A Current-Source Active Power Filter with a New DC Filter Structure

Size: px
Start display at page:

Download "A Current-Source Active Power Filter with a New DC Filter Structure"

Transcription

1 A Current-Source Active Power Filter with a New DC Filter Structure Mika Salo Department of Electrical Engineering, Institute of Power Electronics Tampere University of Technology P.O.Box 692, FIN-3311 Tampere, Finland Abstract- The main drawback of the current-source active power filter is the heavy and bulky dc side filter. The large dc filter is needed to store the energy of the compensated harmonic components. In this paper a new smaller dc filter structure is proposed for the current-source active power filter. In the presented dc filter structure the energy of the most important harmonics are stored in resonant circuit which makes it possible to decrease the overall size of the filter. The function of the proposed dc filter structure is examined with both simulations and experimental tests. Power supply u s i lda i ta Load L f isa L s Supply filter i ra T 1 Rectifier bridge T 3 T dc-filter i dc L dc I. INTRODUCTION In recent years, active power filters have been widely investigated for the compensation of harmonic currents in electrical power systems. These active power filters are divided into two types: voltage-source active filter (VSAF) and current-source active filter (CSAF). CSAF has advantages of excellent current control capability, easy protection and high reliability over VSAF [1]. The main drawbacks of the CSAF has been so far the lag of proper switching devices and large dc side filter. The new IGBTs with reverse blocking capability are being launched on the markets which are suitable for CSAF [2]. However, the bulky and heavy dc side filter is still a problem. Fig. 1 shows the most common main circuit structure of the current-source active power filter (e.g. [3]-[]). The line current characteristics are improved by injecting the current components opposite to the harmonics of the load current. The energy of the injected harmonic components is stored in and restored from the dc circuit which makes ripple in the dc current. In order to keep this ripple in an acceptable level relatively large dc filter inductor is needed. In this paper a new smaller dc filter structure is presented for the current-source active power filter. The proposed dc filter structure is shown in Fig. 1. In the presented dc filter the energy of the most important harmonics are stored in resonant circuit which makes it possible to decrease the overall size of the filter. II. PROPOSED DC FILTER STRUCTURE The most important harmonics in typical nonlinear loads are th and 7th harmonic components which produce 6th harmonic component in the dc circuit of the active power filter. Next important harmonic component in the dc circuit of the CSAF is the 12th harmonic which is caused by the compensation of 11th and Power i lda supply i ta u s 13th load current harmonics. Other components in the dc circuit have order of 18, 24, 3 etc. However, the 6th harmonic components makes the biggest ripple in the dc current because of it s large magnitude and low frequency. The proposed dc filter structure shown in Fig. 1 is designed to damp the 6th harmonic component effectively. The proposed dc filter structure uses a parallel resonant circuit which is tuned for 6th harmonic component. Other harmonics of the dc circuit are filtered with the inductor L dc connected in series with the resonant circuit. With the proposed modified dc filter structure the amount of the total filter inductance can be significantly reduced. Impedance of the conventional dc filter structure is R dc Load L f isa L s Supply filter Fig. 1. The current source active power filter with conventional dc filter structure and with modified dc filter structure. Zs ( ) = R dc sl dc where is the resistance of the dc filter. For modified dc filter structure can be written as L r s R Zs ( ) = r R dc sl dc L r C r s 2 R r C r s 1 C s C s i ra T 1 T 2 T 2 T 3 T 4 T 4 Rectifier bridge T T 6 T 6 i dc L r dc filter L dc i cr C r (1) (2)

2 where L r, C r and R r are the inductance, capacitance and resistance of the parallel resonant circuit respectively. Impedances of the conventional (--) and modified (-) dc filter structures are plotted in Fig. 2 as a function of the angular frequency. With conventional dc filter L dc =17 mh and R dc =8Ω. The modified dc filter have parameter values: L dc =3 mh, R dc =3Ω, L r =1 mh, R r = 2Ω and C r =18.7 µf. The resistances are approximate values at 3 Hz. Fig. 2 shows also the impedance curve with 4 mh dc filter inductor (.-) which is the total inductance of the modified dc filter structure. These parameter values are used with the active power filter of which nominal power is kw. Fig. 2 shows that impedance of the modified dc filter is increased rapidly at 19 rad/s (3 Hz). This is caused by the parallel resonant circuit which is tuned for this frequency (6 th harmonic component). At this frequency the impedance of the modified dc filter is higher than the impedance of the conventional filter which indicates that the proposed filter structure can store effectively the energy of the filtered th and 7th load current harmonics without large ripple in dc current. Fig. 2 shows also that the impedance of the modified filter is very low at 27 rad/s (42 Hz). This is caused by the series resonance of the proposed dc filter structure. The frequency of the series resonance is determined by C r and the parallel connection of L dc and L r. When selecting the parameters for the modified dc filter structure it should be made sure that the frequency of the series resonance is not near to 12th harmonic component which is the next important harmonic component in the dc circuit of the active filter. Otherwise, the series resonance should neither be near 6th harmonic component. This can be avoided when the ratio of L r and is between 1/2-2. L dc III. CONTROL OF CSAF The proposed dc filter topology can be used with any control system of CSAF. Fig. 3 shows a control system [6] which is practical for current-source topology. It is realized in the synchronously rotating reference frame where the active power of the active filter can be simply controlled with i sx i sy real axis component and the reactive power with imaginary axis component of the filter current. The superscript s in space vector variables and x/y in space vector components refers to a synchronously rotating coordinate system. The harmonic compensation is based on the feedforward control of i sxy the load currents. The active filter currents are controlled in an open-loop manner. The reference values for active filter current vector are calculated as follows: i sx = i ffx i dcx (3) Impedance[dB] and Angular frequency [rad/s] Fig. 2. Impedances of the convential dc filter when L dc =17 mh (--) and L dc =4 mh (.-) and impedance of the modified dc filter (-) as function of the angular frequency. i sy = i ffy i qy (4) where i ffxy (both components combined in one expression), i and i dcx qy are outputs of the feedforward, dc current and the reactive power controls respectively. These two components form the rectifier current reference vector i s r which is transformed to the stationary reference frame and fed to the modulator. Due to the open-loop control of the active filter currents the currents references are not realized accurately because the supply filter takes capacitive currents. Also, oscillations may occur in supply currents due to the LC-filter resonance if the active filter current references are rapidly changed. Detailed describtion of the control methods to solve both of these problems can be found in [6]. A. Dc current control The task of the active filter is to compensate the harmonics of the non-linear load. The magnitude of the dc current is changed as the energy of the harmonic components is stored in and restored from the dc circuit. This ripple in the dc current is the basic feature in the active power filter and for that reason the dc current control should not try to remove it. However, the dc current control should work effectively when the reference value of the dc current is changed. For that reason, a non-linear PID controller, where the input of the controller is the square of the error signal, is proposed for the control system shown in Fig. 3. With small error values the controller acts slowly and when the error value is increased faster control dynamics is achieved. Fig. 4 shows the block diagram of the non-linear PI controller where the modified proportional gain P dc k 1 depends on the error value. In practice, it is reasonable to limit P dc k 1 between and max P dc, which is done with Saturation block. To understand how i dcx is constructed in the dc-current control we can first consider that 3 --u 2 sx i dcx = u dcbr i dc ()

3 Load L f i lda Power CSAF supply i i i dc ta sa i ra L dc u dcbr Lr Cr 3->2 i ld e jθ s i ld s i ldx i ldy HPF HPF ^ i ^ ldx i ldy -1-1 CDC θ CDC s u s Reactive power control i qy L s i ffy C s θ s i sy Modulator e jθ s i r i sx i ffx FG i r s = is s i dc i dc PID(e 2 ) u dcbr c 1 i dcx Feedforward control Fig. 3. Control system of CSAF with modified dc filter topology. Dc current control i.e. that the ac and dc active powers of the converter are equal in steady state if the converter losses are ignored. u dcbr is the dc-voltage of the rectifier bridge. By solving () for i dcx and by using the reference values of i dcx and u dcbr we have = u dcbr i dc = 2 i dcx 3u sx cu dcbr i dc which is used in Fig. 3 to transform the dc-voltage reference of the rectifier bridge to vector variable. IV. SIMULATION RESULTS The proposed control methods are tested with the simulation model. The simulation model is built in discrete form to have close analogy with the microcontroller implementation. Simulation is based on the control system shown in Fig. 3. Sampling time of the feedforward and dc current controllers is µs and the modulation frequency 1 khz. The supply filter is realized with parameters: L s =.6 mh and C s =8 µf. Figs. and 6 show the simulation results of CSAF with modified and conventional dc filter structure respectively. As a nonlinear load a three-phase diode rectifier with RL-load is used. The parameters of the modified dc filter are L dc =1 mh, L r =1 mh and C r =28.1 µf and conventional L dc =1 mh. (6), k1 k1 i dc i dc abs P dc P k1 dc Saturation T s T dc Delay Delay Saturation T s In both simulations the the ripple of the dc current is about 1 A. The total harmonic distortion (THD) of the load current in both simulations is 26.8%. THDs of the supply current with modified dc filter is 4.2% and with conventional filter 4.%. Fig. 6 shows the current i cr of the resonant circuit capacitor. It s amplitude is about 3A and frequency 3 Hz. This ac current is caused by the 3 Hz ac voltage component across the resonant circuit. This 3 Hz ac voltage component is caused by the compensation of the th and 7th load current harmonics as was explained earlier. Figs. 7 and 8 show the simulation results of CSAF with D dc Fig. 4. Non-linear PID controller for dc current control. Saturation k u, 1 dcbr

4 Fig.. Simulation results of CSAF with modified dc filter structure when the current harmonics are produced using a three-phase diode rectifier with RL-load. Load current, supply current, dc current and current of the resonant circuit. i lda i ta i dc i cr Fig. 6. Simulation results of CSAF with conventional dc filter structure when the current harmonics are produced using a three-phase diode rectifier with RL-load. Load current, supply current and dc current. i lda i ta i dc modified and conventional dc filter structure respectively when as a non-linear load a three-phase diode rectifier with RC-load is used. In this case the parameters of the modified dc filter are L dc =3 mh, L r =1 mh and C r =18.7 µf and conventional L dc =17 mh. The size of L dc is increased in both modified and conventional dc filter solutions because RC-type diode load contains more harmonics than RL-type load. Also, the size of L r is increased in order to keep the series resonance of the modified filter far enough from the parallel resonance. Furthermore, smaller C r decreases the current of the resonant circuit capacitor. Anyway, Figs. and 7 shows that i cr is much larger with RC-type load than RL-type load due to the larger amount of harmonics included in RC-load which increases also the harmonics of the dc circuit. THD of is i lda

5 Fig. 7. Simulation results of CSAF with modified dc filter structure when the current harmonics are produced using a three-phase diode rectifier with RC-load. Load current, supply current, dc current and current of the resonant circuit. i lda i ta i dc i cr Fig. 8. Simulation results of CSAF with conventionald dc filter structure when the current harmonics are produced using a three-phase diode rectifier with RC-load. Load current i lda, supply current i ta and dc current i dc. 87.9% and THDs of i ta with modified and conventional dc filter 7.3% and 7.6% respectively. V. EXPERIMENTAL INVESTIGATION The prototype of CSAF is built using 12 V, A IGBTs. The control system realization is based on the Motorola MPC 32-bit single-chip microcontroller. The supply filter parameters and the sampling times of the control system are the same as used in simulation model. Figs. 9 and 1 show the experimental results of CSAF with modified and conventional dc filter structure respectively. As a non-linear load a three-phase diode rectifier with RL-load is used. The dc filter parameters are same as used in simulations.

6 Fig. 9. Experimental results of CSAF with modified dc filter structure when the current harmonics are produced using a three-phase diode rectifier with RL-load. Load current i lda, supply current i ta, dc current i dc and current of the resonant circuit i cr Fig. 1. Experimental results of CSAF with conventional dc filter structure when the current harmonics are produced using a three-phase diode rectifier with RL-load. Load current i lda, supply current i ta and dc current i dc. By comparing Figs., 6, 9 and 1 it can be seen that the simulation and experimental results are in good agreement. THD of i lda in Figs. 9 and 1 is 27.1% and THDs of i ta with modified and conventional dc filter 3.3% and 3.2% respectively. Figs. 11 and 12 show the experimental results of CSAF with modified dc filter in two cases when RC-type diode rec- tifier load is used. In the first case shown in Fig. 11 the load current contains only 1.3% of 3rd harmonic current. In the case of Fig. 12 the amount of 3rd harmonic is 7.1%. The 3rd harmonic component in load currents causes 2nd harmonic voltage component in the dc circuit. However, the impedance of the modified dc filter for 2nd harmonic component is very low as can be seen in Fig. 2. As a result, the ripple in dc cur-

7 Fig. 11. Experimental results of CSAF with modified dc filter structure when the current harmonics are produced using a three-phase diode rectifier with RC-load. Load current contains only small amount of 3rd harmonic component. Load current i lda, supply current i ta, dc current i dc and current of the resonant circuit i cr Fig. 12. Experimental results of CSAF with modified dc filter structure when the current harmonics are produced using a three-phase diode rectifier with RC-load. Load current contains large amount of 3rd harmonic component. Load current i lda, supply current i ta, dc current i dc and current of the resonant circuit i cr. -1 rent is much larger in Fig. 11 than in 12 due to the significant 1 Hz component (2nd harmonic). In principle, symmetric three-phase load should not contain 3rd harmonic component which was also confirmed with simulations. The 3rd harmonic components seen in measured load current is caused propably by the distorted supply voltages. The experimental results of the conventional dc filter are shown in Fig. 13. In Figs the THD of i lda is around 82%. The THDs of i ta shown in Figs. 11, 12 and 13 are.7%, 7.% and 6.%. According to simulations and experimental investigation it can be concluded that the proposed dc filter structure works well if the load currents are symmetrical and do not contain

8 Fig. 13. Experimental results of CSAF with conventional dc filter structure when the current harmonics are produced using a three-phase diode rectifier with RC-load. Load current i lda, supply current i ta and dc current i dc. 3rd harmonic component. It seems that in practice threephase diode rectifier with RC-type load generates 3rd harmonic in load currents and is not practical for proposed filter structure. However, the modified filter can be used if the 3rd harmonic component is not compensated. In the case of RLtype diode rectifier load the amount of 3rd harmonic is minimal and the proposed filter structure can be used. In this case the amount of total inductance needed in the modified dc filter is decreased to 1/4 compared to the conventional dc filter. VI. CONCLUSIONS In this paper a new smaller dc filter structure is proposed for the current-source active power filter. In the presented dc filter structure the energy of the most important harmonics are stored in resonant circuit which makes it possible to decrease the overall size of the filter. After simulations and experimental tests it was found that the proposed filter structure works well with symmetrical loads if the load current doesn t contain 3rd harmonic component. REFERENCES [1] Y. Hayashi, N. Sato and K. Takahashi, A novel control of a currentsource active filter for ac power system harmonic compensation, IEEE Trans. Ind. App., Vol. 27, No. 2, pp , March/April [2] A. Lindemann, Characteristics and applications of a reverse blocking IGBT, PCIM Europe, pp.12-16, January-February 21. [3] S. Fukuda and T. Endoh, Control method and characteristics of active power filters, th European Conference on Power Electronics and Applications, Vol 8, pp , [4] S. Fukuda and T. Endoh, Control method for a combined active filter system employing a current source converter and a high pass filter, IEEE Trans. Ind. App., Vol. 31, No. 3, pp. 9-97, 199. [] M.-X W ang and H. Pouliquen, Performance of an active filter using PWM current source inverter, th European Conference on Power Electronics and Applications, Vol. 8, pp , [6] M. Salo and H. Tuusa, H., A novel open-loop control method for a current-source active power filter, IEEE Trans. Ind. Electr., Vol., No. 2, pp , 23.

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 3, Issue 8 (September 2012), PP. 16-20 Implementation of SRF based Multilevel Shunt

More information

SHUNT ACTIVE POWER FILTER

SHUNT ACTIVE POWER FILTER 75 CHAPTER 4 SHUNT ACTIVE POWER FILTER Abstract A synchronous logic based Phase angle control method pulse width modulation (PWM) algorithm is proposed for three phase Shunt Active Power Filter (SAPF)

More information

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter B.S.Nalina 1 Ms.V.J.Vijayalakshmi 2 Department Of EEE Department Of EEE 1 PG student,skcet, Coimbatore, India

More information

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of

More information

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 3, Number 6 (2013), pp. 651-660 Research India Publications http://www.ripublication.com/aeee.htm Design and Simulation of Three Phase

More information

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy Design of Shunt Active Power Filter by using An Advanced Current Control Strategy K.Sailaja 1, M.Jyosthna Bai 2 1 PG Scholar, Department of EEE, JNTU Anantapur, Andhra Pradesh, India 2 PG Scholar, Department

More information

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Control Of Shunt Active Filter Based On Instantaneous Power Theory B.Pragathi Department of Electrical and Electronics Shri Vishnu Engineering College for Women Bhimavaram, India Control Of Shunt Active Filter Based On Instantaneous Power Theory G.Bharathi Department

More information

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL 14 CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL 2.1 INTRODUCTION Power electronics devices have many advantages over the traditional power devices in many aspects such as converting

More information

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER P. SWEETY JOSE JOVITHA JEROME Dept. of Electrical and Electronics Engineering PSG College of Technology, Coimbatore, India.

More information

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System Anju Gupta Department of Electrical and Electronics Engg. YMCA University of Science and Technology anjugupta112@gmail.com P.

More information

Current Rebuilding Concept Applied to Boost CCM for PF Correction

Current Rebuilding Concept Applied to Boost CCM for PF Correction Current Rebuilding Concept Applied to Boost CCM for PF Correction Sindhu.K.S 1, B. Devi Vighneshwari 2 1, 2 Department of Electrical & Electronics Engineering, The Oxford College of Engineering, Bangalore-560068,

More information

Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier

Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier Transactions on Electrical Engineering, Vol. 1 (2012), No. 1 30 Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier Jan Michalík1), Jan Molnár2) and Zdeněk Peroutka2)

More information

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013 Power Quality Enhancement Using Hybrid Active Filter D.Jasmine Susila, R.Rajathy Department of Electrical and electronics Engineering, Pondicherry Engineering College, Pondicherry Abstract This paper presents

More information

Power Quality enhancement of a distribution line with DSTATCOM

Power Quality enhancement of a distribution line with DSTATCOM ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical

More information

Series and Parallel Resonant Circuits

Series and Parallel Resonant Circuits Series and Parallel Resonant Circuits Aim: To obtain the characteristics of series and parallel resonant circuits. Apparatus required: Decade resistance box, Decade inductance box, Decade capacitance box

More information

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive B. Mohan Reddy 1, G.Balasundaram 2 PG Student [PE&ED], Dept. of EEE, SVCET, Chittoor

More information

IMPROVED TRANSFORMERLESS INVERTER WITH COMMON-MODE LEAKAGE CURRENT ELIMINATION FOR A PHOTOVOLTAIC GRID-CONNECTED POWER SYSTEM

IMPROVED TRANSFORMERLESS INVERTER WITH COMMON-MODE LEAKAGE CURRENT ELIMINATION FOR A PHOTOVOLTAIC GRID-CONNECTED POWER SYSTEM IMPROVED TRANSFORMERLESS INVERTER WITH COMMON-MODE LEAKAGE CURRENT ELIMINATION FOR A PHOTOVOLTAIC GRID-CONNECTED POWER SYSTEM M. JYOTHSNA M.Tech EPS KSRM COLLEGE OF ENGINEERING, Affiliated to JNTUA, Kadapa,

More information

CHAPTER 4 PI CONTROLLER BASED LCL RESONANT CONVERTER

CHAPTER 4 PI CONTROLLER BASED LCL RESONANT CONVERTER 61 CHAPTER 4 PI CONTROLLER BASED LCL RESONANT CONVERTER This Chapter deals with the procedure of embedding PI controller in the ARM processor LPC2148. The error signal which is generated from the reference

More information

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation A.Jeraldine viji Associate Professor, EEE department, Mailam Engineering College, Tamil Nadu E-mail: jeraldrovan@gmail.com Dr.M.Sudhakaran

More information

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER International Journal of Electrical and Electronics Engineering Research (IJEEER) ISSN 2250-155X Vol. 3, Issue 2, Jun 2013, 309-318 TJPRC Pvt. Ltd. PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID

More information

Harmonic Filtering in Variable Speed Drives

Harmonic Filtering in Variable Speed Drives Harmonic Filtering in Variable Speed Drives Luca Dalessandro, Xiaoya Tan, Andrzej Pietkiewicz, Martin Wüthrich, Norbert Häberle Schaffner EMV AG, Nordstrasse 11, 4542 Luterbach, Switzerland luca.dalessandro@schaffner.com

More information

RECENTLY, the harmonics current in a power grid can

RECENTLY, the harmonics current in a power grid can IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 2, MARCH 2008 715 A Novel Three-Phase PFC Rectifier Using a Harmonic Current Injection Method Jun-Ichi Itoh, Member, IEEE, and Itsuki Ashida Abstract

More information

Study of Inductive and Capacitive Reactance and RLC Resonance

Study of Inductive and Capacitive Reactance and RLC Resonance Objective Study of Inductive and Capacitive Reactance and RLC Resonance To understand how the reactance of inductors and capacitors change with frequency, and how the two can cancel each other to leave

More information

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF) DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF) Rosli Omar, Mohammed Rasheed, Zheng Kai Low and Marizan Sulaiman Universiti Teknikal Malaysia

More information

Power Factor Corrected Single Stage AC-DC Full Bridge Resonant Converter

Power Factor Corrected Single Stage AC-DC Full Bridge Resonant Converter Power Factor Corrected Single Stage AC-DC Full Bridge Resonant Converter Gokul P H Mar Baselios College of Engineering Mar Ivanios Vidya Nagar, Nalanchira C Sojy Rajan Assisstant Professor Mar Baselios

More information

Lecture 19 - Single-phase square-wave inverter

Lecture 19 - Single-phase square-wave inverter Lecture 19 - Single-phase square-wave inverter 1. Introduction Inverter circuits supply AC voltage or current to a load from a DC supply. A DC source, often obtained from an AC-DC rectifier, is converted

More information

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Mr. A. S. Patil Mr. S. K. Patil Department of Electrical Engg. Department of Electrical Engg. I. C. R. E. Gargoti I. C. R. E. Gargoti

More information

A Control Circuit Small Wind Turbines with Low Harmonic Distortion and Improved Power Factor

A Control Circuit Small Wind Turbines with Low Harmonic Distortion and Improved Power Factor European Association for the Development of Renewable Energies, Environment and Power Quality International Conference on Renewable Energies and Power Quality (ICREPQ 09) Valencia (Spain), 15th to 17th

More information

CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER

CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER 97 CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER 6.1 INTRODUCTION Multi level inverters are proven to be an ideal technique for improving the voltage and current profile to closely match with the sinusoidal

More information

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc.

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc. Chapter 30 Inductance, Electromagnetic Oscillations, and AC Circuits 30-7 AC Circuits with AC Source Resistors, capacitors, and inductors have different phase relationships between current and voltage

More information

Oscillators. An oscillator may be described as a source of alternating voltage. It is different than amplifier.

Oscillators. An oscillator may be described as a source of alternating voltage. It is different than amplifier. Oscillators An oscillator may be described as a source of alternating voltage. It is different than amplifier. An amplifier delivers an output signal whose waveform corresponds to the input signal but

More information

Improving Passive Filter Compensation Performance With Active Techniques

Improving Passive Filter Compensation Performance With Active Techniques IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 1, FEBRUARY 2003 161 Improving Passive Filter Compensation Performance With Active Techniques Darwin Rivas, Luis Morán, Senior Member, IEEE, Juan

More information

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

ICCCES Application of D-STATCOM for load compensation with non-stiff sources Application of D-STATCOM for load compensation with non-stiff sources 1 Shubhangi Dhole, 2 S.S.Gurav, 3 Vinayak Patil, 4 Pushkraj Kharatmal, 5 Magdum Ranjit 1 Dept of Electrical Engg. AMGOI, VATHAR TERF

More information

Improved direct torque control of induction motor with dither injection

Improved direct torque control of induction motor with dither injection Sādhanā Vol. 33, Part 5, October 2008, pp. 551 564. Printed in India Improved direct torque control of induction motor with dither injection R K BEHERA andspdas Department of Electrical Engineering, Indian

More information

Lab 1: Basic RL and RC DC Circuits

Lab 1: Basic RL and RC DC Circuits Name- Surname: ID: Department: Lab 1: Basic RL and RC DC Circuits Objective In this exercise, the DC steady state response of simple RL and RC circuits is examined. The transient behavior of RC circuits

More information

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source International Journal of Emerging Engineering Research and Technology Volume 2, Issue 3, June 2014, PP 220-229 ISSN 2349-4395 (Print) & ISSN 2349-4409 (Online) Load Compensation at a Reduced DC Link Voltage

More information

Investigation of D-Statcom Operation in Electric Distribution System

Investigation of D-Statcom Operation in Electric Distribution System J. Basic. Appl. Sci. Res., (2)29-297, 2 2, TextRoad Publication ISSN 29-434 Journal of Basic and Applied Scientific Research www.textroad.com Investigation of D-Statcom Operation in Electric Distribution

More information

Research and design of PFC control based on DSP

Research and design of PFC control based on DSP Acta Technica 61, No. 4B/2016, 153 164 c 2017 Institute of Thermomechanics CAS, v.v.i. Research and design of PFC control based on DSP Ma Yuli 1, Ma Yushan 1 Abstract. A realization scheme of single-phase

More information

Small-Signal Model and Dynamic Analysis of Three-Phase AC/DC Full-Bridge Current Injection Series Resonant Converter (FBCISRC)

Small-Signal Model and Dynamic Analysis of Three-Phase AC/DC Full-Bridge Current Injection Series Resonant Converter (FBCISRC) Small-Signal Model and Dynamic Analysis of Three-Phase AC/DC Full-Bridge Current Injection Series Resonant Converter (FBCISRC) M. F. Omar M. N. Seroji Faculty of Electrical Engineering Universiti Teknologi

More information

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Application of Fuzzy Logic Controller in Shunt Active Power Filter IJIRST International Journal for Innovative Research in Science & Technology Volume 2 Issue 11 April 2016 ISSN (online): 2349-6010 Application of Fuzzy Logic Controller in Shunt Active Power Filter Ketan

More information

A New 3-phase Buck-Boost Unity Power Factor Rectifier with Two Independently Controlled DC Outputs

A New 3-phase Buck-Boost Unity Power Factor Rectifier with Two Independently Controlled DC Outputs A New 3-phase Buck-Boost Unity Power Factor Rectifier with Two Independently Controlled DC Outputs Y. Nishida* 1, J. Miniboeck* 2, S. D. Round* 2 and J. W. Kolar* 2 * 1 Nihon University Energy Electronics

More information

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller J.Venkatesh 1, K.S.S.Prasad Raju 2 1 Student SRKREC, India, venki_9441469778@yahoo.com

More information

Power Quality Improvement using Shunt Passive Filter

Power Quality Improvement using Shunt Passive Filter Power Quality Improvement using Shunt Passive Filter Assistant Professor, Department of Electrical Engineering Bhutta Group of Institutions, India Abstract: The electricity supply would, ideally, show

More information

Power Quality improvement of a three phase four wire system using UPQC

Power Quality improvement of a three phase four wire system using UPQC International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Volume: 2 Issue: 4 July-215 www.irjet.net p-issn: 2395-72 Power Quality improvement of a three phase four wire system

More information

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online): 2321-0613 Modeling and Simulation of SRF Control Based Shunt Active Power Filter and Application

More information

Design of a Hybrid Active Filter for Harmonics Suppression in Industrial Facilities

Design of a Hybrid Active Filter for Harmonics Suppression in Industrial Facilities Design of a Hybrid Active Filter for Harmonics Suppression in Industrial Facilities Tzung-Lin Lee Yen-Ching Wang Jian-Cheng Li Department of Electrical Engineering National Sun Yat-sen University 7, Lienhai

More information

AN IMPROVED ZERO-VOLTAGE-TRANSITION INTERLEAVED BOOST CONVERTER WITH HIGH POWER FACTOR

AN IMPROVED ZERO-VOLTAGE-TRANSITION INTERLEAVED BOOST CONVERTER WITH HIGH POWER FACTOR AN IMPROVED ZERO-VOLTAGE-TRANSITION INTERLEAVED BOOST CONVERTER WITH HIGH POWER FACTOR Naci GENC 1, Ires ISKENDER 1 1 Gazi University, Faculty of Engineering and Architecture, Department of Electrical

More information

ISSN Vol.03,Issue.07, August-2015, Pages:

ISSN Vol.03,Issue.07, August-2015, Pages: WWW.IJITECH.ORG ISSN 2321-8665 Vol.03,Issue.07, August-2015, Pages:1276-1281 Comparison of an Active and Hybrid Power Filter Devices THAKKALAPELLI JEEVITHA 1, A. SURESH KUMAR 2 1 PG Scholar, Dept of EEE,

More information

ATYPICAL high-power gate-turn-off (GTO) currentsource

ATYPICAL high-power gate-turn-off (GTO) currentsource 1278 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 6, NOVEMBER/DECEMBER 1998 A Novel Power Factor Control Scheme for High-Power GTO Current-Source Converter Yuan Xiao, Bin Wu, Member, IEEE,

More information

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads Ponananthi.V, Rajesh Kumar. B Final year PG student, Department of Power Systems Engineering, M.Kumarasamy College of

More information

A THREE-PHASE HIGH POWER FACTOR TWO-SWITCH BUCK- TYPE CONVERTER

A THREE-PHASE HIGH POWER FACTOR TWO-SWITCH BUCK- TYPE CONVERTER A THREE-PHASE HIGH POWER FACTOR TWO-SWITCH BUCK- TYPE CONVERTER SEEMA.V. 1 & PRADEEP RAO. J 2 1,2 Electrical and Electronics, The Oxford College of Engineering, Bangalore-68, India Email:Seema.aish1@gmail.com

More information

ACTIVE POWER ELECTRONIC TRANSFORMER A STANDARD BUILDING BLOCK FOR SMART GRID

ACTIVE POWER ELECTRONIC TRANSFORMER A STANDARD BUILDING BLOCK FOR SMART GRID INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) Proceedings of the International Conference on Emerging Trends in Engineering and Management (ICETEM14) ISSN 0976 6545(Print) ISSN 0976

More information

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

Assessment of Different Compensation Strategies in Hybrid Active Power Filters Assessment of Different Compensation Strategies in Hybrid Active Power Filters Rashed Bahrekazemi Electrical Engineering Department Iran University of Science & Technology (IUST) Tehran, Iran rbahrkazemi@ee.iust.ac.ir

More information

Input Voltage Modulated High Voltage DC Power Supply Topology for Pulsed Load Applications

Input Voltage Modulated High Voltage DC Power Supply Topology for Pulsed Load Applications Input oltage Modulated High oltage DC Power Supply Topology for Pulsed Load Applications N.ishwanathan, Dr..Ramanarayanan Power Electronics Group, Dept. of Electrical Engineering, IISc., Bangalore -- 560

More information

AC Circuits. "Look for knowledge not in books but in things themselves." W. Gilbert ( )

AC Circuits. Look for knowledge not in books but in things themselves. W. Gilbert ( ) AC Circuits "Look for knowledge not in books but in things themselves." W. Gilbert (1540-1603) OBJECTIVES To study some circuit elements and a simple AC circuit. THEORY All useful circuits use varying

More information

TO LIMIT degradation in power quality caused by nonlinear

TO LIMIT degradation in power quality caused by nonlinear 1152 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 13, NO. 6, NOVEMBER 1998 Optimal Current Programming in Three-Phase High-Power-Factor Rectifier Based on Two Boost Converters Predrag Pejović, Member,

More information

Figure 1: Closed Loop System

Figure 1: Closed Loop System SIGNAL GENERATORS 3. Introduction Signal sources have a variety of applications including checking stage gain, frequency response, and alignment in receivers and in a wide range of other electronics equipment.

More information

Comparative Study of Pulse Width Modulated and Phase Controlled Rectifiers

Comparative Study of Pulse Width Modulated and Phase Controlled Rectifiers Comparative Study of Pulse Width Modulated and Phase Controlled Rectifiers Dhruv Shah Naman Jadhav Keyur Mehta Setu Pankhaniya Abstract Fixed DC voltage is one of the very basic requirements of the electronics

More information

THE third-harmonic current injection is a method to reduce

THE third-harmonic current injection is a method to reduce 96 IEEE POWER ELECTRONICS LETTERS, VOL. 3, NO. 3, SEPTEMBER 2005 Low-Harmonic, Three-Phase Rectifier That Applies Current Injection and a Passive Resistance Emulator Predrag Pejović, Predrag Božović, and

More information

An induced emf is the negative of a changing magnetic field. Similarly, a self-induced emf would be found by

An induced emf is the negative of a changing magnetic field. Similarly, a self-induced emf would be found by This is a study guide for Exam 4. You are expected to understand and be able to answer mathematical questions on the following topics. Chapter 32 Self-Induction and Induction While a battery creates an

More information

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Dr. Jagdish Kumar, PEC University of Technology, Chandigarh Abstract the proper selection of values of energy storing

More information

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online): 2321-0613 Study of Bidirectional AC/DC Converter with Feedforward Scheme using Neural Network Control

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Space Vector PWM and Model Predictive Control for Voltage Source Inverter Control

Space Vector PWM and Model Predictive Control for Voltage Source Inverter Control Space Vector PWM and Model Predictive Control for Voltage Source Inverter Control Irtaza M. Syed, Kaamran Raahemifar Abstract In this paper, we present a comparative assessment of Space Vector Pulse Width

More information

A Contribution to Isolated and Grid-Connected Photovoltaic Systems under Shadow Conditions

A Contribution to Isolated and Grid-Connected Photovoltaic Systems under Shadow Conditions 2 21 22 23 24 25 26 27 28 29 21 211 212 213 214 215 Power (GW) European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable

More information

Sepic Topology Based High Step-Up Step down Soft Switching Bidirectional DC-DC Converter for Energy Storage Applications

Sepic Topology Based High Step-Up Step down Soft Switching Bidirectional DC-DC Converter for Energy Storage Applications IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 12, Issue 3 Ver. IV (May June 2017), PP 68-76 www.iosrjournals.org Sepic Topology Based High

More information

A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems

A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems K Siva Shankar, J SambasivaRao Abstract- Power converters for mobile devices and consumer electronics have become extremely lightweight

More information

LOW PEAK CURRENT CLASS E RESONANT FULL-WAVE LOW dv/dt RECTIFIER DRIVEN BY A VOLTAGE GENERATOR

LOW PEAK CURRENT CLASS E RESONANT FULL-WAVE LOW dv/dt RECTIFIER DRIVEN BY A VOLTAGE GENERATOR Électronique et transmission de l information LOW PEAK CURRENT CLASS E RESONANT FULL-WAVE LOW dv/dt RECTIFIER DRIVEN BY A VOLTAGE GENERATOR ŞERBAN BÎRCĂ-GĂLĂŢEANU 1 Key words : Power Electronics, Rectifiers,

More information

Power Factor Improvement with Single Phase Diode Rectifier in Interior Permanent Magnet Motor

Power Factor Improvement with Single Phase Diode Rectifier in Interior Permanent Magnet Motor Power Factor Improvement with Single Phase Diode Rectifier in Interior Permanent Magnet Motor G.Sukant 1, N.Jayalakshmi 2 PG Student Shri Andal Alagar college of Engineering, Tamilnadu, India 1 PG Student,

More information

Multiple PR Current Regulator based Dead-time Effects Compensation for Grid-forming Single-Phase Inverter

Multiple PR Current Regulator based Dead-time Effects Compensation for Grid-forming Single-Phase Inverter Multiple PR Current Regulator based Dead-time Effects Compensation for Grid-forming Single-Phase Inverter 1 st Siyuan Chen FREEDM Systems Center North Carolina State University Raleigh, NC, USA schen36@ncsu.edu

More information

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES Int. J. Engg. Res. & Sci. & Tech. 2015 xxxxxxxxxxxxxxxxxxxxxxxx, 2015 Research Paper MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES N Lakshmipriya 1* and L

More information

Modeling and Control of Voltage Source Converters Connected to the Grid

Modeling and Control of Voltage Source Converters Connected to the Grid Modeling and Control of Voltage Source Converters Connected to the Grid Michael Lindgren Technical Report No. 351 1998 Modeling and Control of Voltage Source Converters Connected to the Grid by Michael

More information

Vector Control of Three-Phase Active Front End Rectifier

Vector Control of Three-Phase Active Front End Rectifier IJIRST International Journal for Innovative Research in Science & Technology Volume 2 Issue 09 February 2016 ISSN (online): 2349-6010 Vector Control of Three-Phase Active Front End Rectifier Heema Shukla

More information

METHODS TO IMPROVE DYNAMIC RESPONSE OF POWER FACTOR PREREGULATORS: AN OVERVIEW

METHODS TO IMPROVE DYNAMIC RESPONSE OF POWER FACTOR PREREGULATORS: AN OVERVIEW METHODS TO IMPROE DYNAMIC RESPONSE OF POWER FACTOR PREREGULATORS: AN OERIEW G. Spiazzi*, P. Mattavelli**, L. Rossetto** *Dept. of Electronics and Informatics, **Dept. of Electrical Engineering University

More information

Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter)

Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter) Exercise 2 Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter) EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the singlephase grid-tied inverter. DISCUSSION OUTLINE

More information

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage 1 New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage B. B. Pimple, V. Y. Vekhande and B. G. Fernandes Department of Electrical Engineering, Indian Institute of Technology Bombay,

More information

A Resistance Emulation Technique to Improve Efficiency of a PWM Adjustable Speed Drive with Passive Power Factor Correction

A Resistance Emulation Technique to Improve Efficiency of a PWM Adjustable Speed Drive with Passive Power Factor Correction A Resistance Emulation Technique to Improve Efficiency of a PWM Adjustable Speed Drive with Passive Power Factor Correction R. CARBONE A. SCAPPATURA Department I.M.E.T. Università degli Studi Mediterranea

More information

Distributed Active Filter Systems (DAFS): A new approach to power system harmonics

Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Po-Tai Cheng Zhung-Lin Lee CENTER FOR ADVANCED POWER TECHNOLOGIES (CAPT) Department of Electrical Engineering National

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

LRC Circuit PHYS 296 Your name Lab section

LRC Circuit PHYS 296 Your name Lab section LRC Circuit PHYS 296 Your name Lab section PRE-LAB QUIZZES 1. What will we investigate in this lab? 2. Figure 1 on the following page shows an LRC circuit with the resistor of 1 Ω, the capacitor of 33

More information

A SPWM CONTROLLED THREE-PHASE UPS FOR NONLINEAR LOADS

A SPWM CONTROLLED THREE-PHASE UPS FOR NONLINEAR LOADS http:// A SPWM CONTROLLED THREE-PHASE UPS FOR NONLINEAR LOADS Abdul Wahab 1, Md. Feroz Ali 2, Dr. Abdul Ahad 3 1 Student, 2 Associate Professor, 3 Professor, Dept.of EEE, Nimra College of Engineering &

More information

Development of a Single-Phase PWM AC Controller

Development of a Single-Phase PWM AC Controller Pertanika J. Sci. & Technol. 16 (2): 119-127 (2008) ISSN: 0128-7680 Universiti Putra Malaysia Press Development of a Single-Phase PWM AC Controller S.M. Bashi*, N.F. Mailah and W.B. Cheng Department of

More information

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab University of Jordan School of Engineering Electrical Engineering Department EE 219 Electrical Circuits Lab EXPERIMENT 7 RESONANCE Prepared by: Dr. Mohammed Hawa EXPERIMENT 7 RESONANCE OBJECTIVE This experiment

More information

Design of UPS Inverter Control System Based on DSP

Design of UPS Inverter Control System Based on DSP International onference on Applied Science and Engineering Innovation (ASEI 05) Design of US Inverter ontrol System Based on DS Qian Yang, a, Mingming Guo, b and Jianhua Dou, c School of omputer and Information,

More information

Generation of Voltage Reference Signal in Closed-Loop Control of STATCOM

Generation of Voltage Reference Signal in Closed-Loop Control of STATCOM Generation of Voltage Reference Signal in Closed-Loop Control of STATCOM M. Tavakoli Bina 1,*, N. Khodabakhshi 1 1 Faculty of Electrical Engineering, K. N. Toosi University of Technology, * Corresponding

More information

645 P a g e. the quantity of compensate current needed accordingly. Fig. 1. Active powers filter with load current detection.

645 P a g e. the quantity of compensate current needed accordingly. Fig. 1. Active powers filter with load current detection. Shunt Active Power Filter Implementation Using Source Voltage and Source Current Detection Mani Ratnam Tarapatla 1, M Sridhar 2, ANVJ Raj Gopal 3 PG Scholar Department of Electrical Engineering GIET College

More information

Literature Review for Shunt Active Power Filters

Literature Review for Shunt Active Power Filters Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller

More information

A Novel Four Switch Three Phase Inverter Controlled by Different Modulation Techniques A Comparison

A Novel Four Switch Three Phase Inverter Controlled by Different Modulation Techniques A Comparison Volume 2, Issue 1, January-March, 2014, pp. 14-23, IASTER 2014 www.iaster.com, Online: 2347-5439, Print: 2348-0025 ABSTRACT A Novel Four Switch Three Phase Inverter Controlled by Different Modulation Techniques

More information

l1-i VEL SINGLE-PHASE ZCS-PWM HIGH POWER FACTOR BOOST RECTIFIER IVO Barbi Carlos A. Canesin

l1-i VEL SINGLE-PHASE ZCS-PWM HIGH POWER FACTOR BOOST RECTIFIER IVO Barbi Carlos A. Canesin VEL SINGLE-PHASE ZCS-PWM HIGH POWER FACTOR BOOST RECTIFIER Carlos A. Canesin Paulista State University UNESP - FEIS - DEE - P.O. box 31 Fax: (+55) 18-7622125 e-mail: canesin@feis.unesp.br 15385-000 - Ilha

More information

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Riya Philip 1, Reshmi V 2 Department of Electrical and Electronics, Amal Jyothi College of Engineering, Koovapally, India 1,

More information

Generalized Multilevel Current-Source PWM Inverter with No-Isolated Switching Devices

Generalized Multilevel Current-Source PWM Inverter with No-Isolated Switching Devices Generalized Multilevel Current-Source PWM Inverter with No-Isolated Switching Devices Suroso* (Nagaoka University of Technology), and Toshihiko Noguchi (Shizuoka University) Abstract The paper proposes

More information

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 98 CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 6.1 INTRODUCTION Process industries use wide range of variable speed motor drives, air conditioning plants, uninterrupted power supply systems

More information

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION Qing-Chang Zhong The University of Sheffield, UK Tomas Hornik Turbo Power Systems Ltd., UK WILEY A John Wiley & Sons, Ltd., Publication

More information

Class #7: Experiment L & C Circuits: Filters and Energy Revisited

Class #7: Experiment L & C Circuits: Filters and Energy Revisited Class #7: Experiment L & C Circuits: Filters and Energy Revisited In this experiment you will revisit the voltage oscillations of a simple LC circuit. Then you will address circuits made by combining resistors

More information

Synchronous Current Control of Three phase Induction motor by CEMF compensation

Synchronous Current Control of Three phase Induction motor by CEMF compensation Synchronous Current Control of Three phase Induction motor by CEMF compensation 1 Kiran NAGULAPATI, 2 Dhanamjaya Appa Rao, 3 Anil Kumar VANAPALLI 1,2,3 Assistant Professor, ANITS, Sangivalasa, Visakhapatnam,

More information

A Modified Direct Power Control Strategy Allowing the Connection of Three-Phase Inverter to the Grid through LCL Filters

A Modified Direct Power Control Strategy Allowing the Connection of Three-Phase Inverter to the Grid through LCL Filters A Modified Direct Power Control Strategy Allowing the Connection of ThreePhase Inverter to the Grid through C Filters. A. Serpa and J. W. Kolar Power Electronic Systems aboratory Swiss Federal Institute

More information

Unified Power Quality Conditioner based on an Indirect Matrix Converter with a PV panel

Unified Power Quality Conditioner based on an Indirect Matrix Converter with a PV panel Unified Power Quality Conditioner based on an Indirect Matrix Converter with a PV panel Nathan Araujo, Student, IST Abstract The main goal of this master thesis is to propose a Unified Power Quality Conditioner

More information

Design and Implementation of Closed Loop LCL-T Resonant DC-to- DC Converter Using Low Cost Embedded Controller

Design and Implementation of Closed Loop LCL-T Resonant DC-to- DC Converter Using Low Cost Embedded Controller American Journal of Engineering and Applied Sciences, 2012, 5 (4), 291-300 ISSN: 1941-7020 2014 Annamalai and Kumar, This open access article is distributed under a Creative Commons Attribution (CC-BY)

More information

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction Anju Yadav 1, K. Narayanan 2, Binsy Joseph 3 1, 2, 3 Fr. Conceicao Rodrigues College of Engineering, Mumbai, India

More information

ANALYSIS OF SINGLE-PHASE Z-SOURCE INVERTER 1

ANALYSIS OF SINGLE-PHASE Z-SOURCE INVERTER 1 ANALYSIS OF SINGLE-PHASE Z-SOURCE INVERTER 1 K. N. Madakwar, 2 Dr. M. R. Ramteke VNIT-Nagpur Email: 1 kapil.madakwar@gmail.com, 2 mrr_vrce@rediffmail.com Abstract: This paper deals with the analysis of

More information