1 CITY OF TACOMA Transmission & Distribution ADDENDUM NO. 1 DATE: May 3, 2017 REVISIONS TO: Request for Bids Specification No. PT N Solid Insulation Distribution Transformer NOTICE TO ALL: RESPONDENTS: This addendum is issued to clarify, revise, add to or delete from, the original specification documents for the above project. This addendum, as integrated with the original specification documents, shall form the specification documents. The noted revisions shall take precedence over previously issued specification documents and shall become part of this contract. REVISIONS TO THE SUBMITTAL DEADLINE: The submittal deadline has been changed to 11:00 a.m., Pacific Time, Monday, May 08, REVISIONS TO SECTION 3 - TECHNICAL PROVISION: Replace existing Section 3 with the below Technical Provisions. NOTE: Acknowledge receipt of this addendum by initialing the corresponding space as indicated on the Request for Quotations page. Vendors who have already submitted their bid/proposal may contact the Purchasing Division at and request return of their bid/proposal for acknowledgment and resubmittal. Or, a letter acknowledging receipt of this addendum may be submitted in an envelope marked Specification No. PT N, Addendum No.1. The City reserves the right to reject any and all bids, including, in certain circumstances, for failure to appropriately acknowledge this addendum. cc: Kim Kerner, Roberta Cox Form No. SPEC-220A Revised: 07/30/2015

2 Return Bids By 11:00 AM, 05/08/2017 to: Seth J Hartz ABN 4th Floor NE 3628 South 35th Street Tacoma WA Ph Fax Material will ship to: T&D Administration 3628 S 35th St Tacoma WA CITY OF TACOMA THIS IS NOT AN ORDER All prices quoted shall be F.O.B. Destination, Freight Prepaid and Allowed Page 1 of 2 All responses & inquiries must be plainly marked with this REQUEST FOR QUOTATION RFQ Information Collective Bid # PT N Bid Issue Date 04/13/2017 Vendor Number WEB VENDOR FOR RFQ Vendor Information (vendor to complete) Firm Name: Address: City/State/Zip / / Phone/Fax / Contact Name Payment Terms %, days (e.g. 2% 10,N30) Tacoma Bus. Lic. # Taxpayer ID # SIGNATURE OF PERSON AUTHORIZED TO SIGN THIS BID x DATE: / / NAME : TITLE : Item # Material# Delivery QTY UM Net Price Total Description Date ***The City of Tacoma will accept mailed bid submittals sent to sendbid@cityoftacoma.org for this solicitation. Please include the Collective Bid Number in the subject line of your . Bids are subject to the submittal deadline noted in the bid solicitation document. The time of receipt will be considered as the time of submittal. Submittals are accepted by one of the following delivery methods: , facsimile, or mail. The City accepts no responsibility for transmission errors. The City of Tacoma is soliciting bids for PT N Solid Insulation Distribution Transformer Responses must be submitted on the provided City of Tacoma bid solicitation form. Vendor signature is mandatory. All bid pricing shall be FOB Destination, freight prepaid and included in the unit price. Items must be new and unused. Any bidder may be notified to clarify their bid proposals. This action

3 CITY OF TACOMA THIS IS NOT AN ORDER All prices quoted shall be F.O.B. Destination, Freight Prepaid and Allowed Page 2 of 2 All responses & inquiries must be plainly marked with this REQUEST FOR QUOTATION Item # Material# Delivery QTY UM Net Price Total Description Date shall not be construed as negotiations or an indication of intentions to award. The bidder must be able to provide the information within two (2) business days. Purchasing related questions: Seth Hartz, shartz@cityoftacoma.org Addendum No. 1 - Submit this Request for Quotation page acknowledging addendum in place of the original. ***Please initial receipt of addendum No 1: (Initials) and return with your bid submittal Wire Solid Insulation Distribution 5 EA Transformer # 50kVA 20 4 Wire Solid Insulation Distribution 3 EA Transformer # 100kVA 30 Injection Shell 2 EA Line item included to identify any additional charges for the manufacturing of a custom mold design. Net Value $ Plus Tax at % $ Total Amount $

4 SECTION 3 - TECHNICAL PROVISIONS These Technical Specifications have been prepared by a licensed Professional Engineer registered in the State of Washington STANDARDS & TERMINOLOGY Terminology used in this specification is consistent with IEEE C unless otherwise noted STANDARDS All transformers shall meet the most recent editions of the following standards and all others that are applicable: Standard Number IEEE 386 Standard Title SEPARABLE INSULATED CONNECTOR SYSTEMS FOR POWER DISTRIBUTION SYSTEMS ABOVE 600 V IEEE C IEEE C IEEE C IEEE C IEEE C IEEE C IEEE C ANSI Z535 ANSI C119.4 NEMA TR 1 GENERAL REQUIREMENTS FOR LIQUID-IMMERSED DISTRIBUTION, POWER, AND REGULATING TRANSFORMERS General Requirements for Dry-Type Distribution and Power Transformers Including Those with Solid Cast and/or Resin Encapsulated Windings SUBMERSIBLE SINGLE-PHASE TRANSFORMERS: 167 KVA AND SMALLER; HIGH VOLTAGE V AND BELOW; LOW VOLTAGE 600 V AND BELOW PAD-MOUNTED-TYPE, SELF-COOLED, SINGLE-PHASE DISTRIBUTION TRANSFORMERS 250 KVA AND SMALLER: HIGH VOLTAGE, GRDY/ V AND BELOW; LOW VOLTAGE, 480/240 V AND BELOW TERMINOLOGY FOR POWER AND DISTRIBUTION TRANSFORMERS TEST CODE FOR LIQUID-IMMERSED DISTRIBUTION, POWER, AND REGULATING TRANSFORMERS TEST CODE FOR DRY-TYPE DISTRIBUTION AND POWER TRANSFORMERS SAFETY SIGN AND LABEL STANDARDS ELECTRICAL CONNECTORS CONNECTORS TO USE BETWEEN ALUMINUM-TO-ALUMINUM OR ALUMINUM-TO-COPPER CONDUCTORS DESIGNED FOR NORMAL OPERATION AT OR BELOW 93 DEGREES C AND COPPER-TO-COPPER CONDUCTORS DESIGNED FOR NORMAL OPERATION AT OR BELOW 100 DEGREES C TRANSFORMERS, REGULATORS, AND REACTORS

5 ENCLOSURE SPECIFICATIONS DIMENSIONS The maximum dimensions of the submersible transformers should be as shown below. Secondary cable leads are not included. 50 kva and Below 75 kva & 100 kva Length 24 +/ /- 1 Width 24 +/ /- 1 Depth/Height 20 +/ / ENCLOSURE MATERIAL The core-coil assembly shall be encapsulated in a thermo-plastic material that shall serve as the unit enclosure. The thermo-plastic material shall: be non-hygroscopic (does not absorb moisture from the air). provide moisture immunity to depth of 6 feet of water per IEEE Standard 386. o All terminals that extend from the core-coil to external positions shall be sealed to meet this requirement. be corrosion free in the presence of road salts, salt water immersion, petroleum products. require no future maintenance to maintain its corrosion resistance or water penetration UNIT FRAME The encapsulated unit shall be mounted within a corrosion resistant frame that will include: 4 point lifting provisions positioned for balanced lifting o Each lifting position shall be rated for the weight of the unit. o The provisions shall accept: 3/4 shackles 12 kips rated. 1-1/2 (3.8 cm) lifting straps Minimum of two stainless steel parking stands per Section Bonding provisions that will allow for the frame to be grounded to the encapsulated unit. The frame shall allow for the unit to be mounted: Floor installations (Horizontal) CROWNING The unit and frame shall be designed to avoid the pooling of water.

6 NAMEPLATE INFORMATION The nameplate shall meet the intent of IEEE C The nameplate shall include: Manufacture Name Manufacture Location Year of Manufacture Model Number (If not included the serial number) Serial Number City of Tacoma PO# Graphical representation of the winding configurations with polarity clearly marked per IEEE Stds Winding material Insulating/Encapsulation material KVA Rating High-Voltage & Low-Voltage Ratings Design Impedance Temperature Rise Ratings BIL Ratings Weight of the unit with & without frame Statement clearly stating that there are no fluids contained within the unit INSULATION LEVEL The insulation class and basic lightning impulse insulation levels (BIL) for the windings and terminals shall be as shown below: Components Insulation Class BIL High voltage winding and terminals 15 kv 95 kv Low voltage windings and terminals 1.2 kv 30 kv Secondary neutral terminal 1.2 kv 30 kv

7 APPARATUS SPECIFICATIONS ARRAINGMENT OF BUSHINGS The physical arrangement of the high side and low side terminations shall be as shown below PARKING STANDS Minimum of two stainless steel parking stands (Detail A, Figure 2A, IEEE C ): Each will allow for the application of an IEEE kV Loadbreak Portable Feedthru connector (aka: feed-thru parking bushing, see Eaton/Cooper Power rary/500_loadbreakconnectors/ca650072en.pdf ) for parking and grounding of 15kV cable. The location of the parking stands shall allow for minimal movement of the 200A IEEE 386 Load-break elbows GROUNDING ATTACHMENTS Two tin-plated copper grounding pads extending on either side of the transformer. Each pad shall have 2 holes per NEMA Std PRIMARY, HIGH-VOLTAGE, TERMINATIONS The following is required for the primary terminations A BUSHING WELL The bushing well shall: be per Figure 3 of IEEE 386, o able to accept a 15 kv, 200A load-break bushing insert, such as Cooper Power Systems Catalog No. LBI215, or equivalent include a replaceable copper 3/8 inch - 16 UNC stud be shipped with suitable dust covers covers that will withstand transportation from the factory, to Tacoma Power, to the job site as approved.

8 SECONDARY AND NEUTRAL LOW-VOLTAGE TERMINATIONS Each secondary terminal shall extend 6 feet (1.8 m) of cable meeting IEEE Std C Section 6.2 for low-voltage cable leads. (Requirement for minimum of 90 o C 600V application) A SECONDARY CABLE Each secondary cable extensions shall be made up of two segments of cable: Segment Fixed Cable (Winding Extension) Extension Cable (Service Cable) Secondary Connection Requirement The secondary cable shall be composed of fixed flexible cable lead extending 3 ft. (0.9 m) beyond the enclosure of the transformer. The cable shall meet IEEE Std 1580 and UL Std 1309 for 2kV(HD) 110 o C or functional equivalent flexible copper cable and shall be secured to limit physical stress to internal connections to the windings. The extension cable shall be Class B copper cable per Table 3 of IEEE Std C The fixed cable segment shall be connected to the extension cable segment by a compression connector meeting ANSI Std C119.4 covered by a heavy wall heat shrink insulating cover equivalent to TE Raychem WCSM units A.1 SECONDARY CABLE SIZE & STRANDING kva # / Terminal Cable Size Fixed Cable Extension Cable Stranding Cable Size Stranding /0 AWG 532 4/0 AWG /0 AWG 532 4/0 AWG kcmil kcmil kcmil kcmil kcmil kcmil B CONDUCTOR JACKETS The conductor jackets shall meet ICEA S / NEMA WC7 (Cross-Linked- Thermosetting-Polyethylene-Insulated or Cross-Linked-Polyolefin-Insulated) per terminal position shall be as follows: Terminals Jacket Color Fixed Cable Extension Cable X1 & X4 All Black Jacket All Black Jacket X2 & X3 All Black Jacket Black Jacket with permanent Yellow marking / stripe

9 3.04 CORE-COIL SPECIFICATIONS DESIGN REQUIRMENTS The transformers purchased per this specification shall meet the following requirements: Characteristic Requirement Frequency Core Temp Insulation temperature Insulation Type Efficiency 60-hertz 100 o C Rise 200 o C Submersible Type - Solid Insulation without using fluids or gases Meets DOE efficiency requirements per Code of Federal Regulations 10 CFR Energy Conservation Standards and Their Effective Dates Section o Part (c) Medium Voltage Dry-Type Distribution Transformers, Table (2)Efficiency requirements for after January 1, 2016 kva Single-phase BIL* kv Efficiency (%) CORE-COIL SCHEMATICS

10 NOISE LIMITS The noise, under normal operation of the transformer, shall be within the limits of NEMA Standard TR-1 per Table 0-3. The transformers shall be tested per IEEE C , Section 13. KVA Rating Sound Level (db) IMPEDANCE All transformers shall be designed to limit the primary fault current on a bolted secondary fault to the IEEE C maximum CORE CONSTRUCTION All cores shall be made of high-grade silicon steel. Amorphous core transformers are not acceptable for this specification. o Laminations shall be free of burrs, properly annealed, and furnished with a heat resistant insulating coating. All transformer core sections shall be grounded to the grounding tabs with supplemental bonding to the frame. o Core steel banding straps shall not be used for grounding the core The core-coil assembly shall be constructed so as to be secured against shifting due to transport, movement & installation, and secondary faults. o All welds on core braces and interior structures shall be smooth, free from splatter, and clean WINDING COIL CONSTRUCTION Primary Winding Secondary Winding Primary coils will use insulated copper wire. Secondary coils will use insulated aluminum or copper conductor. The insulation shall be suitable for 200 o C and be compatible with encapsulation molding process CORE-COIL INSULATION All solid insulating materials shall be non-hygroscopic. The windings shall be totally vacuum molded in epoxy resin using an automatic pressure gelation (APG) process which shall result in a solid insulated part with no interior voids containing air or gases of any sort.

11 3.05 TESTING & REPORTING All factory tests shall be made in accordance with ANSI/IEEE C , C and C with the following exceptions: Partial discharge test FACTORY TESTS Each transformer shall have the following tests performed at the factory prior to shipment: A. Ratio Tests B. Polarity C. No-load losses be the average-voltage voltmeter method at i. 100% of rated voltage (7200V or 120/240V) and ii. 105% of rated voltage (7560V or 126/252V) D. Exciting current by the average-voltage and rms ammeter method to be performed at: i. 100% of rated voltage (7200V or 120/240V) and ii. 105% of rated voltage (7560V or 126/252V) If required, corrections to a sine-wave basis shall be made by the crest-ammeter method. E. Load losses F. Impedance voltage G. Applied potential tests H. Induced potential tests I. Insulation resistance tests J. Line impulse test consisting of 2 full waves performed on the primary terminals. i. If a design impulse test is order for the 1 st transformer of the order, this transformer may be excluded from the test PARTIAL DISCHARGE TEST A. Phase to ground pre-stress voltage of 1.8 Ur (1.8 x 7200V = 12,960V) shall be induced for 30 seconds, Followed immediately afterward without interruption by a: B. Phase to ground voltage of 1.3 Ur (1.3 x 7200V = 9360V) for 3 minutes during which partial discharge is measured i. The maximum measured partial discharge during this test shall not exceed 10 pc CERTIFIED TEST REPORTS Upon completion of testing a copy of certified test reports shall be furnished to Tacoma Power for review prior to shipment.

12 DATA REPORTS Prior to shipment the following steps will be followed concerning the delivery of data required. Step Action Upon issuance of a Purchase Order the Tacoma Power contract manager will the appropriate representative of the Supplier and/or manufacturer a Microsoft Excel spreadsheet that includes the number of transformers and their pre-assigned Tacoma SAP Equipment numbers. The manufacturer will join individual transformer serial numbers with the Tacoma SAP Equipment numbers. The manufacturer will test assembled units and apply the Tacoma SAP Equipment numbers onto the units as required by Section of the Technical Provisions. The complete spreadsheet is then sent back to the contract manager prior to shipment of the units. The following information is required: Serial Number Year of Manufacture Month of Manufacture No-Load Loss Full Load Loss Weight % Impedance X / R Efficiency value PCB Content (submit 0) Oil Capacity (submit 0) Oil Type (submit 0) A SUBMISSION OF DATA REPORTS Data reports shall be submitted via to: Roberta Cox rcox@cityoftacoma.org DATA REPORT EXAMPLEA

13 3.06 EQUIPMENT NUMBERS, STENCILING AND LABELS VOLTAGE DESIGNATIONS In addition to the KVA being stenciled on the units, Tacoma Power wishes for the voltage designations to be stenciled as well A SIZE AND COLOR OF KVA & VOLTAGE DESIGNATIONS The stencils shall be the color of standard white as used with other identifying markings applied by the supplier. KVA Size Terminal Marking Designation Stencil Size Reference Section B 240/ /4 480/ / CITY OF TACOMA TRACKING NUMBERS (SAP #) Tacoma Power is requiring that the vendor have unique tracking numbers (SAP Equipment Number) supplied by Tacoma Power s data management section stenciled on the units as shown below A SIZE AND COLOR OF NUMBERS The seven digit SAP numbers shall be 1 stencils in the color of standard white as used with other identifying markings applied by the supplier B LOCATION OF NUMBERS ON UNITS Shall be visible from above SAFETY LABELS Current ANSI Z535 approved DANGER labels, free of wrinkles and air bubbles, shall be visible from above.

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical

More information

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Issued by: Approved by: Engineering Department Energy+ Inc. September 2016 Shawn Jackson, P.Eng. Approval is given in accordance with

More information

Howard Smart Transformer Specification Guide

Howard Smart Transformer Specification Guide Howard Smart Transformer Specification Guide General Requirements Overhead pole-type smart distribution transformers shall be single phase, 60 Hz, mineral-oil filled and self-cooled and shall conform as

More information

Distribution Transformers

Distribution Transformers Distribution Transformers Single-Phase Pad-mounted Functional Specification Guide Functional Specification for Single-Phase Pad-Mounted Type Distribution Transformers 5 167 kva 1.0 Scope 1.1 This specification

More information

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric

More information

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016) Typical Specification 1.2kV Class Energy Efficient Dry-Type Distribution Transformers Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016) Canada 595 Southgate Drive Guelph, Ontario N1G

More information

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial

More information

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable: Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.

More information

SECTION TRANSFORMERS

SECTION TRANSFORMERS SECTION 16460 - TRANSFORMERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Section

More information

Distribution/Substation Transformer

Distribution/Substation Transformer Distribution/Substation Transformer Type VFI, Vacuum Fault Interrupter Transformer Option Functional Specification Guide Functional specification for 15 kv, 25 kv, or 35 kv vacuum fault interrupter distribution/substation

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads. -156 Purpose & Industrial Control Purpose (1000 kva and Below) mounted dry-type transformers of the two-winding type, self-cooled, with ratings and voltages as indicated on the drawings. shall be manufactured

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

CITY OF TACOMA Tacoma Power/Transmission & Distribution

CITY OF TACOMA Tacoma Power/Transmission & Distribution CITY OF TACOMA Tacoma Power/Transmission & Distribution ADDENDUM NO. 1 DATE: November 6, 2017 REVISIONS TO: Request for Bids Specification No. PT17-0442N Surplus Overhead Distribution Transformer NOTICE

More information

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CONTENTS COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CONSTRUCTION... 4 ~ 5 A. CORE AND FRAME... 4 B. COIL... 5 C. TEMPERATURE INDICATOR... 5 CHARACTERISTICS... 6 MANUFACTURING FACILITIES...

More information

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS Acme offers a large selection of Dry-Type Distribution Transformers. Ranging from 600 Volt and below, in both Single and Three Phase, you re sure to find

More information

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.

More information

SECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE

SECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE SUBSTATION TRANSFORMERS DRY-TYPE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the primary and/or secondary substation transformers as specified herein and as shown

More information

Liquid-Filled Transformers

Liquid-Filled Transformers Liquid-Filled Transformers Custom Transformers at Standard Prices NIAGARA TRANSFORMER CORP. Induction Furnace Transformer Cycloconverter Rectifier Duty Transformer Arc Furnace Transformer Full Range of

More information

Section 2 Outdoor Voltage Transformers

Section 2 Outdoor Voltage Transformers Section 2 Outdoor Voltage Transformers GE Meter 130 Main St., Somersworth, NH 03878 USA & Canada: (800) 626-2004 Fax: (518) 869-2828; GE Worldwide: (518) 869-5555 2-1 120 V to 600 V BIL 10 kv Outdoor Voltage

More information

Substation transformers

Substation transformers Substation transformers Triplex Indoor Power Centers Functional specification guide Functional specification for Triplex Indoor Power Centers (IPC) 750 2500 kva 1.0 Scope 1.1. This specification covers

More information

Reactor and inductor are names used interchangeably for this circuit device.

Reactor and inductor are names used interchangeably for this circuit device. Recommended Design Criteria for Air-Cooled Reactor for Line and Track Circuits Revised 2015 (7 Pages) A. Purpose This Manual Part recommends design criteria for an air-cooled reactor for line and track

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester s Catalog Data CA3508EN Supersedes November 015 COOPER POWER SERIES POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) General Eaton s Cooper Power series POSI-BREAK M.O.V.E. surge arrester combines metal

More information

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS Management has tentatively approved your request subject to the following conditions: 1. All distribution materials/equipment must be purchased

More information

TRANSMITTAL LETTER. As Builts Change Order Contract Copy of Letter Insurance. For approval Approved as submitted Resubmit copies for approval

TRANSMITTAL LETTER. As Builts Change Order Contract Copy of Letter Insurance. For approval Approved as submitted Resubmit copies for approval Redwood City Electric, Inc. TRANSMITTAL LETTER To: Transworld Construction, Inc. 1178 Folsom Street San Francisco, CA 94103 Date: 05/31/12 Job #: 9340 Regarding: SFO DATA CENTER Attn: Rob Acero We are

More information

Specialty Switches. Inertia Engineering & Machine Works, Inc Hardaway Road, Stockton CA 95215

Specialty Switches. Inertia Engineering & Machine Works, Inc Hardaway Road, Stockton CA 95215 Specialty Switches Inertia Engineering & Machine Works, Inc. 6665 Hardaway Road, Stockton CA 95215 Tel: 800-791-9997 Fax: 209-931-8186 E-mail: sales@inertiaworks.com Section 4 - Specialty Switches Specialty

More information

2.4. Transformers. Contents Description General-Purpose Encapsulated Transformers Catalog Number Selection... Product Selection... Product Description

2.4. Transformers. Contents Description General-Purpose Encapsulated Transformers Catalog Number Selection... Product Selection... Product Description General-Purpose Encapsulated.4 Type EP 3 5 Contents Description General-Purpose Encapsulated Catalog Selection................ Product Selection....................... Single-Phase..........................

More information

SECTION MEDIUM-VOLTAGE CABLES

SECTION MEDIUM-VOLTAGE CABLES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 13 MEDIUM-VOLTAGE CABLES SPEC WRITER NOTE: Delete between //-----// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

T S 15KVA 1PH 240/480 Transformer

T S 15KVA 1PH 240/480 Transformer 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 T2535173S 15KVA 1PH 240/480 Transformer Acme Electric Catalog Number Manufacturer Description Weight per unit Product

More information

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated Catalog 7400CT1001 2010 Class 7400 CONTENTS Description.............................................

More information

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester Surge Arresters Catalog Data CA235025EN Supersedes November 2015 COOPER POWER SERIES Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester General Eaton combines metal (zinc) oxide varistor technology in

More information

REQUEST FOR QUOTATION INVITATION

REQUEST FOR QUOTATION INVITATION REQUEST FOR QUOTATION INVITATION DATE: July 15, 2010 DPS: REQUIREMENT: SUBJECT: Patricia Farina DPS Contract Administrator Email: Patricia.Farina@cityofchicago.org Telephone: 312-744-7660 Silver Halide

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

DTS ISOLATION TRANSFORMER SPECIFICATIONS

DTS ISOLATION TRANSFORMER SPECIFICATIONS 1.1 Scope of Work: DTS ISOLATION TRANSFORMER SPECIFICATIONS The DTS transformers shall be designed to supply isolated power to sensitive computer based equipment. The DTS units will meet or exceed the

More information

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410 DOCUMENT 009104 - ADDENDUM NO. 4 Issued to all Bidders: Date: October 14, 2015 Contract Name: Electrical Installation Contract Number: C8410 This addendum forms a part of the Bid described above. The original

More information

Shrink temperature of 120 C. Rated for 600V, 90 C continuous use. T&B recommended up to 1kV. HS Series Specifications

Shrink temperature of 120 C. Rated for 600V, 90 C continuous use. T&B recommended up to 1kV. HS Series Specifications HS Series Made of thermally stabilized cross-linked polyolefin, enabling a recovered wall thickness greater than that of the cable jacket replaced Withstands severe mechanical requirements of U.R.D., submersible,

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL SINGLE PHASE INSTRUCTION MANUAL DIAGRAM D This manual applies to all single-phase buck & boost transformers sold by Larson Electronics. Please refer to the connection diagram on pages 4-6 for properly

More information

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT

More information

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 13 DISTRIBUTION SWITCHBOARDS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY

More information

Electrical Wiring: Commercial, Seventh Canadian Edition

Electrical Wiring: Commercial, Seventh Canadian Edition Electrical Wiring Commercial Canadian 7th Edition Mullin SOLUTIONS MANUAL Full download at: https://testbankreal.com/download/electrical-wiring-commercialcanadian-7th-edition-mullin-solutions-manual/ Unit

More information

50-SDMS-01 SPECIFICATIONS FOR

50-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------

More information

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents.

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. SECTION 26 05 19 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. 1.2 CONTRACTOR SUBMITTALS A. The

More information

Shrink temperature of 120 C. High-impact, abrasion, corrosion and chemical resistance. Rated for 600V, 90 C continuous use

Shrink temperature of 120 C. High-impact, abrasion, corrosion and chemical resistance. Rated for 600V, 90 C continuous use HS Series 3:1 Shrink Ratio Made of thermally stabilized cross-linked polyolefin, enabling a recovered wall thickness greater than that of the cable jacket replaced Withstands severe mechanical requirements

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 11 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between // -- // if not applicable to project. Also delete any other item or paragraph

More information

35 kv Class M.O.V.E. DirectConnect elbow arrester

35 kv Class M.O.V.E. DirectConnect elbow arrester Surge Arresters Catalog Data CA235026EN Supersedes November 2015 COOPER POWER SERIES 35 kv Class M.O.V.E. DirectConnect elbow arrester General Eaton's Cooper Power series M.O.V.E. DirectConnect elbow arrester

More information

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

INSTALLATION, OPERATION AND MAINTENANCE GUIDE INSTALLATION, OPERATION AND MAINTENANCE GUIDE FOR INDOOR/OUTDOOR SINGLE PHASE ENCAPSULATED TRANSFORMERS Indoor/Outdoor Encapsulated Transformers The pictures used in this guide are only a representation

More information

A. Product Description: Stranded conductor insulated wire.

A. Product Description: Stranded conductor insulated wire. SECTION 16120CPPR CONDUCTORS AND CABLE PART 1 - GENERAL 1.1 SYSTEM DESCRIPTION A. Product Requirements: Provide products as follows: 1. All building wire shall be stranded copper (no aluminum wire). 2.

More information

Steps for Selecting the Proper Transformer

Steps for Selecting the Proper Transformer SECTION I Page 4 Steps for Selecting the Proper Transformer SINGLE PASE LOADS 1. Determine electrical load A. Voltage required by load. B. Amperes or KVA capacity required by load. C. Frequency in z (cycles

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

Hilti, Inc. November Dallas Parkway, Suite 1000 Plano, Texas Toll Free Website Guide Specification

Hilti, Inc. November Dallas Parkway, Suite 1000 Plano, Texas Toll Free Website  Guide Specification Hilti, Inc. November 2015 7250 Dallas Parkway, Suite 1000 Plano, Texas 75024 Toll Free 800-879-8000 Website www.us.hilti.com Guide Specification Specifier Notes: This guide specification is written in

More information

Heat-Shrinkable Tubing

Heat-Shrinkable Tubing HS Series 3:1 Shrink Ratio Made of thermally stabilized cross-linked polyolefin, enabling a recovered wall thickness greater than that of the cable jacket replaced Withstands severe mechanical requirements

More information

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

11-SDMS-03 REV. 02 SPECIFICATIONS FOR 11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice

More information

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer PANELMDP Main Distribution Panel Eaton Corp Catalog Number Manufacturer Description Weight per unit Product Category Descriptions Product Type PANELMDP Eaton Corp 1.0 (lbs/each) Three Phase Energy Efficient

More information

ADDENDUM NO. 3 DATE: November 2, 2017

ADDENDUM NO. 3 DATE: November 2, 2017 City of Tacoma CITY OF TACOMA ADDENDUM NO. 3 DATE: November 2, 2017 REVISIONS TO: Request for Proposals Specification CT17-0359F Citywide Printing and Binding Services NOTICE TO ALL RESPONDENTS: This addendum

More information

SECTION 5 TRANSFORMERS

SECTION 5 TRANSFORMERS SECTION 5 TRANSFORMERS Necessary transformers will be installed and maintained by The City of Aspen. The City of Aspen will not furnish transformers unless they are of standard size and voltage as established

More information

75 kva Isolation Transformer - 480V Delta Primary - 208V Delta Secondary - NEMA 3R

75 kva Isolation Transformer - 480V Delta Primary - 208V Delta Secondary - NEMA 3R 75 kva Isolation Transformer 480V Delta Primary 208V Delta Secondary NEMA 3R Part #: MTDOE163P480D75KVA208DN3R Page: 1 The MTDOE163P480D75KVA208DN3R 480D 3 Phase Energy Efficient Isolation Transformer

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY Section 16195 A. This Section includes electrical identification for the following: 1. Nameplates and labels 2. Wire and cable markers 3. Conduit markers 4. Cable tray markers

More information

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid. 1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS361. 2. Standards All the standards referred

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SPECIAL SPECIFICATION Inch LED Traffic Signal Lamp Unit

SPECIAL SPECIFICATION Inch LED Traffic Signal Lamp Unit 1993 Specifications SPECIAL SPECIFICATION 1201 12 Inch LED Traffic Signal Lamp Unit 1. Description. This specification describes the minimum acceptable design and performance requirements for a twelve

More information

75 kva Isolation Transformer V Delta Primary Voltage - 480Y/277 Secondary Voltage - NEMA 3R

75 kva Isolation Transformer V Delta Primary Voltage - 480Y/277 Secondary Voltage - NEMA 3R 75 kva Isolation Transformer 4160V Delta Primary Voltage 480Y/277 Secondary Voltage NEMA 3R Part #: MTISX3P4160D75KVA480Y.277N3R Page: 1 The MTISX3P4160D75KVA480Y.277N3R 4160D 3 Phase Energy Efficient

More information

HPS Universal BUCK-BOOST TRANSFORMERS

HPS Universal BUCK-BOOST TRANSFORMERS BUCK-BOOST TRANSFORMERS Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

1.5 kva Single Phase Transformer - 120V Primary Voltage - 277V Secondary Voltage - NEMA 3R

1.5 kva Single Phase Transformer - 120V Primary Voltage - 277V Secondary Voltage - NEMA 3R 1.5 kva Single Phase Transformer 120V Primary Voltage 277V Secondary Voltage NEMA 3R Part #: MT120V1.5KVA277V Page: 1 The MT120V1.5KVA277V 120V 1 Phase Energy Efficient Transformer from Larson Electronics

More information

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING 1.0 General This specification covers the electrical characteristics and general

More information

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %

More information

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator) PRODUCT SPECIFICATION FOR A 15 THRU 500 kva, THREE PHASE, MODULAR POWER REGULATOR AND CONDITIONER PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator) 1.0 General This specification covers the electrical

More information

ADDENDUM NO. 1 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO.

ADDENDUM NO. 1 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO. ADDENDUM NO. 1 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO. PS 061 SEVEN SPRINGS WASTEWATER TREATMENT FACILITY IMPROVEMENTS PASCO COUNTY,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 01 3300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

3Ø Short-Circuit Calculations

3Ø Short-Circuit Calculations 3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective

More information

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems Arild Furnes,ATPA OGP/Petrobras workshop, 22.09.09 Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems September 24, 2009 Slide 1 Transformers for Ships and Offshore -

More information

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK PART 1.0 GENERAL 1.1 SCOPE A. This specification contains the minimum requirements for the design, manufacture and testing of a UL listed,

More information

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv) Outdoor Transmission (69 kv through 230 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The circuit-switcher shall conform to the following specification. 1.02 The circuit-switcher shall be

More information

SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Mechanical Design. Brian Brinson Mechanical Design Manager.

Mechanical Design. Brian Brinson Mechanical Design Manager. Mechanical Design Brian Brinson Mechanical Design Manager brian.brinson@spx.com September 26, 2018 Agenda 1. Design Process 2. Pre-Approval Drawings Bid Drawings Preliminary Drawings 3. Approval Package

More information

7.5 kva Isolation Transformer - 460V Primary - 230V Secondary - NEMA 3R - Single Phase - 50/60 Hz

7.5 kva Isolation Transformer - 460V Primary - 230V Secondary - NEMA 3R - Single Phase - 50/60 Hz 7.5 kva Isolation Transformer 460V Primary 230V Secondary NEMA 3R Single Phase 50/60 Hz Part #: MTISX1P460V7.5KVA230VN3R50.60HZ Page: 1 The MTISX1P460V7.5KVA230VN3R50.60HZ 460V 1 Phase Energy Efficient

More information

2.1. Product Description

2.1. Product Description .1 NEMA TP-1 Energy-Efficient Type DT-3 Contents Description NEMA TP-1 Energy-Efficient Features, Benefits and Functions........... Standards and Certifications............... Catalog Selection................

More information

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Part 1 - General Scope and Product Description 1.0 This specification contains the minimum design

More information

UCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL

UCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1. TECHNICAL SPECIFICATIONS for Single Phase, 1 to 3 KVA Power Conditioner with Regulation and Distribution Constant Power 3 (CP3) CP36508A 7/15/04 1.0 General This specification covers the electrical characteristics

More information

REQUEST FOR INFORMATION (RFI) RFI NO: /WJG

REQUEST FOR INFORMATION (RFI) RFI NO: /WJG (RFI) RFI NO: 15-219/WJG WASHINGTON METROPOLITAN AREA TRANSIT AUTHORITY 600 FIFTH STREET, NW WASHINGTON DC 20001 ( WMATA OR AUTHORITY ) 1 ⅝ INCH RADIATING COAXIAL CABLE DATE: AUGUST 7, 2015 Contents Introduction...

More information

Proposal PROJECT MANUAL P R O P E R T Y M A N A G E M E N T F A L L O N C O U N T Y. Baker, MT P.O. Box 846

Proposal PROJECT MANUAL P R O P E R T Y M A N A G E M E N T F A L L O N C O U N T Y. Baker, MT P.O. Box 846 PROJECT MANUAL P R O P E R T Y M A N A G E M E N T F A L L O N C O U N T Y Proposal P.O. Box 846 Baker, MT 59313 P R E C A S T R E I N F O R C E D C O N C R E T E B O X C U L V E R T F O R W E S T M O

More information

INTERNATIONAL TRANSFORMERS. Acme Electric s broad selection of CSA energy efficient transformers

INTERNATIONAL TRANSFORMERS. Acme Electric s broad selection of CSA energy efficient transformers INTERNATIONAL TRANSFORMERS Acme Electric s broad selection of CSA energy efficient transformers International Transformers What is CSA C802.2 Compliant? On January 1, 2005, the Canadian Energy Efficiency

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

Overview The Thomas & Betts Method is Better. Just Four Easy Steps to a Perfect Connection! Step 1. Step 2

Overview The Thomas & Betts Method is Better. Just Four Easy Steps to a Perfect Connection! Step 1. Step 2 Overview The Thomas & Betts Method is Better. The Thomas & Betts method of installing compression connectors on power cables is designed to provide a high degree of reliability in electrical wiring. This

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-27 05 28.36 40 (August 2011) ----------------------------------- Preparing Activity: NASA Superseding UFGS-27 05 28.36 40 (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

CAST RESIN DRY TRANSFORMER

CAST RESIN DRY TRANSFORMER CAST RESIN DRY TRANSFORMER Majority owned subsidiary company of ELETTROMECCANICA COLOMBO s.a.s., Italy Elettromeccanica India Elettromeccanica India Pvt Ltd (EIPL) is a joint-venture company with Elettromeccanica,

More information