INTELLIGENT EVACUATION SYSTEMS WITH SPEAKERS AND INSTALLATION ACCESSORIES DXT 9000 DXT 7000 DXT 3000 ENG

Size: px
Start display at page:

Download "INTELLIGENT EVACUATION SYSTEMS WITH SPEAKERS AND INSTALLATION ACCESSORIES DXT 9000 DXT 7000 DXT 3000 ENG"

Transcription

1 INTELLIGENT EVACUATION SYSTEMS WITH SPEAKERS AND INSTALLATION ACCESSORIES DXT 9000 DXT 7000 DXT 3000 ENG 2017

2 In any place where people live and work, dangererous situations may occur, requiring an effective and efficient evacuation of affected areas, in conditions of maximum safety for all occupants and avoiding panic as much as possible. In these circumstances, time is precious and each second saved means saving human lifes. For this reason the use of Intelligent Evacuation Systems - designed to communicate clear and intelligible instructions - is crucial. Alarms transmitted using encoded tones, usually generated by sirens or alarm sounders, are a suitable solution where occupants are periodically trained to behave in a specific way depending on the specific alarm. However in crowded places, where occupants are occasional bystanders or even foreigners and need to be reassured and guided along safe routes, it is more effective to use a paging microphone and pre-recorded messages, performed in an intelligible way and containing specific instructions on how to behave in situations of alarm or warning (e.g. how to use escape routes). The normative UNI ISO is in force since 2011, introducing new rules and procedures for the design, installation and maintenance of voice evacuation systems, also known as Sound Systems for Emergency Purposes (SSEP), and the use of EN 54 certified components. The UNI ISO contains all information necessary for designers, installers, maintainance engineers and construction companies. Electronics must include devices and strategies for self-diagnosis and protection, and must be certified by accredited notified bodies according to EN 54-16, plus the loudspeakers must be in accordance with EN APPLICATIONS Environments which are more critical in terms of occupants safety (since they are the most critical to be alerted and evacuated) are those with the highest concentration of people. The risk is high and the area to evacuate particularly extended. Examples: hospitals, schools, shopping centres, sales areas, places of entertainment (cinemas, theatres, clubs, etc.), densely populated buildings (offices buildings), factories (production sites, warehouses, etc.), powerstations, chemical industries, railway stations, subways and airports are the most common structures. SYSTEMS AVAILABILITY An intelligent EN54-certified evacuation system must be operational 24 hours a day, every day of the year. In case of interruption of the primary power supply, it must be powered by a secondary source and its autonomy must be guaranteed for at least 24 hours in a quiescent condition and for 30 minutes in a working condition. These systems, on which safety depends at all times, must be maintained in perfect working order with periodic inspections. Intelligent evacuation systems must also be connected to the fire detection system, so that they can react in a programmed way without supervisory staff and communicate the status to the fire alarm system. 2

3 DXT 9000 SMALL TO LARGE APPLICATIONS DXT 9000 is the evolution to the RCF DXT Active Matrix solution range. To design the system, RCF has developed a digital multi-platform where PA-EVAC join PRO-INSTALL systems in a completely scalable and versatile range of configurations and solutions. The system offers a level of reliability that goes beyond standard requirements. The architecture is extremely flexible, based on digital network with Ethernet connection to the outside world through expandable protocol DANTE; it allows centralized or distributed configurations, and each fault is diagnosed and shown in every detail to ensure simplicity, quick check operations and maintenance in order to ensure a fully efficient evacuation. DXT 9000 meets all restrictive requirements imposed by EN 54-16, adding advanced technological solutions, such as access to the system through SELECTIVE CALL PAGING MICROPHONES Equipped with a gooseneck microphone, can be directly connected to the MU 9186 or MX 9500 central units. CONFIGURATION SOFTWARE The DXT 9000 configuration software allows to configure, monitor and equalize the system and supervise in real-time EVENTS, FAULTS and FAILURES. the integrity network console; the powerful configuration diagnostics software is both comprehensive, yet easy to use. Moreover, interconnection with third-parties systems is available to facilitate the integration with alarm systems and building automation. DXT 9000 is easy to install thanks to a few connections made with J-type fire-resistant cables and screw terminals connectors, simple to configure, and favorablee in terms of fault-monitoring management and electric consumption, thanks to D+ technology, unique of RCF. 3

4 MU 9186 MU 9186R MASTER UNITS p/n p/n MU 9186 is the MASTER UNIT without power on-board: it is used when the system requires a high output power and/or a larger number of zones, and can be obtained adding one or more power amplifiers model UP 9501 (1 x 500W), UP 9502 (2 x 250W) or UP 9504 (4 x 125W), connected through the dedicated RCF-Flexicomm data-link port. MU 9186R is the MASTER UNIT with networking facility on-board; it is used when the system requires a distributed configuration where several MU 9186R and relevant slave amplifier units 9501 (1 x 500W), UP 9502 (2 x 250W) or UP 9504 (4 x 125W) connected through the dedicated RCF-Flexicomm data-link port are part of a large installation with hundreds of zones. Main Features Digital matrix unit is 8x6 configurable, with routing to any output channel, is also available with integrated power amplifiers. Priority evacuation messages resident on main control unit protected and monitored memory. Simultaneous delivery is possible. 12 configurable GPI and configurable 8 GPO available on each unit. Control Center PC application to configure and control all system s parameters. Front panel control with LCD display and 8 buttons. Efficient Digital Signal Processors on inputs and outputs; Parametric EQ, High and Low Pass Filters, Compressor / Limiter, Level controls provided on inputs and outputs. The EQ window provides 3-band equalizer for the Background input and the Monitor and Auxiliary Outputs. 5-band equalizer for the Paging input, Auxiliary inputs and BUS Output. For all input channels (EVAC microphone, paging stations, microphones and analog inputs) the Gain, EQ and Dynamic screens will appear in the DSP EDITOR. Fully parametric high and low frequency filters are available for all the inputs and for the Auxiliary Output. Compressor available (Threshold, Attack, Release and Ratio) on the Auxiliary inputs and BUS Output. Dual power supply, allowing both AC and DC operation. RS 485 serial port for optional program remote control and volume adjustment. MP3 built-in music source with USB and SD-Card reader. MU 9186R only: twin LAN ports for DIGITAL AUDIO IN (1 channel from external source) and OUT (2 channels up to 4 sub-systems or 1 channel from 5 to 8 sub-systems) Digital audio over DANTE protocol Applications Shopping centres Hospitals Railway stations Airports Congress centres Schools Stadiums Skyscrapers Certifications EN 54-16:2008 (CPR: 0068-CPR-002/2014). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN 60065:

5 TECHNICAL SPECIFICATIONS MAIN IN, INTEGRITY NETWORK INPUT AUDIO INPUTS - Input sensitivity: dbu - Frequency response (±3 db): 20 Hz 20 khz - Input impedance (1 khz): 25 kω - Signal / noise ratio: 104 db - INTGRITY NETWORK command voltage: 24 V dc PAGING IN (1, 2) AUDIO INPUTS - Input sensitivity: dbu - Frequency response (±3 db): 200 Hz 16 khz - Input impedance (1 khz): 4 kω - Signal / noise ratio: 84 db - Paging console power supply: V c.c. AUX INPUT - Input sensitivity: dbu - Frequency response (±3 db): 20 Hz 20 khz - Input impedance (1 khz): 25 kω - Signal / noise ratio: 94 db BGM (1, 2, 3) AUDIO INPUTS - Input sensitivity: dbu - Frequency response (±3 db): 20 Hz 20 khz - Input impedance (1 khz): 25 kω - Signal / noise ratio: 90 db MONITOR OUT, AUX OUT, MOH AUDIO OUTPUTS - Max. output level: 1 W su 8 Ω - Output impedance (1 khz): 60 Ω - Frequency response (±3 db): 20 Hz 20 khz - Distortion 1kHz): 0,01% GPI (LOGIC INPUTS) - Monitored GPI number: 8 - Photo-coupled GPI number: 4 GPO (LOGIC OUTPUTS) - Max. applicable voltage: 24 V c.c. - Max. current: 0,3 A RCF FLEXCOM BUS - Channels: 4 - Resolution: 24 bit - Sampling frequency: 44,1 khz 24 V DC OUTPUT - Max. output current: 100 ma DATA LINK - 1 LAN ETHERNET connector (control) - 2 LAN ETHERNET connector (DANTE Brooklyn II module) - 2 PAGING IN RJ 45 ports - 1 RS485 EUROBLOCK connector - 2 RCF FLEXCOM BUS EUROBLOCK connectors - Operating voltage: V ac (50-60 Hz), 48 V dc - Max. consumption (power): 60 W - Operating temperature: C ( F) - Relative humidity: 20 90% (non condensing) MECHANICAL SPECS. - Dimensions (w, h, d): 485 mm, 88 mm, 365 mm (2 rack units19 ) - Net weight: 6,9 kg MU 9186 MU 9186R 5

6 MX 9502 MX 9504 AMPLIFIED MASTER UNITS p/n p/n MX 9502 and MX 9504 allow the basic system configuration to be built, combining all necessary inputs and outputs, pre-recorded messaging system, EN control and much more: all that is required for a 500W audio system with two or four constant voltage speakers lines, suitable for example, to serve a school, a supermarket, a factory building etc. Main Features Digital matrix unit is 8x6 configurable, with routing to any output channel, is also available with integrated power amplifiers. Priority evacuation messages resident on main control unit protected and monitored memory. Simultaneous delivery is possible. 12 configurable GPI and configurable 8 GPO available on each unit. Control Center PC application to configure and control all system s parameters. Front panel control with LCD display and 8 buttons. Efficient Digital Signal Processors on inputs and outputs; Parametric EQ, High and Low Pass Filters, Compressor / Limiter, Level controls provided on inputs and outputs. The EQ window provides 3-band equalizer for the Background input and the Monitor and Auxiliary Outputs. 5-band equalizer for the Paging input, Auxiliary inputs and BUS Output. For all input channels (EVAC microphone, paging stations, microphones and analog inputs) the Gain, EQ and Dynamic screens will appear in the DSP EDITOR. Fully parametric high and low frequency filters are available for all the inputs and for the Auxiliary Output. Compressor available (Threshold, Attack, Release and Ratio) on the Auxiliary inputs and BUS Output. Dual power supply, allowing both AC and DC operation. RS 485 serial port for optional program remote control and volume adjustment. Power amplifiers based on RCF ClassD+ digital technology, offering industrial reliability grade, the highest efficiency and the lowest maintenance effort. Twin LAN ports for DIGITAL AUDIO IN (1 channel from external source) and OUT (2 channels up to 4 sub-systems or 1 channel from 5 to 8 sub-systems) MP3 built-in music source with USB and SD-Card reader. Applications Shopping centres Hospitals Railway stations Airports Congress centres Schools Stadiums Skyscrapers Certifications EN 54-16:2008 (CPR: 0068-CPR-002/2014). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN 60065:

7 TECHNICAL SPECIFICATIONS MAIN IN, INTEGRITY NETWORK INPUT AUDIO INPUTS - Input sensitivity: dbu - Frequency response (±3 db): 20 Hz 20 khz - Input impedance (1 khz): 25 kω - Signal / noise ratio: 104 db - INTGRITY NETWORK command 24 V d.c. voltage: PAGING IN (1, 2) AUDIO INPUTS - Input sensitivity: dbu - Frequency response (±3 db): 200 Hz 16 khz - Input impedance (1 khz): 4 kω - Signal / noise ratio: 84 db - Paging console power supply: V dc AUX INPUT - Input sensitivity: dbu - Frequency response (±3 db): 20 Hz 20 khz - Input impedance (1 khz): 25 kω - Signal / noise ratio: 94 db BGM (1, 2, 3) AUDIO INPUTS - Input sensitivity: dbu - Frequency response (±3 db): 20 Hz 20 khz - Input impedance (1 khz): 25 kω LOUDSPEAKER LINE OUTPUTS - Output voltage: 100 V / 70 V (selectable by RCF only) - Number of internal amplifiers: 2 (MX 9502), 4 (MX 9504) - Max. power of each amplifier: 250 W (MX 9502) 125 W (MX 9504) - Load minimum impedance for each amplifier: [100 V] 40 Ω (MX 9502) [70 V] 80 Ω (MX 9504) 20 Ω (MX 9502) 40 Ω (MX 9504) - Loudspeaker line outputs: A1 - A2 - B1 - B2 (MX 9502) A - B - C - D (MX 9504) - Frequency response (±3 db): 20 Hz 20 khz - Distortion 1kHz): 0.1% MONITOR OUT, AUX OUT, MOH AUDIO OUTPUTS - Max. output level: 1 W on 8 Ω - Output impedance (1 khz): 60 Ω - Frequency response (±3 db): 20 Hz 20 khz - Distortion 1kHz): 0.01% GPI (LOGIC INPUTS) - Monitored GPI number: 8 - Photo-coupled GPI number: 4 GPO (LOGIC OUTPUTS) - Max. applicable voltage: 24 V dc - Max. current: 0.3 A - Dimensions (w, h, d): 485 mm, 88 mm, 365 mm (2 unità rack 19 ) - Net weight: MX kg MX ,3 kg MX 9502 SERIAL NUMBER W ARNING AC V OLTAGE SELECTOR AND FUSE INSIDE,REFER TO INSTRUCTION MANUAL 48 V 15 A max MAX OUTPUT POWER 500 W RMS MINIMUM LOAD IMPEDANCE 70 V (20 ) V (40 ) LINE A1 LINE A2 LINE B1 LINE B SPEAKER LINE OUT POWER 115/230V ~ 50-60Hz - 60 W max INPUT OUTPUT SPARE AMP BUS Series EN54-16 COMPLIANCE STICKER BUS IN BUS OUT FLEXCOM BUS RELAY OUTPUTS (contact load 0,3A - 24V DC) GENERAL PURPOSE OUTPUTS GND 28V GND CTRL RS485 MX 2x250W MASTER UNIT MONITOR OUT ROUTINE MESSAGES ETHERNET PAGING IN 2 PAGING IN 1 MAIN IN BGM 2 MOH BGM 1 CAUTION RISK OF ELECTRIC SHOCK DO NOT OPEN MONITORED INPUTS PHOTO-COUPLED INPUTS WARNING TO REDUCE THE RISK 24V DC AUDIO CMD OF FIRE OR ELECTRIC SHOCK, DO NOT GND GND EXPOSE THIS EQUIPMENT TO RAIN OR MOISTURE. DO NOT REMOVE COVER. NO USER SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED PERSONNEL. Max 100 ma GENERAL PURPOSE INPUTS AUX INPUT BGM 3 FALL BACK INPUT GND AUX OUT M ADE IN ITALY MX 9504 SERIAL NUMBER W ARNING AC V OLTAGE SELECTOR AND FUSE INSIDE,REFER TO INSTRUCTION MANUAL 48 V 15 A max MAX OUTPUT POWER 500 W RMS MINIMUM LOAD IMPEDANCE 70 V (20 ) V (40 ) LINE A LINE B LINE C LINE D SPEAKER LINE OUT POWER 115/230V ~ 50-60Hz - 60 W max INPUT OUTPUT SPARE AMP BUS Series EN54-16 COMPLIANCE STICKER BUS IN BUS OUT FLEXCOM BUS RELAY OUTPUTS (contact load 0,3A - 24V DC) GENERAL PURPOSE OUTPUTS GND 28V GND CTRL RS485 MX 1x125W MASTER UNIT MONITOR OUT ROUTINE MESSAGES ETHERNET PAGING IN 2 PAGING IN 1 MAIN IN BGM 2 MOH BGM 1 CAUTION RISK OF ELECTRIC SHOCK DO NOT OPEN MONITORED INPUTS PHOTO-COUPLED INPUTS WARNING TO REDUCE THE RISK 24V DC AUDIO CMD OF FIRE OR ELECTRIC SHOCK, DO NOT GND GND EXPOSE THIS EQUIPMENT TO RAIN OR MOISTURE. DO NOT REMOVE COVER. NO USER SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED PERSONNEL. Max 100 ma GENERAL PURPOSE INPUTS AUX INPUT BGM 3 FALL BACK INPUT GND AUX OUT M ADE IN ITALY 7

8 UP 9504 UP 9502 UP 9501 p/n p/n p/n POWER AMPLIFIERS In order to grant a high installation flexibility and output power on a larger number of zones, DXT 9000 includes three models of RCF ClassD+ power amplifiers, able to deliver up to 500W on 100V or 70V constant voltage speaker lines. In mid-large size systems, models UP 9501 (1 x 500W), UP 9502 (2 x 250W) and UP 9504 (4 x 125W) can be connected to both MX 9502, MX 9504, MU 9186 and MU 9186R through the dedicated RCF-Flexicomm datalink port. Moreover, UP 9501 models can be programmed to become a spare power amplifier for one or more units, and automatically replace them in case of failure. Main Features Power amplifiers and power supply technology used in the system are RCF ClassD+ using digital technology and industrial reliability grade in order to offer the highest efficiency and the lowest maintenance effort. Single and dual channel amplifiers each have two individually managed and monitored speaker outputs. Spare power amplifier connection input present on each unit and the change-over facility for a standby power amplifier unit configurable according to priority and group. Background music and local paging inputs are available. 12 configurable GPI and configurable 8 GPO are available on each unit. Applications Shopping centers Hospitals Railway stations Airports Halls Schools Stadiums Skyscrapers Certifications EN 54-16:2008 (CPR: 0068-CPR-002/2014). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN 60065:

9 TECHNICAL SPECIFICATIONS INTEGRITY NETWORK INPUT AUDIO INPUT - Input sensitivity: dbu - Frequency response (±3 db): 20 Hz 20 khz - Input impedance (1 khz): 25 kω - Signal / noise ratio: 104 db - INTGRITY NETWORK command 24 V dc voltage: AUX INPUT - Input sensitivity: dbu - Frequency response (±3 db): 20 Hz 20 khz - Input impedance (1 khz): 25 kω - Signal / noise ratio: 94 db BGM 3 AUDIO INPUT - Input sensitivity: dbu - Frequency response (±3 db): 20 Hz 20 khz - Input impedance (1 khz): 25 kω LOUDSPEAKER LINE OUTPUTS - Output voltage: 100 V / 70 V (internal selection) - Number of internal amplifiers: 1 (UP 9501) 2 (UP 9502) 4 (UP 9504) - Max. power of each amplifier: 500 W (UP 9501) 250 W (UP 9502) 125 W (UP 9504) - Load minimum impedance for each amplifier: [100 V] 20 Ω (UP 9501) 40 Ω (UP 9502) 80 Ω (UP 9504) [ 70 V] 10 Ω (UP 9501) 20 Ω (UP 9502) 40 Ω (UP 9504) - Loudspeaker line outputs: A1-A2 (UP 9501) A1-A2-B1-B2 (UP 9502) A-B-C-D (UP 9504) - Frequency response (±3 db): 20 Hz 20 khz - Distortion 1kHz): 0.1% GPI (LOGIC INPUTS) - Monitored GPI number: 8 - Photo-coupled GPI number: 4 GPO (LOGIC OUTPUTS) - Max. applicable voltage: 24 V dc - Max. current: 0.3 A RCF FLEXCOM BUS - Channels: 4 - Resolution: 24 bits - Sampling frequency: 44.1 khz 24 V DC OUTPUT - Max. output current: 100 ma - Dimensions (w, h, d): 485 mm, 88 mm, 365mm (2 unità rack 19 ) - Net weight: 7,8 kg (UP 9501), 8,0 kg (UP 9502), 8,3 kg (UP 9504) SERIAL NUMBER MAX OUTPUT POWER 500 W RMS MINIMUM LOAD IMPEDANCE EN V (20 Ω) V (40 Ω) Series UP COMPLIANCE STICKER 4x125W CLASS D + POWER AMPLIFIER LINE A LINE B LINE C LINE D INPUT OUTPUT BUS OUT BUS IN GND 28V GND SPEAKER LINE OUT SPARE AMP BUS FLEXCOM BUS CTRL RS485 MADE IN ITALY 48 V 15 A max POWER 115/230V ~ 50-60Hz W max CAUTION RISK OF ELECTRIC SHOCK DO NOT OPEN WARNING AC VOLTAGE SELECTOR AND FUSE INSIDE,REFER TO INSTRUCTION MANUAL RELAY OUTPUTS (contact load 0,3A - 24V DC) GENERAL PURPOSE OUTPUTS 24V DC Max 100 ma MONITORED INPUTS PHOTO-COUPLED INPUTS GENERAL PURPOSE INPUTS GND AUX INPUT BGM 3 AUDIO CMD GND FALL BACK INPUT WARNING TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS EQUIPMENT TO RAIN OR MOISTURE. DO NOT REMOVE COVER. NO USER SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED PERSONNEL. UP 9504 UP 9502 UP

10 RP 9600 DATA REPEATER p/n RP 9600 Data Repeater is the system component that needs to be inserted between the master unit (either MU 9186 or MU 9186R or MX 9502 or MX 9504) and amplifiers (UP 9501 / UP 9502 / UP 9504) when the bus cable is longer than 180 metres or the system includes more than 15 UP 950x amplifiers. Main Features RCF FLEXCOM BUS 4 Channels. Up to 4 units for each system. Enhance system s flexibility and layouting Fully monitored and EN 54-16/2008 certified Applications Shopping centers Hospitals Railway stations Airports Halls Schools Stadiums Skyscrapers Certifications EN 54-16:2008 (CPR: 0068-CPR-002/2014). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN 60065:

11 TECHNICAL SPECIFICATIONS RCF FLEXCOM BUS - Resolution: 24 bits - Sampling frequency: 44.1 khz DATA LINK - LAN ETHERNET connector 1 - RCF FLEXCOM BUS EUROBLOCK connectors 2 ELECTRICAL SPECS. - Operating voltage: 115 /230 V ac (50-60 Hz), 48 V dc - Max. consumption (power): 60 W - Operating temperature: C ( F) - Relative humidity: 20 90% (non condensing) MECHANICAL SPECS. - Dimensions (w, h, d): 485 mm, 88 mm, 365 mm (19 rack 2 units) - Net weight: 6.5 kg BGM (1, 2, 3) AUDIO INPUTS - Input sensitivity: dbu - Frequency response (±3 db): 20 Hz 20 khz - Input impedance (1 khz): 25 kω - Signal / noise ratio: 90 db MONITOR OUT, AUX OUT, MOH AUDIO OUTPUTS - Max. output level: 1 W on 8 Ω - Output impedance (1 khz): 60 Ω - Frequency response (±3 db): 20 Hz 20 khz 11

12 BM 9802 BM 9804 BM 9804 FM BE 9808 p/n p/n p/n p/n SELECTIVE CALL PAGING MICROPHONES The BM 9000 series microphone consoles for announcements are part of the DXT 9000 digital system, and can be directly connected to all master units. User can send announcements to different pre-configured zones or groups of zones, recall matrix configurations, intervene on sound levels, select music sources in different areas, send routine messages or alarms stored in the system memory or explore other possibilities. BM 9804 is also available in Firemen version, hosted in a closed wall mounting red metal cabinet, with glass door to access console status. This version is equipped with dynamic microphone, with incorporated push to talk button, and can be used in combination with a BE 9808 (also installed inside the cabinet), to improve selective calls efficiency. Main Features Up to 8 microphone consoles can operate on each dedicated connection line. Their configuration in terms of access can be set by the PC system interface. Die-cast metal enclosure with 420 mm gooseneck. Pre-amplified hyper-cardioid hi-quality microphone with integrated compressor and limiter to get intelligible announcements even in critical ambients. Programmable function keys for announcements or commands. Power supply voltage from the Flexicomm BUS or from 24V DC local input. Interactive LCD backlit display associated to an encoder that indicates which operations are active and recovers system information. Alert and evacuation indications. Pre-recorded message activation. 5m connecting cable (with RJ 45 plugs) included. Dedicated chime key. Applications All DXT 9000 applications Certifications EN 54-16:2008 (CPR: 0068-CPR-002/2014). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN 60065:

13 TECHNICAL SPECIFICATIONS BM BM 9804 BM 9804FM Type: electret Dynamic Polar pattern: cardioid Omni-Directional Output impedance: 470 Ω (1 khz) 500Ω±30% (1KHz) Microphone sensitivity: 65 db ± 3 db (0 db=1v/μbar, 1 khz) -70 db ± 3 db (0 db=v/ μbar, 1 khz ) Frequency response: 50 Hz 18 khz ( 3 db) 300 Hz 6 khz ( 3 db) Dimensions: 128 x 39 x 203 mm (without gooseneck) 360 x 360 x 129 mm Gooseneck length: mm - Net weight 1.2 kg (2.7 lbs) 6.9 kg (15.2 lbs) BE 9808 Powered by BM 9802 / BM 9804 paging microphone. Max. current draw: 80 ma (one BE 9808 keyboard only) Dimensions: 78 mm x 39 mm x 203 mm Net weight 0.7 kg (1.6 lbs) BM 9802 BM 9804 BM 9804FM BE 9808 NS 9048 NOISE SENSOR p/n NS 9048 is a noise detector that automatically adjust the volume level depending on the environment noise. It is specifically addres-sed to all those applications with a significantly different people affluence during the day. It shall be connected to any DXT 9000 power amplifiers and can act on every single system s zones, measured with a variable number of microphones (up to a maximum of 8). Main Features Up to 8 microphones can be connected on the rear panel. Specifically designed to work with for 100V speakers used as microphones. However, it can also be used with capsule microphones. Up 2 units can be connected to the same DXT 9000 amplifier. Presence led for each microphone. DATA and LINK leds on the front panel provide feedback on theconnection and data exchange with DXT 9000 amplifiers. Metal case suitable for ceiling and rack installation. All connectors on the rear panel, for easier cabling in rack configuration. Operational voltage: 24V DC or 48V DC from EN54-4 power supplies (PS 4048 or PS 6048). RS485 maximum distance: 8km, with properly shielded and twisted cable pairs. Configurable via PC software. 13

14 IN 9000 INTEGRITY NETWORK CONSOLE p/n IN 9000 EMERGENCY CONSOLE is designed to be interfaced with the evacuation system DXT9000, in order to provide an analog backup solution for emergency communications in case of interruption of the main digital connection RCFBUS. The console is equipped with a monitored FIREMAN microphone with PTT button. The PTT command is also implemented as dedicated button on the front panel, together with a Vumeter on the microphone signal and a on air indication light. IN 9000 can be powered by an external power supply EN54-4 providing at least 20W output power. Moreover, a monitored GPI is provided to report any power supply fault. The audio output can be distributed up to 64 DXT9000 units, and routed on 4 independent lines, selectable on console front panel. Main Features Fully analogue redundancy in the event of interruption by the RCF-Flexicomm bus. Monitored fireman s microphone with PTT button Output signal distributed up to 64 DXT 9000 units over 4 selectable independent lines. Powered by 24V to 48V external supply providing at least 20W output power Applications Shopping centers Hospitals Railway stations Airports Halls Schools Stadiums Skyscrapers Certifications EN 54-16:2008 (CPR: 0068-CPR-002/2014). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN 60065:2002. EOL 3-9 END OF LINE p/n p/n MSW 9000 p/n SW SOFTWARE MONITORING DXT 9000 MS9000 DXT9000 MONITORING SOFTWARE 20 Hz resonator, with an impedance of 200 Ohm at the resonance frequency Installed after the last speaker, it allows to accurately monitor speakers lines integrity. Suitable for DXT3000 and DXT9000 systems. It allows remote monitoring of the DXT 9000 system by the personnel assigned to its management and control Provides real-time information on system status via a web page Provides notification functionality via SMS (subscription service) in conjunction with fault, alarm or evacuation events 14

15 DXT CONFIGURATION EXAMPLES SMALL SIZE SYSTEM BM 9804FM FAS VVFF BM BE 9808 SPEAKERS LINES 100V MX 9504 BM BE 9808 PC MS 1033 bipolar cable 100 V input cable bus system cable MEDIUM SIZE SYSTEM BM 9804FM FAS VVFF BM BE 9808 SPEAKERS LINES 100V MU 9186R UP 9502 BM BE 9808 PC UP 9501 MS 1033 UP 9504 UP 9501 SPARE AMP bipolar cable 100V input cable bus system cable 15

16 DXT CONFIGURATION EXAMPLES LARGE SIZE SYSTEM SYSTEM 1 BM 9804FM FAS VVFF BM BE 9808 SPEAKERS LINES 100V MU 9186R UP 9502 SYSTEM 3 BM BE 9808 Audio input UP 9501 To other subsystem units MS 1033 SWITCH UP 9502 UP 9501 MU 9186R SPARE AMP SWITCH PC / BMS SYSTEM 2 SWITCH SPEAKERS LINES 100V SWITCH To other subsystem units UP 9502 BM 9802 MU 9186R MU 9186R BM 9804 BE 9808 UP 9504 SWITCH MS 1033 SYSTEM 4 UP 9501 SPARE AMP bipolar cable 100V input cable bus system cable redundant ethernet 16

17 DXT 7000 MEDIUM SIZE APPLICATIONS DXT 7000 is a sound system conceived to completely control and manage background music and paging, even for emergency and evacuation purposes. The system has been designed to fulfil all requirements of EN and EN standard, and it is really scalable, suitable for a wide range of applications: up to 32 MU 7100EN can be linked together in order to get an extended system, including many paging stations and up to 256 loudspeaker lines / paging zones. The main unit can play all necessary evacuation and alarm messages previously stored into its built-in digital memory. SPARE AMPLIFIER CHANGE OVER BOARD The line transformer interface override voltage output is used to activate the relay in case of the main amplifier is faulty. PATH MONITORING The whole signal path from fireman s microphone to loudspeaker lines is completely and automatically monitored against faults. The 8 internal digital amplifiers are highly reliable and their efficiency is excellent (> 90%): that means less heat dissipation and smaller capacity required for unbreakable power supply sources (UPS) used in security applications. A digital Matrix 7x8 is configurable for several applications with routing to any output channel, supported by an efficient Digital Signal Processor (DSP) providing Band Parametric EQ, Filters, Delay circuit for line arrays, Compressor / Limiter and Level controls. A software utility is available for saving unit parameters to PC, updating unit firmware, virtual control activation and status indication. 17

18 MU 7100EN DIGITAL MATRIX DXT 7000 p/n MU 7100 is the main unit of the RCF DXT 7000 system, which has been designed to fulfill all requirements of EN and EN standard. The whole signal path from fireman s microphone to loudspeaker lines is completely and automatically monitored against faults. All properties and functions of the system are specified with Windows based DXT 7000 configuration software and are downloaded to master unit through its USB port. Main Features Up to 32 units can be linked together in order to get an extended the systems Up to 256 loudspeaker lines and many paging stations The 8 digital internal amplifiers are highly reliable and excellent efficiency Small capacity requirement for unbreakable power supply sources (UPS) used in security applications The main unit can play all necessary evacuation and alarm messages previously stored into its built-in digital memory Digital Matrix 7 x 8 is configurable for several applications with routing to any output channel An automatic level control facility can be got by simply connecting an omnidirectional noise detection microphone to the inputs Efficient Digital Signal Processor (DSP): 5-Band Parametric EQ, High and Low Pass Filters, Compressor / Limiter, Level controls are provided Delay circuit for line array speaker applications Built-in WAV file message player (up to128 messages) Applications Shopping centers Hospitals Railway stations Airports Halls Schools Stadiums Skyscrapersw Certifications EN 54-16:2008 (CPR: 1438-CPR-0241). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN :

19 TECHNICAL SPECIFICATIONS Analogue input 1 7 sensitivity Analogue input impedance System and local bus audio (balanced) Digital message signal format (WAV) Frequency response ( 1 db) S/N ratio khz Continuous 8 Ω all ch. driven < 1%THD Speaker output nominal impedance Mains operating voltage dbu 20 kω (bilanciato) S/PDIF + 6 dbu ris. 16 bit, freq. camp. 32 khz 20 Hz 20 khz 96 dba < 0,05% 8 x 80W RMS 8 Ω Mains type connector VAC, Hz Power consumption (ac) Classe I Power factor at full load W Mains fuses 5x20mm tipico 0,95 Secondary operating voltage 2 x T3.15A Operating temperature ºC 20 90% RH non-condensing Dimensions (w, h, d) 485 mm, 86mm, 375 mm Net weight 8,4 kg V 45-63Hz W 3,15T 3,15T RS-232 SPEAKER OUTPUTS 80OHM/150W 24VDC 48VDC 2x7A CH2 CH3 CH4 CH5 CH6 CH7 OUT IN IN CH1 CH8 SYSTEM LOCAL CTRL OVERRIDE AUDIO OUT LT 7208 MIC/LINE INPUT CONTROL OUTPUT SR No LOCAL SYSTEM USB BUS BUS LINK CONTROL INPUT MT 7308EN POWER AMPLIFIER MANAGER p/n MT 7308 is suitable to control up to 8 additional power amplifiers and relevant speaker lines, according to EN norm. It works connected to the MU 7100EN master system unit. When speaker lines drive high power loads, it could be convenient to optimize the system configuration by using one or more dedicated power amplifiers dimensioned according the loads involved. Main Features Integrates external (constant voltage) amplifiers into the monitored DXT 7000EN voice evacuation system. It is possible to use any professional single / multichannel amplifier equipped with a 0 6 dbu balanced audio input and 50/70/100 V constant voltage output(s). One or two MT 7308EN can be linked to each MU 7100EN main unit. One unit can be used for up to eight external amplifiers (and its loudspeaker line monitoring). Max. power for each external amplifier: 500 W. Spare amplifier facility on dip-switch with automatic replacement of a faulty one. Half 19 rack unit, so two MT 7308EN can be installed into 19 1U rack. PC configuration software and communication on local bus with host MU 7100EN Certifications EN 54-16:2008 (CPR: 1438-CPR-0241). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN :

20 LT 7208EN LINE TRANSFORMER INTERFACE p/n The LT 7208EN unit has 8 internal transformers (80 W / each) to convert the 8 Ohm loudspeaker outputs of the MU 7100 central unit into constant voltage lines ( V) for loudspeakers having transformers. The possible combinations are 8 x 80W, 4 x 160 W and 2 x 320W (or any combination from these). Main Features Applications Shopping centers Hospitals Railway stations Airports Halls Schools Stadiums Skyscrapers TECHNICAL SPECIFICATIONS Input impedance 8 Ω Output voltage 100 V (on request: V) Max. power (single output) 80 W Dimensions (w, h, d) 483 mm, 88 mm, 382 mm (19 two-unit rack) Net weight 13 kg Certifications EN 54-16:2008 (CPR: 1438-CPR-0241). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN :2002. SR No LOW IMPEDANCE INPUTS 24VDC CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 IN CTRL IN LINE 1 LINE 2 SPEAKER LINE OUTPUTS 50/70/100V LINE 3 LINE 4 LINE 5 LINE 6 LINE 7 The LT 7208EN line transformer interface allows you to link/ group the 8 amplifiers to increase the power of the speaker lines two, three or four times If the needed speaker line power is more than 80W, several outputs (in groups made of 2, 3 or 4) can be connected together (in parallel) in order to get locked groups for 160 W, 240 W or 320 W lines Output line voltage setting ( V) is made by changing the output tapping of each transformer Includes also line specific 24V dc outputs for override relays (max. current: 1A / line) Connection cable to MU 7100EN main unit 8 pcs. of end of line unit, used when the loudspeaker line monitoring is provided The end of line unit shall be installed right at the end of the line, near the last installed loudspeaker OVER- RIDE OVER- RIDE OVER- RIDE OVER- RIDE OVER- RIDE OVER- RIDE OVER- RIDE LINE 8 OVER- RIDE 20

21 21

22 UP 8501 UP 8502 UP 8504 p/n p/n p/n DIGITAL POWER AMPLIFIERS Our class D amplifiers with selectable V output per channel provide pro audio performance with double switching AC-DC power supply and transformer-less galvanic insulated speaker output. They are equipped with double input per channel, active full protections on amplifier and power supply, activity and status indicators, as well as stand-by, priority and fault remote commands. They are equipped with volume knobs on front panel with disablement facility and characterized by a light-weight 1 U 19 rack enclosure. UP 8501, UP 8502 and UP 8504 are EN certified only when combined with DXT Certifications EN 54-16:2008 (CPR: 1438-CPR-0241). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN :

23 Serial No.: Serial No.: Serial No.: TECHNICAL SPECIFICATIONS UP 8501 UP 8502 UP 8504 No. Channels x output power (rms) 1 x 500 W 2 x 250 W 4 x 125 W Frequency response 40 HZ 16 khz Band-pass filter (12 db / oct) 200 HZ 8 khz Thd and noise (at max. Power) MAX. 0.3% Signal / noise ratio (iec-a) 86 DB Input 1 sensitivity 0 dbu (775 mv, max. 7 V) Input 2 sensitivity 0 20 dbu ( mv, max. 7 V) In test sensitivity 0 dbu (775 mv) Input impedance 10 kω Minimum load impedance of each 70 v line 10 Ω 20 Ω 40 Ω Minimum load impedance of each 100 v line 20 Ω 40 Ω 80 Ω Over signal limiter overload, short circuit, overheating Operating voltage V c.a. ±10%, Hz (internal voltage selector) Batteries: 48 V d.c. ±10% Power consumption, ac stand-by 3 W Power consumption, disabled amp. 13 W 15 W 20 W Power consumption, no input signal 25 W 36 W 50 W Power consumption, musical signal 160 W Power consumption, max. Output power 650 W Power consumption, max. Overload 800 W Operating temperature 0 55 C; Humidity: max 90% Dimensions (w, h, d) 482 mm, 44 mm, 375 mm (1 rack unit 19 ) Net weight 5.2 KG 5.4 KG 5.6 KG UP 8501 UP 8502 AC VOLTAGE SELECTOR AND FUSE INSIDE, REFER TO INSTRUCTION MANUAL MADE IN ITALY V dc - 15 A max Status Overload Stand-By / ON Disable Amplifier GND b INPUT 1 a GND GAIN D VOL PRIOR GND IN INPUT 2 INPUT 1 VOL PRIOR GND IN INPUT 2 1 > 2 Test> 1+2 GND 1 > 2 Test> 1+2 GND 115/230V - 50/60Hz W max INPUT 1 VOL PRIOR GND IN INPUT 2 INPUT 1 VOL PRIOR GND IN Rem Vol Test GND R b/l a - + IN 2D GAIN B - + b a GND Rem Vol Test GND R b/l INPUT 2 a GAIN C - + IN 2C GAIN A - + IN 2A OFF 100V OFF 100V B Fltr OFF D Fltr B 70V 100 V D 70V A Fltr OFF C Fltr A 70V 100 V C 70V OFF Master Volume AMP D MAX OUTPUT POWER 125 W RMS MINIMUM LOAD IMPEDANCE 70 V (39 ) v (80 ) a b a b AMP C AMP B AMP A SPEAKER LINE OUTPUT a b a b UP 4x125W POWER AMPLIFIER AC VOLTAGE SELECTOR AND FUSE INSIDE, REFER TO INSTRUCTION MANUAL MADE IN ITALY V dc - 15 A max Status Overload Stand-By / ON Disable Amplifier GND b INPUT 1 a GND GAIN D VOL PRIOR GND IN INPUT 2 INPUT 1 VOL PRIOR GND IN INPUT 2 1 > 2 Test> 1+2 GND 1 > 2 Test> 1+2 GND 115/230V - 50/60Hz W max INPUT 1 VOL PRIOR GND IN INPUT 2 INPUT 1 VOL PRIOR GND IN Rem Vol Test GND R b/l a - + IN 2D GAIN B - + b a GND Rem Vol Test GND R b/l INPUT 2 a GAIN C - + IN 2C GAIN A - + IN 2A OFF 100V OFF 100V B Fltr OFF D Fltr B 70V 100 V D 70V A Fltr OFF C Fltr A 70V 100 V C 70V OFF Master Volume AMP D MAX OUTPUT POWER 125 W RMS MINIMUM LOAD IMPEDANCE 70 V (39 ) v (80 ) a b a b AMP C AMP B AMP A SPEAKER LINE OUTPUT a b a b UP 4x125W POWER AMPLIFIER UP 8504 AC VOLTAGE SELECTOR AND FUSE INSIDE, REFER TO INSTRUCTION MANUAL MADE IN ITALY V dc - 15 A max Status Overload Stand-By / ON Disable Amplifier GND b INPUT 1 a GND GAIN D VOL PRIOR GND IN INPUT 2 INPUT 1 VOL PRIOR GND IN INPUT 2 1 > 2 Test> 1+2 GND 1 > 2 Test> 1+2 GND 115/230V - 50/60Hz W max INPUT 1 VOL PRIOR GND IN INPUT 2 INPUT 1 VOL PRIOR GND IN Rem Vol Test GND R b/l a - + IN 2D GAIN B - + b a GND Rem Vol Test GND R b/l INPUT 2 a GAIN C - + IN 2C GAIN A - + IN 2A OFF 100V OFF 100V B Fltr OFF D Fltr B 70V 100 V D 70V A Fltr OFF C Fltr A 70V 100 V C 70V OFF Master Volume AMP D MAX OUTPUT POWER 125 W RMS MINIMUM LOAD IMPEDANCE 70 V (39 ) v (80 ) a b a b AMP C AMP B AMP A SPEAKER LINE OUTPUT a b a b UP 4x125W POWER AMPLIFIER 23

24 BM 7608 BM 7608D BM 7608DFM BM 7624D MICROPHONE CONSOLE p/n p/n p/n p/n Paging microphone set monitored according to EN norm, with metal body and an high intelligibility microphone mounted on a 250mm gooseneck. The 8 configurable buttons can be programmed to send live microphone announcements in specific zones or groups of zones. There are dedicated buttons to access the emergency operation/functions, in order to send prerecorded security messages or microphone announcements. One input on RCA stereo connector is available for the direct connection of a program source (i.e. CD player), to be sent through the same audio cannel where the console is connected when paging is not in progress. The console is powered through the same system bus or through a local optional power supply. High intelligibility microphone with polyurethane foam wind screen. The connection to the MU 7100EN master unit can be made by using a CAT 5 cable or a J-Type 4 twisted pair cable (es. Fire resistant model RCF CJ 428E). Main Features Modern design Monitored microphone Audio input (3.5 mm TRS jack connector) for an external device Up to 32 paging microphones in the entire system, up to 8 for each local bus 2 data bus ports for redundant systems Connections to system / local buses according to the EIA/TIA-568B standard (CAT 5/6/7 wiring) Flexible gooseneck microphone 8 zone / function buttons BM 7608D, BM 7608DFM, BM 7624D: Backlit LCD (menu based user interface) BM 7608D, BM 7608DFM, BM 7624D: Numeric keyboard BM 7608D, BM 7608DFM, BM 7624D: Input selection and volume control through menu Applications Halls Schools Malls Hospitals Train stations Hotels Certifications EN 54-16:2008 (CPR: 1438-CPR-0241). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN :2002. BM 7608 BM 7608D BM 7608DFM BM 7624D 24

25 Frequency response (-3 db) TECHNICAL SPECIFICATIONS BM BM 7608D Hz (mic) Hz (aux) BM 7608DFM - BM 7624D Hz (mic) Hz (aux) Audio input (aux) -14 0dB (adjustable) db (adjustable) Thd + n 1 khz <0,1% <0,1% Connectors RJ 45 RJ 45 Audio output 3,5mm TRS connector 3,5 mm TRS connector EXT. CONTROL removable screw terminals 3 pin removable screw terminals 3 pin AC 7212 SPARE AMPLIFIER CHANGE- OVER BOARD FOR LT 7208EN p/n SI 7120 MONITORED LOGICAL INPUT BOARD FOR MU 7100EN p/n RO 7102 DRY OUTPUT CONTACT BOARD FOR MU 7100EN p/n The board has 2 main V loudspeaker line inputs, spare amplifier input and output, 2 relays. AC 7212 terminal shall be directly connected to a pair of LT 7208EN loudspeaker V outputs. The LT 7208EN override voltage output is used to activate the AC 7212 relay in case of the main amplifier is faulty and switch the spare amplifier output to the respective loudspeaker line. EN 54-16:2008 (CPR: 1438-CPR-0241) The SI 7120 board is a system monitoring module for the DXT 7000 system. It monitors the operation condition of 2 lines coming from the fire alarm system to DXT If a line is open or shorted, the SI 7120 board will detect the fault and activate a command. EN 54-16:2008 (CPR: 1438-CPR-0241) A RO 7102 board can be directly connected to a pair of MU 7100EN control outputs. It converts the 2 MU 7100EN opencollector control outputs to 2 dry closing contacts that can be used as commands or external devices. It also has resistors needed for monitored alarm lines. EN 54-16:2008 (CPR: 1438-CPR-0241) SV 7982 p/n REMOTE PROGRAMME SELECTOR AND LEVEL CONTROL DEVICE LI 7903 REMOTE LOCAL INPUT / CONTROL DEVICE p/n Used as local sound control device. It controls a zone group volume and operates as program selector. Connection to local or system bus by using CAT5/6 cabling. To be wall mounted by using with accessories provided. Used for connection and routing of a local program source (mono signal, 3.5 mm balanced stereo plug). 3 function keys can be individually programmed, for example, to route local program source to desired loudspeaker lines. To be wall mounted by using the accessories provided. 25

26 DXT CONFIGURATION EXAMPLES SMALL SIZE SYSTEM SV 7982 LI 7903 BM 7608D MS 1033 MU 7100 VVFF LT 7802 MQ 50 MQ 50 C DXT MEDIUM SIZE SYSTEMS MQ 50 C MEDIUM SIZE SYSTEM bipolar cable 100 V input cable bus system cable BM 7608D MS 1033 MU 7100 LT 7802 MQ 50 MQ 50 C BM 7608D MS 1033 MU 7100 LT 7802 MQ 50 MQ 50 C MQ 50 C bipolar cable 100 V input cable bus system cable 26

27 DXT CONFIGURATION EXAMPLES LARGE SIZE SYSTEM 27

28 POWER SUPPLIES and SYSTEMS ACCESSORIES FOR DXT9000 and DXT7000 PS 4048 PS VCC POWER SUPPLY ACCORDING TO EN VCC POWER SUPPLY ACCORDING TO EN 54-4 p/n p/n PS 6048 and PS 4048 are power supply units suitable to get continuity power for EN systems units like DXT 9000 and DXT 7000, and relevant complementary devices in case of mains power supply interruptions. They include recharging and monitoring functions for the lead-acid batteries connected to them and are EN certified. They must be equipped with batteries with suitable capacity, dimensioned according to the system power absorption and to the evacuation requirements. According to EN standard, PS 6048 and PS4048 shall be installed into the same rack cabinet where there is the audio system with emergency purposes (or a system part) to which it is connected. EN 54-4: A1: A2: 2006 (CPR: 0333-CPD ) for PS 4048 EN 54-4: A1: A2: 2006 (CPR: 0333-CPD ) for PS 6048 TECHNICAL SPECIFICATIONS PS 4048 PS 6048 Rated output voltage 48 V DC 48 V DC Output voltage at half load (25 c): 54.4 V dc ±0.5% 54.4 V dc ±0.5% Nominal output current: 8 A 12 A Nominal power 400 W 7200 W (Jumper set to 75 ), 4800 W (Jumper set to 50) Battery voltage 48 V DC (4 x 12 V) 48 V DC (4 x 12 V) Authorized battery capacity Ah Ah (Jumper set to 75 ), Ah (Jumper set to 50) CJ 228E FIRE RESISTANT DATA CABLE p/n p/n CJ 428E FIRE RESISTANT DATA CABLE Fire resistant cables for data with conductor thickness of 0.8 mm shielded. Color of the outer cover Red. Inner conductors colors Yellow, Grey, Blue, Red. Certification VDE 0815, DIN 4102, EN PH 120, EN , EN , FIPEC (EN) Coils of 200 m. The construction process consists in conductors isolation using a layer of silicon rubber. The core is then separated into two twisted pairs together and screens, subsequently the outer sheath is applied with a process of compression seeds. 28

29 DXT 3000 SCALABLE COMPACT SOLUTION DXT 3000 is a wall-mounting intelligent evacuation system dedicated to small and medium size applications, where an EN54-16 system is required. It includes a digital DSP-based master unit equipped with up to 6 RCF Class D+ power amplifiers, able to provide up to 250W on 100V or 70V speaker lines. A spare power amplifier with automatic replacement of a faulty unit is configurable too. MX 3250 hosts batteries and the necessary EN54-4 circuitry for the DC back-up. Furthermore it offers inputs, controls and pre-recorded messages to get a real plug & play solution. ADVANCED TECHNOLOGY Digital DSP-based master unit equipped with 2, 4 or 6 RCF Class D+ technology power amplifiers. MONITORED PAGING CONSOLE BM 3804, a low power consumption monitored console, suitable for selective emergency paging and message triggering. Monitored paging consoles and 6 button extensions allow to complete the installation by adding live announcements. Local single-button paging microphones and background music programs can be implemented as well. The system can be expanded to fit with middle size applications, centralized or distributed connecting up to eight using a dedicated interlink accessory board. DXT 3000 system has been designed to be wired by using very convenient fire-rated J-TYPE cables for paging console and interlink connections. 29

30 MX 3500/2 MX 3500/4 MX 3500/6 MASTER UNITS WITH AMPLIFIERS p/n p/n p/n MX 3500 is the master unit of the evacuation system DXT 3000, dedicated to small and medium size applications, with double power compared to MX As the smaller model, it includes a digital DSP-based master unit equipped with up to 6 RCF Class D+ power amplifiers, able to provide up to 500W on 100V or 70V speaker lines. Furthermore it offers inputs, controls and pre-recorded messages to get a real plug & play solution, included a music source easily accessible from the front panel. All other features, included scalability through IE 3008, are the same of MX Main Features DSP-based Master Unit Equipped with 2, 4 or 6 RCF Class D+ technology power amplifiers. A/B speakers lines Spare power amplifier with automatic replacement Internal power supply with battery charger and space for batteries. Emergency messages on monitored SD card. Applications Halls Schools Shopping Centers Offices Public buildings Accessories Rack lateral support Certifications CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN 60065:2002. EN 54-16:2008 / EN 54-4: A1: A2: 2006: certification in progress. 30

31 TECHNICAL SPECIFICATIONS OUTPUT POWER Frequency response: Distortion (THD + N): Output voltage to speaker lines: Signal / noise ratio: Operating voltage (mains): Operating voltage (batteries): Nominal Load Mains Input Power Battery Input Current Battery Capacity Ambient operating temperature Up to 500W distributed on 2, 4 or 6 zones (max 250W per zone) Hz (± 1 db) < 1 khz 100 V, 70 V > 80 dba 115/230V +10/-15% 50/60Hz Internal setting 48Vdc (4x12V) Ri max= 440mΩ Rl=20/10Ω ; Cl=10nF 700W max A max 4 x 12 Ah (int. setting) 40 C max Max. number of daisy-chained BM 3804 paging microphones 4 Simultaneous audio channels 3 Paging microphone cable Integrated audio player: Dimensions (w, h, d) CAT 6 FTP or J-type (RCF) SD card, USB pen drive, 3.5mm jack aux input 430 mm, 620 mm, 180 mm (19 rack 14 units) MX 3500 is equipped with an integrated audio source, directly accessible from the unit front panel and connected to the BGM input. The source, which supports mp3 files only, includes an SD card reader, a USB pen drive reader and an auxiliary input on 3.5 mm jack. In addition to the inputs, the front panel offers also the basic controls for track selection and the pause command. Moreover, a monitor output is available on 3.5 mm jack, and allows checking the audio content before send it to the speakers lines. After control, audio shall be activated manually using the AUDIO ON button (also indicated by LED). 31

32 MX 3250/2 MX 3250/4 MX 3250/6 p/n p/n p/n MASTER UNITS WITH AMPLIFIERS MX 3250 is the master unit of the DXT 3000 evacuation system, dedicated to small and medium size applications, where an EN54-16 system is required. It includes a digital DSP-based master unit equipped with 2, 4 or 6 RCF Class D+ power amplifiers, able to provide up to 250W on 100V or 70V speaker lines. A spare power amplifier with automatic replacement of a faulty unit is configurable too. It hosts batteries and the necessary EN54-4 circuitry for the DC back-up. Furthermore it offers inputs, controls and pre-recorded messages to get a real plug & play solution. The system can be completed with BM 3804 monitored paging consoles and 6 BE 3806 button extensions, allowing to complete the installation by adding live announcements. Local single-button paging consoles (not monitored) BM 3022 and background music programs can be implemented as well. DXT 3000 system has been designed to be wired by using very convenient fire-rated J-TYPE cables for paging console and interlink connections. Main Features DSP-based Master Unit Equipped with 2, 4 or 6 RCF Class D+ technology power amplifiers. Spare power amplifier with automatic replacement Internal power supply with battery charger and space for batteries. Emergency messages on monitored SD card. Applications Halls Schools Shopping Centers Offices Public buildings Accessories Rack lateral support Certifications EN 54-16:2008 / EN 54-4: A1: A2: 2006 (CPR: 0068-CPR-007/2015). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN 60065:

33 TECHNICAL SPECIFICATIONS OUTPUT POWER Frequency response: Distortion (THD + N): Output voltage to speaker lines: Signal / noise ratio: Operating voltage (mains): Operating voltage (batteries): Nominal Load Mains Input Power Battery Input Current Battery Capacity Ambient operating temperature Up to 250W distributed on 2, 4 or 6 zones Hz (± 1 db) < 1 khz 100 V, 70 V > 80 dba 115/230V +10/-15% 50/60Hz Internal setting 24Vdc (2x12V) Ri max= 220mΩ Rl=40/20Ω ; Cl=5nF 400W max. 18A max Ah (int. setting) 40 C max Max. number of daisy-chained BM 3804 paging microphones 4 Simultaneous audio channels 3 Paging microphone cable Dimensions (w, h, d) CAT 6 FTP or J-type (RCF) 430 mm, 530 mm, 180 mm (19 rack 12 units) AC BAT 18 BATTERIES p/n EOL 3-9 END OF LINE p/n Pair of sealed lead acid batteries (12V - 18Ah each.) IE 3008 p/n DXT 3000 INTERLINK BOARD 20 Hz resonator, with an impedance of 200 Ohm at the resonance frequency. Installed after the last speaker, it allows to accurately monitor speakers lines integrity. Suitable for DXT3000 and DXT9000 systems. MG 3006 p/n MONITORED GPI BOARD It allows connecting up to 8 MX 3250 units, in a MASTER/SLAVE configuration. The system units communicate over 2 eight poles euroblock connectors, in order to guarantee a fully redundant network. Local paging for non-emergency purpose is also possible. MG 3006 is an additional monitored GPI board for the MX 3250 main unit (DXT 3000 system). It allows to monitor emergency system general purpose inputs (GPI), and detect (and report) any open line or short circuit along the path between DXT 3000 and other alarm devices, such as alarm buttons. MG 3006 is installed inside the MX 3250 cabinet, and powered (24V) directly by the system. 33

34 BM 3804 BM 3804 FM BE 3806 p/n p/n p/n DESKTOP PAGING MICROPHONES BM 3804 is a desktop paging microphone exclusively dedicated for the RCF DXT 3000 system. It can be directly connected to the MX 3250 main unit through a fourpair J-type fire-rated cable. Up to four interlocked BM 3804 paging microphones can be linked (daisy-chained) to the line. The first BM 3804 paging microphone (of the line) is directly powered by the MX 3250 main unit, while the second, the third and the fourth need 24 V dc adapters (500 ma, i.e. RCF AC AD 2405, optional). BM 3804 is also available in Firemen version, hosted in a closed wall mounting red metal cabinet, with glass door to access console status. This version is equipped with dynamic microphone, with incorporated push to talk button, and can be used in combination with a BE 3806 (also installed inside the cabinet), to improve selective calls efficiency. BE 3804 can be directly connected to the MX 3250 main unit through a fourpair J-type fire-rated cable. Main Features Up to 8 microphone consoles can operate on each dedicated connection line. Their configuration in terms of access can be set by the PC system interface. Die-cast metal enclosure with 420 mm gooseneck. Pre-amplified hyper-cardioid hi-quality microphone with integrated compressor and limiter to get intelligible announcements even in critical ambients. Programmable function keys for announcements or commands. Power supply voltage from the Flexicomm BUS or from 24V DC local input. Interactive LCD backlit display associated to an encoder that indicates which operations are active and recovers system information. Alert and evacuation indications. Pre-recorded message activation. 5m connecting cable (with RJ 45 plugs) included. Dedicated chime key. Applications Shopping centers Hospitals Railway stations Airports Halls Schools Stadiums Skyscrapers Certifications EN 54-16:2008 (CPR: 0068-CPR-007/2015). CE in compliance with EU directives 2004/108/CE (EMC) and 2006/95/CE (LVD). EMC according to IEC EN A1+A2, IEC EN A2+EC, EN , EN A1. LVD according to IEC EN 60065:

35 DR 5301 Data Repeater PB 5310 Power Bridge DR 5301-P Data Repeater for Power Bridge TECHNICAL SPECIFICATIONS BM 3804 BM 3804 FM Microphone type: electret dynamic Polar patter: cardioid omnidirectional Output impedance: 470 Ω (1 khz) 500 Ω ± 30% (1 khz) Microphone sensitivity: 65 db ± 3 db (0 db=1v/μbar, 1 khz) 70 db ± 3 db (0 db=1v/μbar, 1 khz) Frequency response: 50 Hz 18 khz ( 3 db) 300 Hz 6 khz ( 3 db) Power supply: TECHNICAL SPECIFICATIONS 24 V dc (MX 3250 or RCF AC AD2405 external adapter) 24 V dc (MX 3250 Dimensions: 128 x 39 x 203 mm (without gooseneck) 360 x 360 x 129 mm Gooseneck length: mm - Net weight: 1.2 kg (2.7 lbs) 6.9 kg (15.2 lbs) MU MT BM SPECIFICATIONS BM 3806 Power supply: through the BM 3804 paging microphone Dimensions: 78 mm x 39 mm x 203 mm Net weight: 0.7 kg (1.6 lbs) BM BM 3804FM BE 3806 BM BE PU MS GENERAL 39 78ALARM (mm) n DR PB GENERAL MU ZONE ALARM CONFIGURATION WITH MG 3006 GENERAL ALARM 63 n 1 LT B A ZONE (mm) MS BM 7801FM n BM 3804 n MS 1033 BM MS n1033 BM 3804 B A 1 B BM 3022 A ZONE 2 (mm) 1 B A B A GENERAL ALARM BM BM 3804 B A BM 3022 BM bipolar cable 100V input cable ZONE 1 BM bipolar cable 100V input cable ZONE 1 Emergency button Internal resistor n bipolar cable 100V input cable ZONE 1 Emergency button Internal resistor 470 Ohm E bipolar cable 100V input cable Emergency button Internal resistor 470 Ohm End of line resistor 4.7 kohm 35

36 DXT CONFIGURATION EXAMPLES BASIC CONFIGURATION VVFF ZONE 2 MS 1033 B A BM 3804 B A BM 3022 ZONE 1 bipolar cable 100 V input cable EXTENDED CONFIGURATION MS 1033 VVFF ZONE 4 ZONE 3 B A BM 3804 BE 3806 B A B A B A BM 3022 ZONE 2 ZONE 1 BM 3022 bipolar cable 100 V input cable bus system cable 36

37 37

38 PL 82EN p/n WAYS CEILING SPEAKER FIRE DOME The PL 82EN is a 2 ways ceiling speaker featuring a flameproof steel bottom designed for recess installation in false ceilings or panels. It is especially suitable for broadcasting alarm messages thanks to highly intelligible sound reproduction and it is resistant to the high temperatures reached during fires. The terminal connection boards are in ceramic material for input and output flameproof cables. A thermal fuse protects the integrity of the line in case of heat affecting the speaker. Ground screw. Cables inside speaker made using flameproof leads. Main Features Speaker for transmitting alarm voice messages with high intelligibility and background music. Power (selectable) at 100V: 20 W 10 W 5 W. 8 diameter wide band loudspeaker. Steel protection Fire Dome, terminal strip in ceramic material for connecting flameproof input and output cables, thermal fuse, suitable internal wiring. Structure, front grille, and protection cap in steel, RAL 9016 White. 120 mm 147 mm ø 236 mm ø 272 mm TECHNICAL SPECIFICATIONS Input voltage 100 V (70 V) Power 20 W 10 W 5 W Input impedance (1 khz) 1.67 kω (20 W) 3.33 kω (10 W) 6.67 kω (5 W) Frequency response 130 Hz 20 khz ( 10 db) Sensitivity 94 db (1 W, 1 m), 82 db (1 W, 4 m) Sound pressure level 88 db (1 W, 1 m) Transducer 8 Material Colour Connector Steel Body and grille: white RAL Dome: red Ceramic terminal IP protection grade IP 40 Dimensions ø 270 mm (10.63 ), h: 127 mm (5 ) Net weight 1,8 kg (3.6 lb) 38

39 PL 70EN CEILING SPEAKER FIRE DOME p/n The PL 70EN is a ceiling speaker featuring a flameproof steel bottom designed for recess installation in false ceilings or panels. It is especially suitable for broadcasting alarm messages thanks to highly intelligible sound reproduction and it is resistant to high temperatures that are reached during fires. The terminal connection boards are in ceramic material for input and output flameproof cables. A thermal fuse protects the integrity of the line in case of heat affecting the speaker. Ground screw. Cables inside speaker made using flameproof leads. Main Features EN 54-24:2008 certified (CPR: 1488-CPR-0487/W) Speaker for transmitting alarm voice messages with high intelligibility and background music Music power/rms: 24/6W 6 diameter dual cone wide band loudspeaker Low impedance (8 Ω) or 100V Steel protection Fire Dome, terminal strip in ceramic material for connecting flameproof input and output cables, thermal fuse, suitable internal wiring Structure, front grille, and protection cap in steel, RAL 9003 White 124 mm 137 mm ø 199 mm ø 230 mm TECHNICAL SPECIFICATIONS Input voltage 100 V (70 V) Power 6 W 3 W 1.5 W 0.75 W Input impedance 1.67 kω (6 W) 3.33 kω (3 W) kω (1.5 W) kω (0.75 W) Frequency response 145 Hz 20 khz ( 10 db) Sensitivity 95 db (1 W, 1 m) Sound pressure level 103 db (6 W, 1 m), 91 db (6 W, 4 m) Transducer Material Colour Connector 6 dual-cone Steel Body and grille: white RAL 9003 Dome: red Ceramic terminal IP protection grade IP 40 Dimensions ø 230 mm (9.1 ), H: 127 mm (5 ) Net weight 2 kg (4.4 lb) Notes False ceiling cutout size: ø 205 mm (8.1 ) 39

40 PL 68EN CEILING SPEAKER WITH FIRE DOME p/n The PL 68EN is a ceiling speaker featuring a flameproof steel bottom designed for recess installation in false ceilings or panels. It is especially suitable for broadcasting alarm messages thanks to highly intelligible sound reproduction and is resistant to the high temperatures reached during fires. The terminal connection boards are in ceramic material for input and output flameproof cables. A thermal fuse, protects the integrity of the line in case of heat affecting the speaker. Ground screw. Cables inside speaker made using flameproof leads. Main Features EN 54-24:2008 certified (CPR: 1488-CPR-0486/W) Speaker for transmitting alarm voice messages with high intelligibility and background music Power (selectable) at 100V: 6 W 3 W 1.5 W (power values are halved at 70 V) 6 diameter dual cone wide band loudspeaker Steel protection Fire Dome, terminal strip in ceramic material for connecting flameproof input and output cables, thermal fuse, suitable internal wiring Structure, front grille, and protection cap in steel, RAL 9003 White 90.7 mm 96 mm ø 180 mm ø 220 mm 2.4 mm TECHNICAL SPECIFICATIONS Input voltage 100 V (70 V) Power 6 W 3 W 1.5 W 0.75 W Input impedance 1.67 kω (6 W) 3.33 kω (3 W) kω (1.5 W) kω (0.75 W) Frequency response 130 Hz 20 khz ( 10 db) Sensitivity 94 db (1 W, 1 m), 82 db (1 W, 4 m) Sound pressure level 102 db (6 W, 1 m), 90 db (6 W, 4 m) Transducer Material Colour Connector 6 dual-cone Steel Body and grille: white RAL 9003 Dome: red Ceramic terminal IP protection grade IP 40 Dimensions ø 220 mm (8.6 ), H: 96 mm (3.8 ) Net weight 1,1 kg (2.4 lb) Notes False ceiling cutout size: ø 200 mm (7.9 ) 40

41 PL 50EN p/n CEILING SPEAKER WITH FIRE DOME The PL 50EN is a ceiling speaker featuring a flameproof steel bottom designed for recess installation in false ceilings or panels. It is especially suitable for broadcasting alarm messages thanks to highly intelligible sound reproduction and is resistant to the high temperatures reached during fires. The terminal connection boards are in ceramic material for input and output flameproof cables. A thermal fuse, protects the integrity of the line in case of heat affecting the speaker. Ground screw. Cables inside speaker made using flameproof leads. Main Features Speaker for transmitting alarm voice messages with high intelligibility and background music Power (selectable) at 100V: 6 W 3 W 1.5 W 0,75W. 5 diameter wide band loudspeaker. Steel protection Fire Dome, terminal strip in ceramic material for connecting flameproof input and output cables, thermal fuse, suitable internal wiring. Structure, front grille, and protection cap in steel, RAL 9016 White. 123 mm 136 mm ø 160 mm ø 181 mm TECHNICAL SPECIFICATIONS Input voltage 100 V (70 V) Power 6 W 3 W 1.5 W Input impedance 1.67 kω (6 W) 3.33 kω (3 W) 6.67 kω (1.5 W) Frequency response 130 Hz 15 khz ( 10 db) Sensitivity 94 db (1 W, 1 m) Sound pressure level 100 db (6 W, 1 m) Transducer 5 Material Steel Colour Body and grille: white RAL 9016 Dome: red Connector Ceramic terminal IP protection grade IP 40 Dimensions ø 180 mm (7.1 ), H: 135 mm (5.3 ) Net weight 1,45 kg (3.2 lb) Notes False ceiling cutout size: ø 200 mm (7.9 ) 41

42 PLP 50EN p/n CEILING SPEAKER WITH PLASTIC FIRE DOME The PLP 50EN is a ceiling speaker featuring a flameproof plastic bottom designed for recess installation in false ceilings or panels. It is especially suitable for broadcasting alarm messages thanks to highly intelligible sound reproduction and is resistant to the high temperatures reached during fires. The terminal connection boards are in ceramic material for input and output flameproof cables. A thermal fuse, protects the integrity of the line in case of heat affecting the speaker. Ground screw. Cables inside speaker made using flameproof leads. Main Features Speaker for transmitting alarm voice messages with high intelligibility and background music. Power (selectable) at 100V: 6W - 3W - 1.5W 5 diameter wide band loudspeaker. Plastic protection Fire Dome, terminal strip in ceramic material for connecting flameproof input and output cables, thermal fuse, suitable internal wiring. Structure, front grille, and protection cap in steel, RAL 9016 White. 66 mm 71 mm ø 144 mm ø 175 mm TECHNICAL SPECIFICATIONS Input voltage 100 V (70 V) Power 6W - 3W - 1.5W Input impedance (1 khz) 1.67 kω (6 W) 3.33 kω (3 W) kω (1.5 W) Frequency response 130 Hz 15 khz ( 10 db) Sensitivity 93 db (1 W, 1 m) Sound pressure level 97 db (6 W, 1 m) Transducer 5 Material Grille: steel Dome: plastic Colour White RAL 9016 Connector Ceramic terminal IP protection grade IP 40 Dimensions ø 115 mm (6,9 ) Net weight 0,9 kg (3.2 lb) 42

43 DP 5EN UNIDIRECTIONAL SOUND PROJECTOR p/n DP 5EN is a 20W, EN certified weatherproof sound projector. It is suitable for all those installations where high intelligibility for alarm messages broadcasting and great sound reproduction quality are required; moreover, thanks to its IP 65 protection grade, it can be installed both indoor and outdoor. A modern and endearing design makes it the perfect product for environments where projectors are intended also as architectural elements and contribute to improve global aesthetics. Main Features EN 54-24:2008 certified (CPR: 0068-CPR-058/2014) 5 full range speaker for alarm voice messages broadcasting and high quality background music ABS cabinet with steel mesh grille. It can be installed both indoors and outdoors (IP 65 protection grade). Equipped with transformer for 100 V (/ 70 V) constant voltage lines. Internal power setting. Ceramic screw terminal for connection. Internal thermal fuse. Color: white. 147 mm 176 mm 183 mm TECHNICAL SPECIFICATIONS 73 mm 261 mm 334 mm Input voltage 100 V (70 V) Power 20 W - 10 W - 5 W W Input impedance 500 Ω (20 W) - 1 kω (10 W) - 2 kω (5 W) - 4 kω (2.5 W) Frequency response 100 Hz 20 khz Sensitivity 88 db (1 W, 1 m), 76 db (1 W, 4m) Sound pressure level 101 db (20 W, 1 m), 89 db (20 W, 4 m) Transducer Material Colour Connector 5 full range Body: ABS Grille: steel White Ceramic terminal IP protection grade IP 65 Dimensions Net weight ø 180 mm (7.1 ), depth: 260 mm (10.2 ) (without bracket) 2.6 kg (5.75 lb) 43

44 BD 5EN BIDIRECTIONAL SOUND PROJECTOR p/n BD 5EN is a 20 W weatherproof bidirectional EN certified sound projector. It is suitable for all those installations where high intelligibility for alarm messages broadcasting and great sound reproduction quality are required; moreover, thanks to its IP 65 protection grade, it can be installed both indoor and outdoor. A modern and endearing design makes it the perfect product for environments where projectors are intended also as architectural elements contributing to improve global aesthetics. Main Features EN 54-24:2008 certified (CPR: 0068-CPR-058/2014) 2 x 5 full range speakers for alarm voice messages broadcasting and high quality background music ABS cabinet with steel mesh grille. It can be installed both indoors and outdoors (IP 65 protection grade). Equipped with transformer for 100 V (/ 70 V) constant voltage lines. Internal power setting. Ceramic screw terminal for connection. Internal thermal fuse. Color: white. 147 mm 176 mm 183 mm 179 mm TECHNICAL SPECIFICATIONS 332 mm Input voltage 100 V (70 V) Power 20 W - 10 W - 5 W W Input impedance 500 Ω (20 W) - 1 kω (10 W) - 2 kω (5 W) - 4 kω (2.5 W) Frequency response 60 Hz 20 khz Sensitivity 86 db (1 W, 1 m), 74 db (1 W, 4m) Sound pressure level 99 db (20 W, 1 m), 87 db (20 W, 4 m) Transducer Material Colour Connector 2 x 5 full range Body: ABS Grille: steel White Ceramic terminal IP protection grade IP 65 Dimensions Net weight ø 180 mm (7.1 ), depth: 340 mm (13.4 ) (without bracket) 3.6 kg (7.9 lb) 44

45 BS 5EN PENDANT SPEAKER p/n BS 5EN is a 20W, EN certified pendant speaker. It is suitable for all those installations where high intelligibility for alarm messages broadcasting and great sound reproduction quality are required; moreover, thanks to its IP 65 protection grade, it can be installed both indoor and outdoor. A modern and endearing design makes it the perfect product for environments where projectors are intended also as architectural elements and contribute to improve global aesthetics. Main Features EN 54-24:2008 certified (CPR: 0068-CPR-058/2014) 5 coaxial speaker for alarm voice messages broadcasting and high quality background music. 5 meters cable. ABS cabinet with steel mesh grille. It can be installed both indoors and outdoors (IP 65 protection grade). Equipped with transformer for 100 V (/ 70 V) constant voltage lines. Internal power setting. Ceramic screw terminal for connection. Internal thermal fuse. Color: white. 176 mm 147 mm 261 mm 5 m TECHNICAL SPECIFICATIONS Input voltage 100 V (70 V) Power 20 W - 10 W - 5 W W Input impedance 500 Ω (20 W) - 1 kω (10 W) - 2 kω (5 W) - 4 kω (2.5 W) Frequency response 80 Hz 20 khz Sensitivity 88 db (1 W, 1 m), 76 db (1 W, 4m) Sound pressure level 101 db (20 W, 1 m), 89 db (20 W, 4 m) Transducer Material Colour Connector 5 coaxial with 20 mm dome tweeter Body: ABS Grille: steel White Ceramic terminal IP protection grade IP 65 Dimensions ø 180 mm (7.1 ), depth: 260 mm (10.2 ) Net weight 2.79 kg (6.15 lb) 45

46 DP 1420EN ALUMINIUM SOUND PROJECTOR p/n Main Features The DP 1420EN sound projector is elegant and suitable for sound distribution in very large environments. These have a cylindrical fire protection steel body and an U bracket support in aluminum for the installation. The projector incorporates a 130 mm (5 ) loudspeaker. It includes a transformer inside for the connection to ( V) constant voltage lines. Thanks to its ceramic termination blocks (capable of withstanding temperatures in excess of 650 C/202 F), its thermal fuse (threshold: 150 C/ 302 F) and its fire-resistant cable, the speaker does not allow fire to move to the audio system. EN 54-24:2008 certified (CPR: 1488-CPR-0485/W) Unidirectional sound projector characterized by high acoustic performance Ceramic screw terminal for connection. Internal thermal fuse. IP 66 protection, suitable for outdoor use It s ideal for train stations, underground stations, car parks, factories, warehouses, and PA systems in general Continuous nominal power: 20/40 W ([100 V]: W - [70V]: W) Ø 7 mm 61 mm Ø 146 mm 156 mm TECHNICAL SPECIFICATIONS 200 mm Input voltage 100 V (70 V) Power 20 W 10 W 5 W 2.5 W (100 V) 20 W 10 W 5 W 2.5 W 1.25 W (70 V) Input impedance 500 Ω (20 W) - 1 kω (10 W) - 2 kω (5 W) - 4 kω (2.5 W) Frequency response 160 Hz 20 khz ( 10 db) Sensitivity 92 db (1 W, 1 m) Sound pressure level 105 db (20 W, 1 m), 93 db (20 W, 4 m) Transducer 5 full range Material Body: aluminium Grille: stainless steel Colour Light Grey RAL 7035 Connector Ceramic terminal IP protection grade IP 66 Dimensions ø 146 mm (5.8 ), depth 200 mm (7.9 ) Net weight 2.5 kg (5.5 lb) 46

47 BD 2412EN ALUMINIUM BIDIRECTIONAL SOUND PROJECTOR p/n BD 2412EN sound projector is elegant and suitable for sound distribution in very large environments. These have a cylindrical fire protection steel body and support for the installation. The projector incorporates two 130 mm (5 ) loudspeaker. It includes a transformer inside for the connection to (100 70V) constant voltage lines. Thanks to its ceramic termination blocks (capable of withstanding temperatures in excess of 650 C/202 F), its thermal fuse (threshold: 150 C/ 302 F) and its fire-resistant cable, the speaker does not allow fire to move to the audio system. Main Features Bidirectional sound projector with double loudspeaker, characterized by high acoustic performance, excellent design and compact dimensions Ceramic screw terminal for connection. Internal thermal fuse. IP 66 protection, suitable for outdoor use It s ideal for train stations, underground stations, car parks, factories, warehouses, and PA systems in general Continuous nominal power: 20/10/5 W ([100 V] Ø 146 mm Ø 5 mm 170 mm TECHNICAL SPECIFICATIONS 100 mm 184 mm Input voltage 100 V (70 V) Power 20 W 10 W 5 W Input impedance 500 Ω (20 W) 1 kω (10 W) 2 kω (5 W) Frequency response 130 Hz 20 khz ( 10 db) Sensitivity 89 db (1 W, 1 m) Sound pressure level 102 db (20 W, 1 m), 90 db (20 W, 4 m) Transducer 2 x 5 full range Material Body: aluminium Grille: stainless steel Colour Light Grey RAL 7035 Connector Ceramic terminal IP protection grade IP 66 Dimensions ø 146 mm (5.8 ), depth 184 mm (7.2 ) Net weight 3.3 kg (7.26 lb) 47

48 MR 52BEN MR 52WEN p/n p/n WAYS BASS REFLEX CABINET SPEAKERS Compact design and a wealth of mounting options make the RCF MR 52BEN / MR 52WEN a Compact 2-way loudspeakers ideal for use both for alarm and business music systems. The installation is fast and efficient using the accompanying adjustable mounting bracket. Connections are made with ceramic terminals. Wattage taps and voltage adjustments selectable by means of two rotary switches. The enclosure is constructed of high density, scratch resistant ABS and includes a protective steel grille and connection cover. Compliant with EN 54-24:2008 standard. Main Features 2 ways bass reflex cabinet speakers characterized by high acoustic performance. Ceramic termination block, thermal fuse and internal fireresistant cable. It s ideal for both voice alarm and business music applications. 4 power levels selectable plus 8 Ω option. 242 mm 192 mm 190 mm 90.5 mm TECHNICAL SPECIFICATIONS 37 mm Input voltage 100 V (70 V) Power 30W - 15W - 7.5W W Input impedance (1 khz) 333Ω (30 W) - 667Ω (15 W) kΩ (3.75 W) kΩ (7.5 W) Frequency response 80 Hz 20 khz ( 10 db) Sensitivity 89 db (1 W, 1 m) Sound pressure level 104 db (30 W, 1 m) Transducer Material Colour Connector 5 woofer 1 tweeter Body: ABS Grille: steel Black (MR 52BEN) and white (MR 52WEN) Ceramic terminal IP protection grade IP 40 Dimensions H 242 mm (9,5 ), L 192 mm (7,6 ), D 190 mm (7,5 ) Net weight 2.75 kg (6.06 lb) 48

49 CS 6520EN TWO-WAY COLUMN SPEAKER p/n Two-way speakers with very compact dimensions, the CS 6520EN features 4 extended-range speakers and a tweeter. This model utilizes a series of innovative technological solutions that guarantee highly intelligible reproduction of the vocal message. It s complete with line transformer for directly connecting the speaker columns to 70 V or 100 V constant-voltage systems and, thanks to multiple sockets, permit selecting the power to be diffused from among various values. Thanks to IP 66 insulation, the column speakers can also be used outdoors. Usable in railway stations, subways, churches, factories, warehouses, PA systems in general. Main Features EN 54-24:2008 certified (CPR: 1488-CPR-0490/W) Ideal for speech reproduction with high intelligibility in acoustically difficult environments, both indoors and outdoors, also suitable for music Music power/rms: 40/20W Four 3 mid-woofer speakers and one central 20mm tweeter Weather-resistant construction IP 66 for use also outdoors, sturdy hinged support in resin, stainless steel fasteners Body in aluminium and front grille in steel bake-painted RAL 9003 White Articulated support for wall mounting included 620 mm 55 mm 96 mm 119 mm 114 mm TECHNICAL SPECIFICATIONS Input voltage 100 V (70 V) Power 20 W 10 W 5 W 2.5 W (100 V) 20 W 10 W 5 W 2.5 W 1.25 W (70 V) Input impedance 250 Ω (20 W) Ω (20 W) - 1 kω (10 W) - 2 kω (5 W) - 4 kω (2.5 W) Frequency response 140 Hz 20 khz ( 10 db) Sensitivity 92 db (1 W, 1 m), 80 db (1 W, 4m) Sound pressure level 105 db (20 W, 1 m), 93 db (20 W, 4 m) Transducer Material 4 x 3 mid-woofer one central 20 mm dome tweeter Body: extruded aluminium Grille: aluminium Colour White RAL 9003 Connector Ceramic terminal IP protection grade IP 66 Dimensions H 620 mm (24.4 ), L 114 mm (4.5 ), D 96 mm (3.8 ) Net weight 4.5 kg (9.9 lb) 49

50 CS 6940EN TWO-WAY COLUMN SPEAKER p/n Two-way speakers with very compact dimensions, the CS 6940 EN features 8 round extended-range speakers and a tweeter. This model utilizes a series of innovative technological solutions that guarantee highly intelligible reproduction of the vocal message. It s complete with line transformer for directly connecting the speaker columns to 70V or 100V constant-voltage systems and permit selecting the power to be diffused from among various values. Thanks to IP 66 insulation, the speaker columns can also be used out of doors. Usable in railway stations, subways, churches, factories, warehouses, PA systems in general. EN 54-24:2008 certified. Main Features EN 54-24:2008 certified (CPR: 1488-CPR-0490/W) Ideal for speech reproduction with high intelligibility in acoustically difficult environments, both indoors and outdoors, also suitable for music. Rated power: 40W. Eight 3,5 mid-woofer speakers and one central tweeter Weather-resistant construction IP 66 Body in aluminum and front grille in steel bake-painted RAL 9003 White Articulated support for wall mounting included. 995 mm TECHNICAL SPECIFICATIONS 55 mm 96 mm 119 mm 114 mm Input voltage 100 V (70 V) Power 40 W 20 W 10 W 5 W Input impedance (1 khz) 250 Ω (40 W) Ω (20 W) - 1 kω (10 W) - 2 kω (5 W) Frequency response 140 Hz 20 khz ( 10 db) Sensitivity 93 db (1 W, 1 m) Sound pressure level 109 db (20 W, 1 m) Transducer 8 x 3 mid-woofer and one central 20 mm dome tweeter Material Body: extruded aluminium Grille: aluminium Colour White RAL 9003 Connector Ceramic terminal IP protection grade IP 66 Dimensions H 956 mm (37.6 ) L 114 mm (4.5 ), D 96 mm (3.8 ) Net weight 7.3 kg (16.06 lb) 50

51 DU 50EN WALL/CEILING STEEL SPEAKER p/n DU 50EN is a speaker with high intellegibility designed for use in alarm messages and background music. The 4.5 full range speaker is included in a steel can; the speaker is provided with a multitap transformer for 100V/70V constant voltage systems, a terminal block made with ceramic material for input and output antiflame cables and thermal switch. DU 50EN is EN certified. Main Features EN 54-24:2008 certified (CPR: 1488-CPR-0489/W) Speaker designed for transmitting alarm messages with high intelligibility, and background music Musical power/rms: 12/6W Wide-band dual cone loudspeaker, diameter 4.5 Extra-thick steel housing, terminal strip for connections made of ceramic material for fl ameproof input and output cables, thermal fuse, suitable internal wiring Colour: RAL 9010 White 21 mm mm 60 mm mm TECHNICAL SPECIFICATIONS Input voltage 100 V (70 V) Power 6 W 3 W 1.5 W 0.75 W Input impedance 1.67 kω (6 W) 3.33 kω (3 W) kω (1.5 W) kω (0.75 W) Frequency response 190 Hz 11 khz ( 10 db) Sensitivity 90 db (1 W, 1 m) Sound pressure level 88 db (6 W, 4 m) Transducer Material 4.5 full range Steel Colour White RAL 9010 Connector Ceramic terminal IP protection grade IP 40 Dimensions H 164 mm (6.5 ), L 164 mm (6.5 ), D 60 mm (2.4 ) Net weight 2 kg (4.4 lb) 51

52 DU 60EN WALL/CEILING STEEL SPEAKER p/n DU 60EN is a speaker with high intelligibility designed for use in alarm messages and background music. The 5 dual cone speaker is included in a steel can; the speaker is provided with a multitap transformer for 100V/70V constant voltage systems, a terminal block made with ceramic material for input and output flameproof cables and thermal switch. DU 60EN is EN certified. Main Features EN 54-24:2008 certified (CPR: 1488-CPR-0488/W) Steel construction. Dual cone 5 loudspeaker. Transformer for connection to 100 V (/ 70 V) constant voltage lines. Power selection among four values. Ceramic terminal strips. Thermal fuse that prevents damage to the audio line due to heat on the speaker. Colour: RAL 9016 White 3.5 mm 20 mm 40 mm35 mm 75 mm 155 mm 165 mm 195 mm TECHNICAL SPECIFICATIONS Input voltage 100 V (70 V) Power 6 W 3 W 1.5 W 0.75 W Input impedance 1.67 kω (6 W) 3.33 kω (3 W) kω (1.5 W) kω (0.75 W) Frequency response 100 Hz 20 khz ( 10 db) Sensitivity 92 db (1 W, 1 m), 80 db (1 W, 4 m) Sound pressure level 100 db (6 W, 1 m), 88 db (6 W, 4 m Transducer 5 dual-cone Material Steel Colour White RAL 9016 Connector Ceramic terminal IP protection grade IP 40 Dimensions ø 195 mm (7.7 ), H: 75 mm (2.9 ) Net weight 1.9 kg (4.2 lb.) 52

53 HD 21EN PLASTIC HORN SPEAKER p/n HD 21EN is a 30W, EN certified horn loudspeaker. Thanks to the IP 66 protection and its UV resistant ABS housing and it is suitable for both indoors and outdoors applications. It can be easily aimed towards any direction through the adjustable wallmount bracket, and can used in sounds systems having large spaces, for instance supermarkets, railway stations, undergrounds, factories, warehouses, etc. and also in all environments that need high efficiency loudspeakers grade. Equipped with transformer for 100 V / 70 V constant voltage lines, internal power setting and ceramic terminal strip to link cables, it also has a thermal fuse that prevents damages to the audio line due to heat. Main Features Compact speaker with 30 W driver Rear cover in UV stabilized self-extinguishing ABS Suitable for indoor and outdoor use (thanks to IP 66 protection) Transformer for 100 V (/ 70 V) constant voltage connection Thermal fuse to protect the audio line from heat 212 mm 7 mm 60 mm 280 mm 106 mm 151 mm TECHNICAL SPECIFICATIONS Input voltage 100 V (70 V) Power 30 W 15 W 7.5 W 3.75 W (100 V) 15 W 7.5 W 3.75 W W (70 V) Input impedance 333 Ω (30W) Ω (15W) kω (7.5 W) kω (3.75 W) Frequency response 340 Hz 9 khz ( 10 db) Sensitivity 104 db (1 W, 1 m), 92 db (1 W, 4m) Sound pressure level 119 db (30 W, 1 m), 107 db (30 W, 4 m) Transducer 38 mm dome compression driver Material ABS Colour Light grey Connector Ceramic terminal IP protection grade IP 66 Dimensions ø 212 mm (8.3 ), depth: 279 mm (10.9 ) Net weight 2 kg (4.4 lb.) 53

54 HD 31EN PLASTIC HORN SPEAKER p/n Main Features HD 31EN is a 30W horn. Thanks to IP66 protection and its UV resistant ABS housing and it is suitable for both indoors and outdoors applications. It can be easily aimed towards any direction through the adjustable wallmount bracket, and can used in sounds systems having large spaces, for instance supermarkets, railway stations, undergrounds, factories, warehouses, etc. and also in all environments that need high efficiency loudspeakers grade. Equipped with transformer for 100V/70V constant voltage lines, internal power setting and ceramic terminal strip to link cables, it also has a thermal fuse protection. EN 54-24:2008 certified. Compact horn speaker with 30 W driver Rear cover in UV stabilized self-extinguishing ABS Suitable for indoor and outdoor use (thanks to IP 66 protection) Transformer for 100V/70 V constant voltage connection Thermal fuse to protect the audio line from heat Color: Grey RAL mm 7 mm 60 mm 325 mm 106 mm TECHNICAL SPECIFICATIONS 151 mm Input voltage 100 V (70 V) Power 30 W 15 W 7.5 W 3.75 W Input impedance (1 khz) 333 Ω (30 W) Ω (15 W) kω (7.5 W) kω (3.75 W) Frequency response 400 Hz ~ 7.5k Hz Sensitivity 110 db (1 W, 1 m) Sound pressure level 125 db (30 W, 1 m) Transducer 38 mm dome compression driver Material ABS Colour Light grey Connector Ceramic terminal IP protection grade IP 66 Dimensions (9.16) Dia. X (12.19) Length mm. (in.) Net weight 2.11 kg (4.65 lb) 54

55 HD 6045EN LONG-THROW MULTI CELL HORN SPEAKER p/n HD 6045EN is a fiberglass horn designed to withstand the most adverse weather conditions, offering high sound reproduction quality and sound pressure levels. A high level of efficiency and sound pressure can be obtained thanks to the use of 4 dynamic driver units for a total output power of 200W. Internal transformers for 100V/70V constant voltage systems are equipped with ceramic terminal blocks for input and output flameproof cables and thermal switch. HD 6045EN is EN certified. Main Features EN 54-24:2008 certified (CPR: 0068-CPR-030/2015) Long-throw horn speaker Body in RAL 9003 white fiberglass Mounting bracket Watertight construction IP 65 protection grade 4 x 50W drivers with transformers for constant voltage line 475 mm 620 mm 564 mm TECHNICAL SPECIFICATIONS Input voltage 100 V (70 V) Power 200 W Input impedance 50 Ω (100 V, 200 W) Frequency response 200 Hz 10 khz ( 10 db) Sensitivity 110 db (200 W, 1 m), 91 db (200 W, 4 m) Sound pressure level 133 db (200 W, 1 m), 114 db (200 W, 4 m) Transducer 4 x 50 mm (2 ) horn loaded compression driver units Material Fiberglass Colour White RAL 9003 Connector Ceramic terminal IP protection grade IP 65 Dimensions H 620 mm (24.4 ), L 475 mm (18.7 ), D 564 mm (22.2 ) Net weight 21.4 kg (47 lb.) 55

56 FIRE RESISTANT LOUDSPEAKER CABLES The CV Series cables are suitable for the transmission of electrical signals and commands for those applications where maximum security is required in situations of fire alarm. They ensure the transmission of the signal to emergency speakers even when exposed to flames, allowing the safe evacuation of the environments where they are installed. The CV Series cable are suitable for fixed installation indoors in wet or normal environments, and temporarily outside. They can be installed on platforms, pipes, conduits and similar systems. 56

57 CV 210 CV 215 CV 225 p/n p/n p/n SPEAKER CABLE 100V SECTION SPEAKER CABLE 100V SECTION SPEAKER CABLE 100V SECTION 2 2 X 1 MMQ 2 X 1.5 MMQ X 2.5 MMQ 57

58 RACK COMPONENTS FOR THE OPTIMUM MANAGEMENT OF THE SYSTEM CONFIGURATIONS MODEL CR 2609 CR 2615 CR 2615 FV CR 2628 CR 2642 Part number Type 9 U 15 U 15 U 28 U 42 U Base dimensions 600 x 500 mm 600 x 600 mm 600 x 600 mm 600 x 600 mm 600 x 600 mm Height 470 mm 800 mm 800 mm 1600 mm 2000 mm Weight 24 Kg 26 Kg 30 Kg 54 Kg 68 Kg Max load 25 Kg mountable on rack 105 Kg 100 Kg 320 Kg 350 Kg Ventilation Natural ventilation on sides - Thermostat controlled Thermostat controlled Thermostat controlled Thermal dissipation 25 c 100 W 230 W 3130 W 3280 W 3320 W Thermal dissipation 35 c 150 W 140 W 2070 W 2160 W 2180 W Included accessories - 4 wheels with braking system 4 wheels with braking system - - Model door (included) AK 2615 AK 2615 AK 2628 AK 2642 Part number door - ( ) ( ) ( ) ( ) 58

59 CR 2600 RACK ENCLOSURES The CR 2600 series rack enclouseres are designed to hold all RCF 19" rack standard components. They are constructed in compliance with the IEC dimensional standard, and the depth is 600 mm for all models. The structure is made of steel painted RAL 7035 light grey. The rack enclosures are bake-painted at high temperature using epoxy powders to make the structure unalterable over time and resistant to scratching, abrasion, and atmospheric agents. The protection level is IP 30. The CR 2600 SERIES rack enclosures are composed of a basic structure that is assembled simply and quickly by fitting and securing four steel uprights to the upper and lower panels. The lower door and side panels are fitted following the wiring operations to facilitate the insertion and connection of the components. The lower panel, which forms the base of the rack, has openings for the passage of external connection cables (speaker lines, power supply, data, etc.) that are sized and shaped to guarantee the electrical safety of the structure. The earthing of the rack complies with current safety regulations. For the optimisation of the internal wiring, supports are supplied to gather the cable and attach them in an orderly fashion. The packing materials can be reused for transport the enclosure once it has been wired. Front doors are also available, which are useful for to protect the components installed in the rack. RR 2601 RACK WHEELS KIT p/n AR 2605 FRAME WITH POWER SOCKETS p/n AR 1050-N RACK LATERAL SUPPORT p/n P AER1 FRONT VENTILATION PANELS p/n Front ventilation panel, 1U for CR 2600 series racks, RAL 9005 black Wheels for RCF rack cabinets CR 2628 and CR The kit includes 2 wheels with brake and 2 swivel wheels. Wheel diameter: 80 mm. The maximum applicable load does not change when wheels are mounted. 5-socket frame, Schuko and Italian standard, on back-rack support 2U. Portion of Omega bar for installing 5 Omega standard modules 16A total capacity; cable included Accessory for installation in RCF CR2600 series racks BH 1042 BATTERY HOLDER p/n Universal battery holder for RCF series CR

60 PV 2603 VENTILATION UNIT p/n PV 2603 is a ventilation unit composed by 3 blowers (230 V ac) and a main switch. The blowers turn on due to the activation command of a thermostat included in all RCF CR 2600 rack cabinets series g mm VENTILATION UNIT The ventilation unit is composed of 3 fans (powered by 230 V AC) with one main switch on the rear panel It can be turned on from the thermostat of rack units belonging to the CR 2600 Series The ventilation unit has an air flow capacity of 500 m/h, from the bottom to the top 19 Rack mounting Energy consumption less than 45 W Low noise CLOSURE PANELS PU 1 PU 2 p/n p/n PU 3 p/n PU 4 p/n U Closure Panel RAL 9005 Nero 2U Closure Panel RAL 9005 Nero 3U Closure Panel RAL 9005 Nero 4U Closure Panel RAL 9005 Nero 60

61 61

VX-3000 Series Voice Alarm and Public Address System

VX-3000 Series Voice Alarm and Public Address System VX-3000 Series Voice Alarm and Public Address System VX-3000 SERIES Combined highly integrated voice alarm and public address system. The issue of security is more than ever important. Our VX-3000 is a

More information

... yet still led out of the terminal quickly and safely in an emergency.

... yet still led out of the terminal quickly and safely in an emergency. ... yet still led out of the terminal quickly and safely in an emergency. VX-3000 SERIES Combined highly integrated voice alarm and public address system. The issue of security is more than ever important.

More information

INTEGRATED VOICE EVACUATION SYSTEM VM-3000 Series

INTEGRATED VOICE EVACUATION SYSTEM VM-3000 Series OPERATION MANUAL INTEGRATED VOICE EVACUATION SYSTEM VM-3000 Series VOICE ALARM SYSTEM AMPLIFIER VM-3240VA VOICE ALARM SYSTEM AMPLIFIER VM-3360VA VM EXTENSION AMPLIFIER VM-3240E VM EXTENSION AMPLIFIER VM-3360E

More information

VEB Series. TCP/IP Network Matrix PA System. 32 simultaneous Audio Buses. Up to 60 Network Paging Consoles. Up to 128 Audio Output channels

VEB Series. TCP/IP Network Matrix PA System. 32 simultaneous Audio Buses. Up to 60 Network Paging Consoles. Up to 128 Audio Output channels 32 simultaneous Audio Buses Up to 60 Network Paging Consoles Up to 128 Audio Output channels Up to 1,500 Speaker Zones Up to 600 Control Inputs UP to 600 Control Outputs VEB Series TCP/IP Network Matrix

More information

FreeSpace IZA 250-LZ / 190-HZ TECHNICAL DATA SHEET. integrated zone amplifier. Key Features. Product Overview. Product Information.

FreeSpace IZA 250-LZ / 190-HZ TECHNICAL DATA SHEET. integrated zone amplifier. Key Features. Product Overview. Product Information. Product Overview For background/foreground music and paging applications, the Bose FreeSpace IZA 250-LZ and IZA 190-HZ s are designed to deliver premium sound, provide simplified set up and easy daily

More information

FreeSpace IZA 2120-LZ Integrated Zone Amplifier

FreeSpace IZA 2120-LZ Integrated Zone Amplifier Product Description For background/foreground music and paging applications, Bose FreeSpace IZA 2120-LZ integrated zone amplifier elevates the audio experience when using FreeSpace loudspeakers. Optimized

More information

Integrated mixer amplifier PA-60/120/240

Integrated mixer amplifier PA-60/120/240 Integrated mixer amplifier PA-60/120/240 SUMMARY The Inter-M PA-60/120/240 are integrated mixer amplifiers. They are complete and economical multipurpose desktop mixer-amplifiers providing a cost-effective

More information

Overview. Features. Technical Data Sheet 1 / 5. Power Amplifier XMV8140-D

Overview. Features. Technical Data Sheet 1 / 5. Power Amplifier XMV8140-D Overview Multi-channel power amplifiers with features designed specifically to benefit installation sound systems. Features Eight-channel power amp that can operate in both high-impedance (70V/100V line)

More information

PB-400-CN. Datasheet. IndustryAmp PB-400-CN * Applies to Part Number: *This unit has a CobraNet interface installed

PB-400-CN. Datasheet. IndustryAmp PB-400-CN * Applies to Part Number: *This unit has a CobraNet interface installed PB-400-CN Datasheet Applies to Part Number: 590403 IndustryAmp PB-400-CN * *This unit has a CobraNet interface installed User Notice: No part of this document including the software described in it may

More information

Bosch Plena Public Address Solutions A flexible approach to sound management

Bosch Plena Public Address Solutions A flexible approach to sound management Bosch Plena Public Address Solutions A flexible approach to sound management 2 Plena Public Address Solutions Your easy-to-expand public address system Whether it is a local supermarket, a larger retail

More information

PERMA Series Revision 2 Amplifiers

PERMA Series Revision 2 Amplifiers PERMA Series Revision 2 Amplifiers High Efficiency Life Safety Digital Power Amplifiers Current Thinking Document Number DDC PER 7001 02 ACS Introduction Voice Alarm (VA) systems are the quickest way to

More information

Datasheet. Octadrive DSP-CN * Applies to Part Number: *This unit has a CobraNet interface installed

Datasheet. Octadrive DSP-CN * Applies to Part Number: *This unit has a CobraNet interface installed OCTADRIVE DSP-CN Datasheet Applies to Part Number: 391030 Octadrive DSP-CN * *This unit has a CobraNet interface installed User Notice: No part of this document including the software described in it may

More information

User Manual. MA 21 Two zone mixing amplifier

User Manual. MA 21 Two zone mixing amplifier User Manual MA 21 Two zone mixing amplifier Safety instructions When using this electronic device, basic precautions should always be taken, including the following: 1 Read all instructions before using

More information

USER MANUAL MU DXT 9000 EVACUATION / PAGING AUDIO SYSTEM MU 9186 MAIN UNIT

USER MANUAL MU DXT 9000 EVACUATION / PAGING AUDIO SYSTEM MU 9186 MAIN UNIT USER MANUAL MU 9186 - - DXT 9000 EVACUATION / PAGING AUDIO SYSTEM MU 9186 MAIN UNIT TABLE OF CONTENTS ENGLISH 4 5 6 10 11 12 16 21 23 23 25 25 30 31 32 33 34 SAFETY PRECAUTIONS NOTES ABOUT AUDIO SIGNAL

More information

DPA602 1/7. Multi-Channel Network Amplifier. General Description. Features. Applications. AtlasIED.com. DPA602 Front. DPA602 Back

DPA602 1/7. Multi-Channel Network Amplifier. General Description. Features. Applications. AtlasIED.com. DPA602 Front. DPA602 Back 1/7 DPA602 Multi-Channel Network Amplifier Features Configurations 2 x 300 Watt 70V / 100V (Factory Default) 4 x 150 Watt @ 4Ω 1 x 300 Watt 70V / 100V & 2 x 150 Watt @ 4Ω No Computer Required to Operate

More information

PM1060 / 1120 INSTRUCTION MANUAL. Thank you for choosing another quality product from Amperes Electronics.

PM1060 / 1120 INSTRUCTION MANUAL. Thank you for choosing another quality product from Amperes Electronics. INSTRUCTION MANUAL PM1060 / 1120 Dekstop Paging Microphone With Zone Selector PM 1120 amperes 1 2 3 4 5 6 7 8 9 10 11 12 12 ZONE PAGING MICROPHONE ALL CALL CHIME TALK Thank you for choosing another quality

More information

Z4MK3/Z8MK3 : Zone Mixers

Z4MK3/Z8MK3 : Zone Mixers ZMK/ZMK : Zone Mixers Clearly better sound. mm Z MK Four Zone Venue Mixer Microphone Microphone Paging Mic Level Music Source Music Level. mm (U) / Power Mute Zone Zone Zone Zone ZMK Zone Mixer Z MK Eight

More information

MA80FT Mini Amplifier

MA80FT Mini Amplifier MA8FT Mini Amplifier LF HF MA8FT 8W MIXER AMPLIFIER OFF 1 OFF 1 STATUS MUTE PEAK OFF 1-1 db +1-1 db +1 MUSIC EQ MA8FT Front Panel PAGE/ INPUT +5 +1 db HI-Z SPKR IN 7/ - -1V SETTINGS 1: / PAGE MODE 2: /

More information

PAC Multi-zone all-in-one 2 bus Mixer Amplifier

PAC Multi-zone all-in-one 2 bus Mixer Amplifier Multi-zone all-in-one 2 bus Mixer Amplifier SUMMARY The mixer amplifier is a digital multi-zone amplifier system, which offers up to 24 separate zone switching/selection and BGM facilities. The has 24

More information

USER MANUAL QSM-606AZ QSM-612AZ QSM-624AZ MIXER AMPLIFIER

USER MANUAL QSM-606AZ QSM-612AZ QSM-624AZ MIXER AMPLIFIER USER MANUAL QSM-606AZ QSM-612AZ QSM-624AZ MIXER AMPLIFIER WARNING: THIS APPLIANCE MUST BE EARTHED IMPORTANT The wires in the mains lead are coloured In accordance with the following code: Green and Yellow:

More information

Q-Tech Commercial Series. 86 Derby St. Pascoe Vale VIC 3055 ( :www.questaudio.net *

Q-Tech Commercial Series. 86 Derby St. Pascoe Vale VIC 3055 ( :www.questaudio.net * www.questaudio.net Contents QTA4120P Power Amp.................................... 3 QTA 1240P Power Amp.................................... 4 QTM60 Public Address Mixer.................................

More information

User Manual. MA 240 Mixing amplifier

User Manual. MA 240 Mixing amplifier User Manual MA 240 Mixing amplifier Safety instructions When using this electronic device, basic precautions should always be taken, including the following: 1 Read all instructions before using the product.

More information

for Mass Notification Installations

for Mass Notification Installations OPERATING INSTRUCTIONS INTEGRATED VOICE EVACUATION SYSTEM VM-3000 Series VOICE ALARM SYSTEM AMPLIFIER VM-3240VA VM EXTENSION AMPLIFIER VM-3240E REMOTE MICROPHONE RM-200M for Mass Notification Installations

More information

Instruction Kit MIXER AMPLIFIER GT 60C GT 125C. GROMMES-PRECISION SINCE-46

Instruction Kit MIXER AMPLIFIER GT 60C GT 125C. GROMMES-PRECISION SINCE-46 Instruction Kit GT 60C GT 125C MIXER AMPLIFIER GROMMES-PRECISION 1-800-SINCE-46 www.grommesprecision.com Thank you for purchasing from Grommes~Precision! Grommes~Precision and its commercial audio division,

More information

Datasheet. IndustryAmp PB-800-CN * Applies to Part Number: *This unit has a CobraNet interface installed

Datasheet. IndustryAmp PB-800-CN * Applies to Part Number: *This unit has a CobraNet interface installed PB-800 800-CN Datasheet Applies to Part Number: 590803 IndustryAmp PB-800-CN * *This unit has a CobraNet interface installed User Notice: No part of this document including the software described in it

More information

Professional Audio for your world

Professional Audio for your world General Catalogue Professional Audio for your world Summary Voice evacuation systems Multizone voice/music systems Page 6 Mixer Amplifiers Booster units Page 30 CMDS Compact Music Distribution Systems

More information

MediaMatrix X-Frame 88

MediaMatrix X-Frame 88 S P E C I F I C A T I O N S MediaMatrix X-Frame 88 Description The X-Frame 88 is a fully programmable, fully configurable, Digital Signal Processor (DSP) based audio processing and control system. It includes

More information

PowerShare PS604A adaptable power amplifier

PowerShare PS604A adaptable power amplifier Product Description Bose delivers 600 watts for fixed-install applications. Through patented technology, total amplifier power is shared across all output channels, allowing installers the freedom to utilize

More information

Bosch Communications Systems Get your message across, effectively.

Bosch Communications Systems Get your message across, effectively. Bosch Communications Systems Get your message across, effectively. Bosch Security Systems is an innovative, one-stop global shop for high-quality, safety, security and communication products. With an unrivalled

More information

DIGITAL CROSSOVERS AND DSP PROCESSORS

DIGITAL CROSSOVERS AND DSP PROCESSORS Prophon electronics DIGITAL CROSSOVERS AND DSP PROCESSORS DSP processors and loudspeaker management systems are in a way the heart of a sound system, if they fail, there will be silence! We have developed

More information

Amplifiers and battery charger

Amplifiers and battery charger DPAfour Digital Power Amplifiers Public Address - Voice Alarm Audio Distribution over IP Commercial Audio Intelligent Acoustic Solutions Intercommunication Loudspeakers Amplifiers and battery charger DPAfour

More information

CABINET POWERED MIXING CONSOLE

CABINET POWERED MIXING CONSOLE R SHS AUDIO SPMU- 00 CABINET POWERED MIXING CONSOLE USER'S MANUAL SAFETY INSTRUCTIONS SPECIFICATIONS Inputs Input modes Input Impedance Rated Input level Connector WARNING - TO REDUCE THE RISK OF FIRE

More information

Mixing Amplifier MA 247MR

Mixing Amplifier MA 247MR MA 247MR Mixing Amplifier Less is more. As the CD is losing more and more ground, there is no more CD-player in the MA247MR. No moving parts, higher reliability. Something of a legend already, this 240

More information

RAD STATUS INDICATORS. The Ambient Light Sensor dims the display and LEDs in darkened rooms cm (5.85 in)

RAD STATUS INDICATORS. The Ambient Light Sensor dims the display and LEDs in darkened rooms cm (5.85 in) Description Using one shielded category cable drop, the provides any room with a dual 4-watt amp, end user control via a color custom LCD display & encoders, a dual universal audio I/O interface, plus

More information

TOA 500 SERIES MIXER POWER AMPLIFIER

TOA 500 SERIES MIXER POWER AMPLIFIER TOA 500 SERIES MIXER POWER AMPLIFIER Operation Instruction Manual A-503A A-506A A-512A Features General Description 1. High quality design and construction. 2. Full frequency response: 50-15,000Hz, ±3dB.

More information

DSP AMPLIFIERS DI

DSP AMPLIFIERS DI DATA SHEET DSP AMPLIFIERS THE LATEST GENERATION OF DIGITAL HIGH-PERFORMANCE AMPLIFIERS EN PRODUCT DESCRIPTION The new DI-SERIES digital amplifiers have been developed and manufactured in house by FOHHN

More information

MA40E Mini Amplifier with DSP

MA40E Mini Amplifier with DSP MA40E Mini Amplifier with DSP Clearly better sound MA40E Front Panel MA40E Rear Panel General Description The MA40E is a very compact stereo amplifier of advanced design, intended for integration into

More information

IMPORTANT SAFETY INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS When using this electronic device, basic precautions should always be taken, including the following: 1. Read all instructions before using the product. 2. Do not use this

More information

Dante. Dante Network Class D Professional Audio Amplifier D-3000

Dante. Dante Network Class D Professional Audio Amplifier D-3000 Dante TM Dante Network Class D Professional Audio Amplifier D-3000 SUMMARY The D-3000 is a high power professional amplifier specially designed for the sound re-enforcement market also referred to as SR,

More information

PRELIMINARY AA35G/AA60G. 3-Input, 35-Watt Mixer Amplifier with Global Power Supply

PRELIMINARY AA35G/AA60G. 3-Input, 35-Watt Mixer Amplifier with Global Power Supply 1/6 AA5G/AA60G -Input, 5-Watt Mixer Amplifier with Global Power Supply 01 Atlas Sound LP. The Atlas Circle A, Soundolier, and Atlas Sound are trademarks of Atlas Sound L.P. IED is a Registered Trademark

More information

DPAfour125, DPAfour250 AMPLIFIERS. Operating Manual

DPAfour125, DPAfour250 AMPLIFIERS. Operating Manual DPAfour125, DPAfour250 AMPLIFIERS Operating Manual Operating manual, DPA Series DPA-10UMS01-V01R04 version revision date 01 02 24-02-2012 www.ateis-europe.com ATEÏS Europe BV - Sydneystraat 42-3047BP ROTTERDAM

More information

PowerMatch PM8500 / 8500N TECHNICAL DATA SHEET. configurable power amplifier. Key Features. Product Overview. Applications

PowerMatch PM8500 / 8500N TECHNICAL DATA SHEET. configurable power amplifier. Key Features. Product Overview. Applications Product Overview Bose PowerMatch PM8500 is a configurable professional power amplifier delivering concert sound quality for fixed installation sound reinforcement systems. Building on the ruggedness proven

More information

Overview. Features. Technical Data Sheet 1 / 6. Mixing Console MG20. MG20 is a versatile mixer suitable for a wide range of users and applications.

Overview. Features. Technical Data Sheet 1 / 6. Mixing Console MG20. MG20 is a versatile mixer suitable for a wide range of users and applications. Overview MG20 is a versatile mixer suitable for a wide range of users and applications. Rear Panel Features Input channels: 20 Line Inputs (12 mono, 4 stereo), 16 Mic Inputs with 48V phantom power and

More information

IDA 4 XM V 1.X. Installation and configuration of IDA 4 XM User Manual

IDA 4 XM V 1.X. Installation and configuration of IDA 4 XM User Manual IDA 4 XM V 1.X Installation and configuration of IDA 4 XM User Manual IMPORTANT SAFETY INSTRUCTIONS - Switch the device s power off before any maintenance operation (changing the CU card, etc.) - The 24V

More information

3.Avoid spilling liquids or allowing materials to enter the cabinet

3.Avoid spilling liquids or allowing materials to enter the cabinet PUBLIC ADDRESS MIXER POWER AMPLIFIER INSTRUCTION MANUAL PL-260A 260 WATT RMS RISK OF ELECTRIC SHOCK, DO NOT OPEN! CAUTION: TO REDUCE THE RISK OF ELECTRIC SHOCK, DO NOT OPEN COVER. NO USER SERVICEABLE PARTS

More information

Mixing Power Amplifiers WA-MA120N WA-MA240N

Mixing Power Amplifiers WA-MA120N WA-MA240N Mixing Power Amplifiers WA-MA0N WA-MA40N All-in-One Mixer and Amp From the simplest to the most complex public address needs, the WA-MA0N and WA-MA40N have what it takes. These mixing power amplifiers

More information

.2 Section Waste Management and Disposal..4 Section Electrical General Requirements.

.2 Section Waste Management and Disposal..4 Section Electrical General Requirements. Issued 2006/08/01 Section 16724 Public Address System Page 1 of 8 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3 Section 01780

More information

9000M2 Series Modular Digital Matrix Mixer and Mixer/Amplifiers

9000M2 Series Modular Digital Matrix Mixer and Mixer/Amplifiers 9000M2 Series Modular Digital Matrix Mixer and Mixer/Amplifiers Unparalleled DSP mixer ideal for multi-zone paging, music distribution and room-combining applications. The 9000 Series Modular Digital Matrix

More information

Portable Multi-Channel Recorder Model DAS240-BAT

Portable Multi-Channel Recorder Model DAS240-BAT Data Sheet Portable Multi-Channel Recorder The DAS240-BAT measures parameters commonly found in process applications including voltage, temperature, current, resistance, frequency and pulse. It includes

More information

PowerShare PS602 adaptable power amplifier

PowerShare PS602 adaptable power amplifier Product Description Bose delivers 600 watts for fixed-install applications. Through patented technology, total amplifier power is shared across all output channels, allowing installers the freedom to utilize

More information

User Manual. imix 63 Stereo mixing preamplifier

User Manual. imix 63 Stereo mixing preamplifier User Manual imix 63 Stereo mixing preamplifier Safety instructions When using this electronic device, basic precautions should always be taken, including the following: 1 Read all instructions before using

More information

MA6480A. Energy-Efficient, Multi-Function 240-Watt Mixing Amplifier with Dual 70/100 V and 4 Ohms Outputs. Features

MA6480A. Energy-Efficient, Multi-Function 240-Watt Mixing Amplifier with Dual 70/100 V and 4 Ohms Outputs. Features Features Multi-function 240-Watt mixing amplifier with dual 70/100 V and 4 Ω outputs, designed for continuous operation in distributed music, paging and AV applications State-of-the-art, energy-saving

More information

page1 - - Zoned system for high quality BGM and paging System Overview Key Features

page1 - - Zoned system for high quality BGM and paging System Overview Key Features Zoned system for high quality BGM and paging System Overview In addition to individual sound systems in each studio, this system provides the ability to broadcast announcements throughout the entire facility.

More information

DNA Pro series 10K8 3K8

DNA Pro series 10K8 3K8 The culmination of five years intensive effort, the Danley Sound Labs DNA series amplifiers represent the leading edge of amplifier design. In a straightforward robust package, they surpass similar products

More information

ZM 84 Audio Mixer. User Manual. Order code: CRAM41. Audio Mixer ZM 84 AUX 3 AUX 1 AUX 2 AUX 4 MASTER 1 MASTER 2 OFF BASS BASS TREBLE TREBLE BASS BASS

ZM 84 Audio Mixer. User Manual. Order code: CRAM41. Audio Mixer ZM 84 AUX 3 AUX 1 AUX 2 AUX 4 MASTER 1 MASTER 2 OFF BASS BASS TREBLE TREBLE BASS BASS ZM 84 Audio Mixer User Manual -20-10 0 +10 +20-20 -10 0 +10 +20 POWER L R 0 0 ON ZM 84 Audio Mixer AUX 4 MIC/LINE 1 MIC/LINE 1 MIC/LINE 2 MIC/LINE 3 MIC/LINE 4 THR THR +6 +10 +6 AUX 3 AUX 1 AUX 2 AUX 4

More information

MIXING CONSOLE CX-124 CX-164. TOA Corporation. Operating Instructions

MIXING CONSOLE CX-124 CX-164. TOA Corporation. Operating Instructions MIXING CONSOLE Operating Instructions CX-124 CX-164 Please follow the instructions in this manual to obtain the optimum results from these units. We also recommend you to keep this manual handy for future

More information

Specifications MPS 602

Specifications MPS 602 Specifications MPS 602 Video VGA Inputs Gain... Unity Bandwidth... 350 MHz (-3 db) Crosstalk... -50 db @ 10 MHz, -30 db @ 100 MHz Switching speed...

More information

T L Audio. User Manual EQ1 VALVE EQUALISER. Tony Larking Professional Sales Limited, Letchworth, England.

T L Audio. User Manual EQ1 VALVE EQUALISER. Tony Larking Professional Sales Limited, Letchworth, England. T L Audio User Manual EQ1 VALVE EQUALISER Tony Larking Professional Sales Limited, Letchworth, England. Tel: 01462 490600, International +44 1462 490600. Fax: 01462 490700, International +44 1462 490700.

More information

NE SERIES. ne Models ne800 ne1600 ne2400

NE SERIES. ne Models ne800 ne1600 ne2400 5-Year Warranty Hand-built in Webster, NY ne800 ne1600 ne2400 NE SERIES Two-Channel, Network-Enabled Power Amplifiers Our 2-channel ne (Networked-Enabled) Series Amplifiers are designed to meet the specifications

More information

Dante Kit MEG FEATURES DELIVERY INCLUDES PRODUCT VARIANTS

Dante Kit MEG FEATURES DELIVERY INCLUDES PRODUCT VARIANTS PRODUCT SPECIFICATION 1/6 FEATURES Great speech intelligibility Phantom power via PoE Remote controllable gain level Daisy-chaining possible DELIVERY INCLUDES 1 SL DI 4 XLR Dante interface 4 MAT 133-S

More information

T-link8. SPLITTER/MIXER T-link8. T-link8

T-link8. SPLITTER/MIXER T-link8. T-link8 SPLITTER/MIXER CH CH CH CH CH CH Technical Specifications AUDIO INPUTS AUDIO OUTPUTS SYSTEM SPECIFICATIONS FUNCTION CONTROLS FUNCTION SWITCHES INDICATORS POWER SUPPLY PHYSICAL Connectors Type Impedance

More information

Z44R. Multi-purpose Rack Mixer. Item ref: User Manual

Z44R. Multi-purpose Rack Mixer. Item ref: User Manual Z44R Multi-purpose Rack Mixer Item ref: 953.020 User Manual 2 balanced microphone inputs Lo-cut rumble filters 3-band EQ per Mic channel Switchable 48V phantom power 2 x A/B selectable stereo line inputs

More information

Audio & Data Transmission Solution FTA-108S FRA-108S

Audio & Data Transmission Solution FTA-108S FRA-108S Audio & Data Transmission Solution FTA/ Inter-M has developed solutions such as FTA/ to transmit High quality uncompressed multi-channel audio and control over TCP/IP networks, dedicated copper lines and

More information

CX-A6 Amplifier Installation & User Guide V9.0

CX-A6 Amplifier Installation & User Guide V9.0 CX-A6 Amplifier Installation & User Guide V9.0 Cloud Electronics Limited 140 Staniforth Road, Sheffield, S9 3HF England Tel + 44 (0) 114 244 7051 Fax + 44 (0) 114 242 5462 E-mail info@cloud.co.uk Web site

More information

ECI 6D. Balanced Integrated Amplifier. Owner's Manual. (with a built-in DAC) ENGLISH

ECI 6D. Balanced Integrated Amplifier. Owner's Manual. (with a built-in DAC) ENGLISH ECI 6D Balanced Integrated Amplifier (with a built-in DAC) Owner's Manual EN ENGLISH Unpacking the ECI 6D Immediately upon receipt of the ECI 6D, inspect the carton for possible damage during shipment.

More information

User Manual VOLUME PTT 1 MIC/LINE 2 MIC/LINE 3 MIC/LINE 4 MIC/LINE 5 MIC/LINE 6 MIC/LINE 7 MIC/LINE 8 MIC/LINE 9 MIC/LINE 10 LEVEL LEVEL TREBLE 6 MIC

User Manual VOLUME PTT 1 MIC/LINE 2 MIC/LINE 3 MIC/LINE 4 MIC/LINE 5 MIC/LINE 6 MIC/LINE 7 MIC/LINE 8 MIC/LINE 9 MIC/LINE 10 LEVEL LEVEL TREBLE 6 MIC + 7 54 ZM 0 Audio Mixer User Manual www.cleveracoustics.co.uk CAUTION RISK OF ELECTRIC SHOCK DO NOT OPEN. NO USER SERVICABLE PARTS INSIDE WARNING: TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK. DO NOT EXPOSE

More information

mix 502, mix 802, mix 1202FX mixer user manual

mix 502, mix 802, mix 1202FX mixer user manual mix 502, mix 802, mix 1202FX mixer user manual Musikhaus Thomann Thomann GmbH Hans-Thomann-Straße 1 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: info@thomann.de Internet: www.thomann.de

More information

PLE 2CS Plena Two-zone Call Station

PLE 2CS Plena Two-zone Call Station Communications Systems PLE 2CS Plena Two-zone Call Station PLE 2CS Plena Two-zone Call Station Modern two-zone call station for the PLE series Selectable gain Speech filter and limiter Output level control

More information

AX6220Z/AX6240Z. Energy-Efficient, DSP-Powered and Ethernet/USB-Controlled 1000/900-Watt 70/100 V High-Impedance Power Amplifier.

AX6220Z/AX6240Z. Energy-Efficient, DSP-Powered and Ethernet/USB-Controlled 1000/900-Watt 70/100 V High-Impedance Power Amplifier. Features Ultra-reliable, dual-channel 2*500/2*900-Watt power amplifier with 70/100 V technology, designed for continuous operation in distributed music, paging and AV applications State-of-the-art, energy-saving

More information

Professional Audio for your world

Professional Audio for your world General Catalogue 2014 Professional Audio for your world Summary Voice evacuation systems Multizone voice/music systems Interphone system for counters Page 6 Mixer Amplifiers Booster units Page 28 CMDS

More information

PM7400MKII. Instruction manual

PM7400MKII. Instruction manual PM7400MKII Instruction manual PM7400MKII Instruction manual 3 PM7400MKII Manual 4 Pre-amplifier Safety first! Caution: hot and sharp surfaces! This professional device needs to be installed by qualified

More information

M-300 Mono power amplifier User s guide

M-300 Mono power amplifier User s guide M-300 Mono power amplifier User s guide M-300 Mono power amplifier User s guide Specifications: Contents: Power output: 8Ω: 290W, 0.01% THD SPECIFICATIONS Page 2 Input impedance: Gain: 4Ω: 580W, 0.01%

More information

Multi-Channel, Network-Enabled

Multi-Channel, Network-Enabled 5-Year Warranty Hand-built in Webster, NY 70V Rated 100V Rated ne4250 NE SERIES Multi-Channel, Network-Enabled Power Amplifiers Our multi-channel ne (Networked-Enabled) Series Amplifiers are uniquely designed

More information

VX-3000 Series. Integrated Voice Alarm & Public Address System. ...yet still led out quickly and safely in an emergency.

VX-3000 Series. Integrated Voice Alarm & Public Address System. ...yet still led out quickly and safely in an emergency. www.toa.com.hk VX3000 Series Integrated Voice Alarm & Public Address System...yet still led out quickly and safely in an emergency. VX3000 Series Integrated Voice Alarm & Public Address System Description

More information

AXYS IndustryAmp PB-800

AXYS IndustryAmp PB-800 AXYS IndustryAmp PB-800 Datasheet by Geert de Vries IndustryAmp PB-800 datasheet User s Notice: No part of this document including the software described in it may be reproduced, transmitted, transcribed,

More information

PS 19 AM SINGLE CHANNEL BELTPACK IN METAL CASE WITH PGM (AUX) INPUT

PS 19 AM SINGLE CHANNEL BELTPACK IN METAL CASE WITH PGM (AUX) INPUT PS 19 AM SINGLE CHANNEL BELTPACK IN METAL CASE WITH PGM (AUX) INPUT USER MANUAL August 2016 This product is designed and manufactured by: ASL Intercom BV Zonnebaan 42 3542 EG Utrecht The Netherlands Phone:

More information

Ver Tornado KT2 - KT2C KTL2 - KTL2C. USER GUIDE English KT2 KTL2 KT2C KTL2C

Ver Tornado KT2 - KT2C KTL2 - KTL2C. USER GUIDE English KT2 KTL2 KT2C KTL2C Tornado KT2 - KT2C KTL2 - KTL2C USER GUIDE English KT2 KTL2 KT2C KTL2C TABLE of CONTENTS SYMBOLS... 3 1. INTRODUCTION... 4 2. KEY features... 4 4. APPLICATIONS... 4 3. OPTIONAL FEATURE... 4 5. SAFETY information...

More information

Primare A32 Amplifier User Guide

Primare A32 Amplifier User Guide > Primare A32 Amplifier User Guide i 0 Preface.pm7 1 > Preface COPYRIGHT AND ACKNOWLEDGMENTS Copyright 2005 Primare Systems AB. All rights reserved. Primare Systems AB Renvägen 1 SE-352 45 Växjö Sweden

More information

SPA2060, SPA2120, SPA2240 amplifier. User Manual

SPA2060, SPA2120, SPA2240 amplifier. User Manual SPA2060, SPA2120, SPA2240 amplifier User Manual User manual, SPA-10UMS01-V01R03 Delivering Your Message version revision date 01 03 09-09-2011 www.ateis-europe.com ATEÏS Europe BV - Sydneystraat 42-3047BP

More information

ZM-6. Professional 19 Rack Mixer USER MANUAL. Content

ZM-6. Professional 19 Rack Mixer USER MANUAL. Content Professional 19 Rack Mixer ZM-6 USER MANUAL Thank you for buying an LD Systems audio product. Please read these operating instructions carefully before you use the product for the first time and keep them

More information

Tel. 0621/ FAX 0621/

Tel. 0621/ FAX 0621/ Änderungen und Irrtümer vorbehalten Video VGA Gain Bandwidth Crosstalk Switching speed Unity 350 MHz (-3 db) -50 db @ 10 MHz, -30 db @ 100 MHz

More information

COMMERCIAL AUDIO SOLUTIONS FOR COMMERCIAL AUDIO AND PUBLIC ADRESS INSTALLATIONS

COMMERCIAL AUDIO SOLUTIONS FOR COMMERCIAL AUDIO AND PUBLIC ADRESS INSTALLATIONS COMMERCIAL AUDIO SOLUTIONS FOR COMMERCIAL AUDIO AND PUBLIC ADRESS INSTALLATIONS Pre-amplifiers, zonemixers, matrix mixers, amplifiers, mixer amplifiers, zonemixer amplifiers, DSP processors, DSP matrix

More information

The Alpha Omega 900 amplifies the best qualities of one of the most powerful and distinct Darkglass pedals ever made.

The Alpha Omega 900 amplifies the best qualities of one of the most powerful and distinct Darkglass pedals ever made. OWNER S MANUAL The Alpha Omega 900 takes the best elements of our most successful distortion preamplifier ever, combined with state-of-the-art features to make a monstrous 900-watt amplifier with earth-shattering

More information

MA V 35W Mixer Amplifier

MA V 35W Mixer Amplifier MA V W Mixer Amplifier User Manual MA Mixer Amplifier EQUALISER MASTER VOLUME POWER ON - + - + - + OFF MIC MIC LINE /LINE Hz khz khz POWER CONSUMPTION: W (max.) Order code: CRAM Safety advice WARNING FOR

More information

LA-SERIES LOOP AMPLIFIERS. Item ref: UK, UK User Manual

LA-SERIES LOOP AMPLIFIERS. Item ref: UK, UK User Manual LA-SERIES LOOP AMPLIFIERS Item ref: 952.864UK, 952.867UK User Manual Caution: Please read this manual carefully before operating Damage caused by misuse is not covered by the warranty SAFETY SYMBOL AND

More information

PowerMatch PM4250 / PM4250N TECHNICAL DATA SHEET. configurable power amplifier. Key Features. Product Overview. Applications

PowerMatch PM4250 / PM4250N TECHNICAL DATA SHEET. configurable power amplifier. Key Features. Product Overview. Applications Product Overview The Bose PowerMatch PM4250 configurable professional power amplifier provides concert-quality sound with a high level of scalability and configurability. The PM4250 offers multiple channel

More information

CX-A6 Amplifier Installation & User Guide V8.0

CX-A6 Amplifier Installation & User Guide V8.0 CX-A6 Amplifier Installation & User Guide V8.0 Cloud Electronics Limited 140 Staniforth Road, Sheffield, S9 3HF England Tel + 44 (0) 114 244 7051 Fax + 44 (0) 114 242 5462 E-mail info@cloud.co.uk Web site

More information

Dante Kit MEG basic

Dante Kit MEG basic PRODUCT SPECIFICATION 1/6 FEATURES Great speech intelligibility Phantom power via PoE Remote controllable gain level Daisy-chaining possible DELIVERY INCLUDES 1 SL DI 4 XLR Dante interface 4 MAT 133 tablestands

More information

plifier D-501 otion Am Tactile M

plifier D-501 otion Am Tactile M Tactile Motion Amplifier D-501 IMPORTANT SAFETY INSTRUCTIONS WARNING: 1. Read and keep these instructions for future reference. 2. Do not use this apparatus near water. 3. Clean only with a dry cloth.

More information

Dante Kit MEB 114-S. Thanks to its rugged housing and its high-quality microphone capsule the MEB 114-S ensures the best speech intelligibility.

Dante Kit MEB 114-S. Thanks to its rugged housing and its high-quality microphone capsule the MEB 114-S ensures the best speech intelligibility. PRODUCT SPECIFICATION 1/6 FEATURES Great speech intelligibility Phantom power via PoE Remote controllable gain level Daisy-chaining possible DELIVERY INCLUDES 1 SL DI 4 XLR Dante interface 4 MEB 114-S

More information

KXR. Owner, s Manual. One hundred KEYBOARD EXTENDED RANGE TYPE: PR 262 P/N

KXR. Owner, s Manual. One hundred KEYBOARD EXTENDED RANGE TYPE: PR 262 P/N THE SOUND THAT CREATES LEGENDS KEYBOARD EXTENDED RANGE KXR One hundred TYPE: PR 262 Owner, s Manual P/N 047761 KXR 100 Owner s Manual Congratulations on your purchase of the Fender KXR 100 keyboard amplifier.

More information

PAM-240/360 Public Address Amplifier

PAM-240/360 Public Address Amplifier PAM-240/360 Public Address Amplifier PAM-240 PUBLIC ADDRESS AMPLIFIER CLIP 0-6 -8-11 -14-19 PROT CHANNEL 1 CHANNEL 2 CHANNEL 3 CHANNEL 4 CHANNEL 5 CHANNEL 6 BASS TREBLE MASTER CHIME SP 1 SP 2 SP 3 SP 4

More information

USER GUIDE English. Tornado KT2 - KT2-HV KT2C - KT2C-HV KTL2 - KTL2-HV KTL2C - KTL2C-HV KT2 - KT2-HV KTL2 - KTL2-HV KT2C - KT2C-HV KTL2C - KTL2C-HV

USER GUIDE English. Tornado KT2 - KT2-HV KT2C - KT2C-HV KTL2 - KTL2-HV KTL2C - KTL2C-HV KT2 - KT2-HV KTL2 - KTL2-HV KT2C - KT2C-HV KTL2C - KTL2C-HV Tornado KT2 - KT2-HV KT2C - KT2C-HV KTL2 - KTL2-HV KTL2C - KTL2C-HV USER GUIDE English KT2 - KT2-HV KTL2 - KTL2-HV KT2C - KT2C-HV KTL2C - KTL2C-HV NEW All Tornado models are also available in a 70V version!

More information

MA120 - MA240 Instruction manual

MA120 - MA240 Instruction manual MA120 - MA240 Instruction manual MA120 / MA240 Instruction manual 3 MA120 / MA240 manual 4 Mixing amplifiers Safety instructions Caution! This professional device needs to be installed by qualified personnel

More information

pêma protea êquipped media amplifier

pêma protea êquipped media amplifier Powered Matrix Processors pêma protea êquipped media amplifier pêma 4125 4250 8125 8250 pêma specifications Features: Powered Processors Ashly Audio s promise to Simplify Integration continues with pêma

More information

SPNCWB. Wideband Bridging Conference Interface TECHNICAL DATA

SPNCWB. Wideband Bridging Conference Interface TECHNICAL DATA SPNCWB Wideband Bridging Conference Interface TECHNICAL DATA Quad-reference Wideband Acoustic Echo Canceller supporting 3-way Bridging Two maximum speed grade, 4th generation SHARC processors* Dual Codec

More information

PA0688 Microphone Pre-Amplifier Module

PA0688 Microphone Pre-Amplifier Module PA0688 Microphone PreAmplifier Module Installation and Operating Instructions Description The PA0688 Microphone Preamplifier board is intended to provide emergency and nonemergency microphone preamplification

More information

02/11/2015

02/11/2015 Modem communication plug and play solutions GSM Part number 88970119 For remote control of your application Automatic notification of alarms via SMS (GSM Modem) / email or on a PC with M3 ALARM software.

More information

PLENA SOLUTIONS F E A T U R E S PUBLIC ADDRESS GUIDE

PLENA SOLUTIONS F E A T U R E S PUBLIC ADDRESS GUIDE PUBLIC ADDRESS GUIDE PLENA SOLUTIONS Plena - latin for complete P L E N A E L E C T R O N I C L I N E M O D E L S PLE-1MA030-US 30W Single Zone Mixer Amplifier PLE-1MA060-US 60W Single Zone Mixer Amplifier

More information

UMA 4300 Professional Series Installation Power Amplifer Owner s Manual

UMA 4300 Professional Series Installation Power Amplifer Owner s Manual 1 UMA 4300 Professional Series Installation Power Amplifer Owner s Manual UMA 4300 Professional Installation Power Amplifier ENGLISH The UMA 4300 is a high quality, commercial grade analog audio mixer/amplifier.

More information