring system, which can be disconnected and features a signalling contact can be used

More information

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex Data Sheet 10/-8.54 EN Level 0: Information FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Resistance thermometer (2,

More information

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Switching Repeater Series 9170 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit / short-circuit monitoring and messaging (can be switched

More information

Current / residual current and voltage transformers. Current / residual current and voltage transformers

Current / residual current and voltage transformers. Current / residual current and voltage transformers Current / residual current and voltage transformers Current / residual current and voltage transformers 1 Overview Current transformer overview DIN rail current transformer with fuse Current transformer...

More information

Positioner with HART Communication Type 3780

Positioner with HART Communication Type 3780 Positioner with HART Communication Type 780 Application Single-acting or double-acting positioner for attachment to pneumatic control valves. Supplied with an electric input signal from to 20 ma Travels

More information

Isolating Repeater Input Series 9163

Isolating Repeater Input Series 9163 > For 4-wire HART transmitters and voltage sources > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2 (IEC 61508) > High accuracy www.stahl.de

More information

Operating Instructions

Operating Instructions Level and Pressure Operating Instructions VEGATOR 620, 621, 622 max. 0 10 min. 0 10 on VEGATOR 622! 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 Note Ex area... 2 1 Product description

More information

SUBJECT TO CHANGE WITHOUT NOTICE

SUBJECT TO CHANGE WITHOUT NOTICE TRNSUCERS & ISTRS Theta 30P www.sifamtinsley.co.uk TSHEET Issue 1.0 Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders igital Panel Meters Current Transformers

More information

For non-electrical quantities

For non-electrical quantities Controlgear 3UG3 monitoring relays 3RS17 interface converters N nsb0346h nsb0348h nsb0775h For electrical quantities For non-electrical quantities 3RS17 interface converter Selection and ordering data

More information

SALES SERVICE +358 (0)

SALES SERVICE +358 (0) SALES SERVICE +358 (0)17 262 3555 info@econosto.fi ADCATROL ELECTRO-PNEUMATIC POSITIONERS PE 986 (ATEX) DESCRIPTION The ADCATROL PE986 positioner requires an input signal of 4 20 ma for proportional control

More information

Fieldbus Isolating Repeater Series 9185/11

Fieldbus Isolating Repeater Series 9185/11 www.stahl.de > For operation of the intrinsically safe Profibus DP (RS-485 IS to PNO standard) > Intrinsically safe fieldbus RS-422, RS-485 [Ex ib] IIC > Galvanic isolation between RS-422 / RS-485, RS-232,

More information

2 or 4 pole changeover contact Plug-in/Faston 187

2 or 4 pole changeover contact Plug-in/Faston 187 56 Miniature power relays 56 Plug-in - Power relay, & 4 pole Flange mount option - (Faston 87, 4.8 x 0.5 mm termination) C coils & DC coils Lockable test button and mechanical flag indicator Cadmium Free

More information

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i Temperature Transmitter Series 9182 www.stahl.de > One unit for nearly all temperature sensors indivdually configurable > Intrinsically safe input [Ex ia] IIC > Signal duplication possible > Galvanic isolation

More information

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/ > 4 channels for 2-wire HART transmitters and 4 channels for 4-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

Rail mounted Temperature Transmitter TH102/TH102-Ex

Rail mounted Temperature Transmitter TH102/TH102-Ex Data Sheet 10/-8.54 EN Rail mounted Temperature Transmitter TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Input Resistance thermometer (2, 3, 4 wire circuit) Thermocouples

More information

Inductive sensor slot-type SI2-K08-AP7

Inductive sensor slot-type SI2-K08-AP7 SI2-K08-AP7 Slot sensor, height 8 mm Plastic, polypropylene Mechanical end stop, removable, for analog pointer instruments 3-wire DC, 10 30 VDC NO contact, PNP output Cable connection Wiring diagram Type

More information

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: 49 661 60030 Fax: 49 661 6003607 Email: mail@jumo.net Internet: www.jumo.net JUMO

More information

Process Protection Acoustic sensors for pump monitoring

Process Protection Acoustic sensors for pump monitoring coustic sensors for pump monitoring acoustic diagnostic unit Overview The acoustic diagnostic unit acoustically measures the structure-borne noise In the version for pump monitoring; on oscillating displacement

More information

Valve Series V2001 Globe Valve Type 3321 with Pneumatic or Electric Actuator

Valve Series V2001 Globe Valve Type 3321 with Pneumatic or Electric Actuator Valve Series V2001 Globe Valve Type 3321 with Pneumatic or Electric Actuator ANSI version Application Control valves designed for mechanical and plant engineering. Suitable for liquids, gases and steam

More information

n True RMS measurement n Fully onsite programmable input voltage range (for CIP-V)

n True RMS measurement n Fully onsite programmable input voltage range (for CIP-V) Tranducers for alternating current/voltage n True RMS measurement n Fully onsite programmable input voltage range (for CIP-V) and input current range (for CIP-I) n Available in single or dual output type

More information

Output of three-phase motors at 50 Hz and 400 V

Output of three-phase motors at 50 Hz and 400 V RT0, RH Coupling Relays (Interfaces) Description DC operation IEC 0 947 and EN 0 947 (VDE 00) The RT0 coupling relays for switching motors and RH for auxiliary circuits are laid out to the special requirements

More information

Level Measurement silometer FMX 570

Level Measurement silometer FMX 570 Technical Information TI 01F/00/en Level Measurement silometer FMX 570 Measurement of liquids and bulk solids Suitable for explosion hazardous areas For use with capacitance and hydrostatic probes The

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22 www.stahl.de > 16 channels for contacts and NAMUR proximity switches (EN 60947-5-6) > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: 49 661 60030 Fax: 49 661 6003607 Email: mail@jumo.net Internet: www.jumo.net JUMO

More information

M224. M C bis. TYPE CODE M K Y 45 / 18 x 60 - / / / - #

M224. M C bis. TYPE CODE M K Y 45 / 18 x 60 - / / / - # Solenoid coil MKY/18x60 For explosion-hazard zones Protection class IP65/66/67 Optional with integrated amplifier electronics Ex db IIC T6 / T4 Gb Ex tb IIIC IP65 T80 C/T130 C Db Ex db I Mb II 2 G Ex db

More information

RISH Ducer IXX / VXX Series (TRMS/Average) Transducer for AC current / AC Voltage (Single or Dual Output)

RISH Ducer IXX / VXX Series (TRMS/Average) Transducer for AC current / AC Voltage (Single or Dual Output) RISH Ducer IXX / VXX Series (TRMS/verage) Transducer for C current / C Voltage (Single or Dual Output) Data Sheet Transducer for C Current and C Voltage Fig. 1. RISH Ducer I11 in housing E16 clipped onto

More information

Single-Channel Safety Barriers Series 9001

Single-Channel Safety Barriers Series 9001 Single-Channel Safety Barriers Series 9001 > Broad product range for all standard applications in the world of automation > Flexible and space saving single and dual channel versions available > Time saving

More information

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells

More information

ABB ME ASURE ME NT & AN AL YT ICS D AT A SHE ET. 9QGPS2000S Hermetically sealed bending beam load cell

ABB ME ASURE ME NT & AN AL YT ICS D AT A SHE ET. 9QGPS2000S Hermetically sealed bending beam load cell BB ME SURE ME NT & N L YT ICS D T SHE ET 9QGPS2000S Hermetically sealed bending beam load cell 2 Measurement made easy High-end load cell combining high accuracy with high resistance in harsh environment.

More information

Temperature Input Module for Zone 1 Series 9482/32

Temperature Input Module for Zone 1 Series 9482/32 www.stahl.de > 8 channels for temperature sensors > Intrinsically safe inputs Ex ia > For Pt-, Ni- and Cu-resistance temperature detectors according to DIN, IEC and GOST in 2-, 3- and 4-wire circuits >

More information

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter) JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net

More information

Isolators A3/1.

Isolators A3/1. > Compact limit value switch with 2 configurable limiting values and 4... 20 ma output > Suitable for 2-, 3-wire transmitters, 2-wire HART transmitters and ma sources > Intrinsically safe input [Ex ia]

More information

LINAX 4000L Continuous-line recorder

LINAX 4000L Continuous-line recorder -48-852-0 4/2.99 1 to 4 line channels Format 144 mm x 144 mm, mounting depth 250 mm Combined recording table for roll chart (2 m) or fanfold chart (16 m) Measuring channels electrically isolated Rugged

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series Transmitter Supply Unit Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring and messaging for input

More information

Level Limit Switch nivotester FTL 370, FTL 372

Level Limit Switch nivotester FTL 370, FTL 372 Technical Information TI 98F/00/en Limit Switch nivotester FTL 370, FTL 37 With intrinsically-safe signal circuits for connection to sensors Liquiphant, Nivopuls, Soliphant. Features at a Glance High operational

More information

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique Operator Manual Transmitters Series KAT-... Analog transmitters in 2-wire technique Important Safety Notes! In the case of non-observance of the installation and safety notes or improper use of the transmitter

More information

Temperature Transmitters TMT 136, TMT 137

Temperature Transmitters TMT 136, TMT 137 Technical Information TI 066R/09/en Part No. 51000855 Temperature Transmitters TMT 136, TMT 137 For Pt100 Resistance Thermometers 2-wire head transmitter Standard- and instrinsically safe versions Head

More information

Solid-State Soft Starters

Solid-State Soft Starters Selection and ordering data Rated operational voltage U e V Soft starters for three-phase asynchronous motors 3RW30 25-1B14 3RW30 35-1B14 t ambient temperature 40 C Size Order No. Price Weight Pack. Rated

More information

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted Electrical temperature measurement OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 further approvals see page 10 Applications Machine building, plant

More information

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted Electrical temperature measurement Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted WIKA data sheet TE 60.34 Applications Machine building, plant and vessel construction

More information

Technical data Model F1301 F13C1 ATEX/IECEX 2) F13C1 (Option) Nominal load F nom 10 / 20 / 30 / 50 / 100 / 200 kn 10 / 20 / 30 / 50 / 100 / 200 kn 10

Technical data Model F1301 F13C1 ATEX/IECEX 2) F13C1 (Option) Nominal load F nom 10 / 20 / 30 / 50 / 100 / 200 kn 10 / 20 / 30 / 50 / 100 / 200 kn 10 Compression force transducer with Thin-film sensor Accuracy: 1 % Output signal: 4...20 ma; 2-wire, 0...10 VDC; 3-wire Optional Optional ATEX/IECEX II 2G Ex ib IIC T4/T3 for SIL3-Applications with 2-channel

More information