Cutes Corporation IGBT INVERTER. Instruction

Size: px
Start display at page:

Download "Cutes Corporation IGBT INVERTER. Instruction"

Transcription

1 Cutes Corporation CT-2 Series IGBT INVERTER Instruction Head Office : 2-22, Nan Yuan Road, Chung Li City, Taiwan TEL: or ext. 275 FAX: or michael_huang@cutes.com.tw URL:

2 Introduction Thank you for choosing the CT-2 inverter unit, this inverter unit is suitable for operating squirrel cage induction motors. Please read this instruction manual carefully before actual usage in order to ensure proper operation and suit your needs. Table of Contents 1. Inspection upon receiving 2. Installation and Storage 3. Application notes 4. Block diagram and Wiring 5. Operation Test 6. Function Setup and Specification 7. Description of alarm display indications 8. Troubleshooting 9. Maintenance and Inspection 1. Function code Table

3 11. Inspection upon receiving A. Check that the model, the capacity and power voltage specifications are as ordered. B. Check that no damage has occurred during transportation. C. Check that none of the internal parts have been damaged or have fallen off. D. Check that none of the connectors have been damaged or have fallen off. E. Check that there is no loosening of the terminals or screws of each of the parts. 2. Installation and Storage A. Storage: If the equipment is not to be installed immediately, it should be stored in a clean and dry location at ambient temperatures from 2 to 55. The surrounding air must be free of corrosive contaminants. B. Installation place: Places where the peripheral temperature is from -1 to 4, and where the relative humidity is 9% or less. Avoid installing at places where there is dust, iron particles, corrosive gas, water spray, direct sunlight or too much vibration. And places where has good ventilation. 1cm min. 1cm min. 1cm min. 1cm min. 3. Application notes A. Concerning the inverter unit: (1) Do not fit capacitors to the output side of the inverter in order to improve the power ratio. (2) In case of fitting MC between inverter and motor to control motor operation, then the capacity of inverter must be 6 times the capacity

4 of motor. (3) Run a motor that is within the capacity of the inverter unit, light load current and no-load current will cause the motor to develop ripple current. (4) This unit is provided with a current limiting function. The starting torque is assumed to be from 8% to 12%. B. Concerning the AC motor (1) When general-purpose motors are operated at low speeds, there is a reduced cooling effect, please apply the special purpose motor. (2) Operation at frequencies exceeding 6 Hz requires caution as there is the danger of the mechanical strength failure of the motor. (3) When motors with brakes are being operated, the power for the brake and inverter should be taken from the same power supply and the brake operation must be in phase when the unit is started and stopped. 4. Block diagram, Wiring A. Wiring of main and control circuit Wire according to the standard connection diagram. On using the external sequence control, please use small signal relay or double terminal relay to avoid relay terminal malfunction. B. Signal circuit The signal circuit uses either shielded pairs or twisted pairs, should be wired either using a wiring duct separated from that for the power circuit, or with the wiring conduit isolated as much as possible. C. Connecting the power supply and the AC motor Connect the main circuit, by wiring according to the main circuit terminal connection diagram. Care is required not to make a mistake when connecting the input and output terminals, lest it will cause inverter damage. Specifications of main circuit path and NFB are as follow:

5 Voltage (V) Model NFB (A) Wire size for circuit (mm 2 ) CT-22-A CT-22-1A CT-22-2A CT-22-3A CT-22-5A CT-22-7A CT CT CT CT CT CT CT CT CT-24-A CT-24-1A CT-24-2A CT-24-3A CT-24-5A CT-24-7A CT CT CT CT CT CT CT CT CT D. The main purpose for fitting A.C.L. at the R.S.T. input side is to curb instantaneous current and to improve power ratio, it should be fitted the A.C.L. to R.S.T. input side under the following circumstance: a. Where power supply capacity is larger than 5 KVA. b. Using thyrister, phase advance capacitor etc. from the same power

6 supply. A.C.L. Specifications table: Voltage (V) Model Current (Ar.m.s) Induction Value CT-22-A75 6A 1.8mH CT-22-1A5 1A 1.1mH CT-22-2A2 15A.71mH CT-22-3A7 2A.53mH CT-22-5A5 3A.35mH CT-22-7A5 4A.26mH 22 CT A.18mH CT A.13mH CT A.9mH CT A 7uH CT A 5uH CT A 44uH CT A 35uH CT A 27uH CT-24-A75 5A 4.2mH CT-24-1A5 5A 4.2mH CT-24-2A2 7.5A 3.6mH CT-24-3A7 1A 2.2mH CT-24-5A5 15A 1.42mH CT-24-7A5 2A 1.mH 38 CT A.7mH CT A.53mH 44 CT A.36mH CT A.26mH CT A.21mH CT A.18mH CT A.14mH CT A.11mH CT A.1mH Notes: The A.C.L. for 22V and 38V/44V have different induction values, please do not mix up.

7 E. Standard External Connection Diagram 3-phase Power Supply 22V/5Hz 2-23V/ 6Hz 4V/5Hz 38-44V/ 6Hz MCB Ext. Operation controller 5K -1V ACL R S T E VC IN2 Adaptor Voltage detect Current detect special request TH DBR P PR DBR N Braking Control Interface Convertor * U V W IM CC Ext. Operation controller 5K -1V VC IN3 CC CPU External Signal 4-2mA IN1 CC Power Control VOUT CC %tachometer (DC 1V MAX) Forward operation Reverse operation Common terminal Common terminal Common terminal Common terminal Common terminal Common terminal FR RR 1(AC2) 2(DC2) 3(3DF) 4(JOG/5DF) 5(2DF) 6(MBS/RST) COM Operational panel C1 NO1 NC1 C2 NO2 NC2 No.1 Multifunctional relay output terminal No.2 Multifunctional relay output terminal Twisted Shield wires * While external is required for DBR, disconnect internal DBR first.

8 F. Control circuit C1 NO1 NC1 C2 NO2 NC2 No.1 Multifunctional relay output terminal No.2 Multifunctional relay output terminal Vout IN1 IN2 IN3 VC CC 4-2mA Current -1V Set DC Voltage Output Accessory Voltage Set Main Voltage Set 1/2W 5K ohm 1/2W 5K ohm AC2 DC2 3DF JOG 2DF RST COM RR FR COM Multifunctional input terminal Multifunctional input terminal Multifunctional input terminal Reverse Forward operation operation

9 G. Terminal Specifications Main Circuit R.S.T AC power input terminal 3 AC power 2V/5Hz, 2-23/V/6Hz, 4V/5Hz, 4-46V/6Hz U.V.W Inverter output terminal 3-phase induction motor E Ground terminal Ground terminal of inverter chassis P.PR Brake resistor connecting terminal Connected proper brake resistor according to rated ampere Control VC Power speed output DC 1V Terminal (1) IN1 setting Current speed input DC 4-2mA, CD1=2 setting IN2 Voltage speed input DC -1V/5KΩVR, CD1=1 setting IN3 Voltage speed input setting CD -1V/5KΩVR, CD1=3 VOUT Operation With + -VOUT and - -CC shorted input (Frequency/Current) -1V DC, Frequency/Current set by CD54 output indication CC Common input control terminal Ground terminal for speed setting Control Terminal COM Sequence control common terminal Ground terminal for sequence control (2) FR Forward operation Forward operation by FR-COM shorted input terminal RR Reverse operation input terminal Reverse operation by RR-COM shorted 1 2 nd acceleration input Select 2 nd acceleration time mode by terminal (AC2) shorting 1-COM, set CD1 2 2 nd deceleration input Select 2 nd deceleration time mode by terminal (DC2) shorting 2-COM, set CD rd speed input terminal (3DF) Select 3 rd operation speed by shorting 3-COM, frequency is set by CD13 4 Jogging operation or Shorting 4-COM, JOG/5DF is set by CD59 5 th speed (JOG/5DF) 5 2 nd speed input terminal (2DF) Select 2 nd operation speed by shorting 5-COM, frequency is by CD12

10 6 Free-run operation or Shorting 6-COM, MBS/RST is set by CD59 alarm reset (MBS/RST) C1,NC Control output 1,NO1, terminal C2,NC 2,NO2 NO NC C Multifunctional relay output terminal Connector capacity AC 22V,.1A While normal C-X closed and NC-X Closed While operating C-X open and NO-X closed Functions of C1, NC1, NO1 are set by CD47 Functions of C2, NC2, NO2 are set by CD48

11 5. Operational Test A. Check before test Please check the following: (1) Is wiring correct? Check especially the input and output terminals. (2) Is there a short-circuit or ground connection on external wiring? (3) Make sure there is no loosening of screws. (4) Check external sequence control circuit. (5) Check voltage of power supply. B. Operation Method FN-8 series inverter unit has both operator panel and external operation methods. (1) Operator panel M PANEL INPUT FN-8 (2) External signal operation MCB M SWITCH CONTROL FN-8 C. Operational test Test according to the following procedure and be aware of indications. (1) Basic operational test -Operational procedure

12 I. Connect power supply II. Monitor glittering indicates frequency III. Press either FWD or REV key, motor starts running. It will stop accelerating after reaching set frequency IV. After pressing STOP key, motor stops and indicating frequency steps down. The set frequency starts glittering after the motor stops. V. Repeat procedures III and IV to test forward and reverse operations. -Operation monitor display I. Stop display, with reciprocal glittering indicated Hz LED and factory setting 1. Hz. II. Hz display, with FWD(or REV) LED lighted up steadily, indication goes up according to frequency until reaching value 1. Hz III. Indication goes down according to operation frequency, and returns to situation I after stop (2) Frequency change test - Operational procedure I. Exercise the above operation test procedures I, II, III II. Directly press panel number key to input value III. Use SET key to change frequency value Directly use step keys at procedure II to change, or use function keys (PROG, READ, SET) to program IV. Repeat procedures II, III to increase or decrease frequency -Operation monitor display I. The same as the above basic test of I, II II. Monitor display indicates the input value while motor is running as the original setting III. Monitor display indicates the current new setting value Note: 1. Is motor operation direction correct? (Changing any two of U.V.W output terminals to change motor operation direction) 2. Is there any noise or vibration on motor? 3. Is it run smoothly during acceleration and deceleration? 4. Is there any power failure?

13 6. Adjust and Function Specification Operator panel parts names and functions 7-segement monitor 1.Displays frequency Cd2= Displays current Cd2=1 Displays RPM NO2=2 Displays various readings see Cd2 2. After indicates alarm, ignore Cd2, directly displays failure status READY Displays that the panel is ready to accept key input Monitor mode display Displays monitor status Ten-key pad Data input key Operation monitor display Displays forward/reverse/stop status READY HZ A ALARM Operation instruction keys FWD REV STOP Control from keyboard External control operation, stop mode by set Cd4=1 PROG READ SET 1. STOP key Step keys 1. Stops inverter operation 2. Resets function 3. Resets alarm indication 1. To change frequency 2. Select function items Function setting keys These three keys offer selecting read or setting value of function Code No. Set frequency (settable range -24 HZ) There are 5 methods to change set frequency, items A-C are methods of panel key operation, items D-E are methods of external terminal input. A. Directly use number keys to input data B. Use PROG key to input data

14 C. Use step keys(, ) for setting D. Set external voltage E. Set external current Note: 1. Set value should be in accordance with V/F slope (CD5) and upper limit frequency (Cd17). Set function key PROG C d C d READ 3 3 SET C d 3 SET 3 Set step key (, ) Press [Arrow up] key ( ) to increase set frequency. Press [Arrow down] key ( ) to decrease set frequency. Code No.1 Setting procedure of frequency (Selective range -7) The function cannot be modified during revolution. Setting procedure of frequency is to select either panel key or external analog signal. Cd1= Set frequency on operation panel, as the above items A-C. Cd1=1 Set frequency by terminal In2 DC -1V/5KΩVR Cd1=2 Set frequency by terminal In1 DC 4-2mA Set number key Ex.: Set frequency to 2Hz 2 2 Ex. Instant change to 2Hz 2 SET 2 *Note:

15 1. Displays frequency only in frequency status. Code No.2 Select monitor display (Selective range -6) The monitor is consisted of four 7-setment LEDs, displays frequency, current and various data by digital number and character. Cd2= Display the frequency, LED HZ active Cd2=1 Display the current, LED A active Cd2=2 Display RPM, LED HA, A de-active Cd2=3 Display DC bus Cd2=4 Display rms of U.V.W AC output Cd2=5 Display external control terminal status Cd2=6 Display MCK Code No.3 Torque mode (Selective range,1) The function cannot be modified during revolution. Cd3= Automatic torque compensation de-active, set compensation by Cd7. Cd3=1 Automatic torque compensation active, the largest compensation is 2 times of the setting Cd7. Code No.4 Operation command mode (Selective range,1) The function cannot be modified during revolution. Cd4= Operation on operation panel Cd4=1 Operation by external terminal, including FR, RR, common terminal (1, 2, 3, 4, 5, 6) Code No.5 Set V/F pattern (Selective range 1-11) The function cannot be modified during revolution. There are 11 patterns of V/F slope, as follow:

16 V V V V V F F F F 5HZ 6HZ 5HZ 1HZ 6HZ 12HZ V V V V F F F F 5HZ 15HZ 6HZ 18HZ 5HZ 2HZ 6HZ 24HZ V 9 1 F F 87HZ 174HZ 13HZ 26HZ When Cd5=11, V/F slope is determined by Cd57, Cd58. Note: Select Cd5=11 if set frequency exceeds 24 Hz. Code No.6 Motor current rate (Settable range 25-1) Set motor overload protective current, in order to avoid motor failure because of overload. Set value=1, please calculate the following formula: Set Value = Motor rated current / Inverter rated current 1 Ex. Use inverter with 3.7KW(5HP) to drive motor with 2.2KW(3HP) Inverter rated current = 17.4A Motor rated current = 8A Set Value = 8 / = 46% Code No.7 Torque compensation Vb (Settable range -15) The function cannot be modified during revolution. This function is to raise output voltage to increase torque of motor. It can also be used to increase load slope of low voltage produced by long wiring between inverter and motor, as well as fluid, fan and pump.

17 Output Voltage 1% 5% 15% VB FS % Output Frequency (HZ) Code No.8, 9, 1, 11 Acceleration / deceleration time (Settable range ) The time needed for set frequency from Hz to 5Hz. There are 2 selections for each of acceleration time and deceleration time. To set acceleration/deceleration time Set Value (T) = (5- ) / F T1 T1: time needed for accelerate / decelerate F: frequency changed Ex.: Frequency from 5Hz down to 3Hz, needed time 1 sec. Then: Set Value (T) = 5 / = 2.5 Cd8 = Acceleration time Cd9 = Deceleration time Cd1 = 2 nd Acceleration time Cd11 = 2 nd Deceleration time Note: The 2 nd acceleration / deceleration time only available on external operation mode (e.g. Cd3=1). Code No.12, 13, 14 Speed setting (Settable range.5-24) This function has 4 kinds of speed setting The 2 nd, 3 rd, 4 th speeds are set from external terminal FR (or RR) which accommodate terminal 3, 5, the setting value cannot exceed the allowed range. Cd12 = 2 nd speed setting Cd13 = 3 rd speed setting Cd14 = 4 th speed setting Note: When apply to multi-speed setting, use external control (e.g. Cd3=1) to start and use panel to pre-input to set frequency.

18 Code No.15 Jogging frequency (Settable range.5-3) To control jogging, use external terminal 4-FR or 4-RR with COM shorted. Set running direction FR or RR 2 Running mode: Jogging Forward(Reverse) Note: Jogging operation is valid only when operation command selects the external operation signal mode (e.g. Cd3=1) and Cd59= or 1. Jogging operation procedures: 1. First put in 4, and then FR (or RR). 2. Put in 4 and FR (or RR) simultaneously. Be sure always to put in 4 before FR (or RR). Code No.16 Start frequency (Settable range.5-3) Set motor start frequency Settable range of frequency is.5hz to 3Hz, accuracy is.1hz. Frequency Start Frequency Time Note: The most appropriate range for start frequency is.5hz to 1Hz. Code No.17 Upper limiter of frequency (Selective range 1-24) This limiter is used to operate within upper limit frequency of motor Avoid input errors caused by the panel keys and result in mechanical

19 damage. Note: If set frequency exceeds 24Hz, set Cd5=11. Code No.18 Lower limiter of frequency (Settable range.5-1) This limiter is used to operate within lower limit frequency of motor FH Output Frequency Upper Limiter Lower Limiter Set Frequency Operation Code No.19 Acceleration / deceleration time of jogging (Setting range.1-3.) Time needed for set frequency from Hz to 5Hz. Set Value (T) = (5 - ) / F T1 T1: Time needed for acceleration/deceleration F: Frequency changed Code No.2, 21 Jump frequency (Settable range -24) This function is to avoid mechanical resonance frequency Frequency operation automatically jumps to point +/- jump width (set by Cd22) This function is only available on constant speed operation, not influence during acceleration/deceleration, it is settable at 2 points. Output Frequency Cd21 Cd22 Cd2 Cd22 Time Code No.22 Jump frequency width (Settable range -6) This function must accommodate Cd2 and Cd21

20 Code No.23 Braking mode (Settable range -3) This function must accommodate Cd24, Cd25, Cd26. Cd23= No DC braking Cd23=1 Stop mode Cd23=2 Start mode Cd23=3 Stop and start mode Code No.24 DC braking frequency (Settable range 1-1) This function must accommodate Cd23, Cd25, Cd26. Set frequency of DC brake starts at the time of inverter deceleration stops, the DC brake is active when operates below the starting frequency. Code No.25 DC braking voltage (Settable range 1-15) This function must accommodate Cd23, CD24, Cd26. DC braking torque setting When DC brake is active, monitor displays dcbr Cd25=1-15, the higher value the higher output brake torque Note: When DC brake voltage is high, be aware of over current. Code No.26 DC braking time (Settable range 1-6) Adjust DC braking time Output Frequency Start Frequency Braking Frequency Braking Voltage Braking Rate Braking Time Time Time Note: 1. DC braking time too long or too many times is possible to cause motor damage because of overheat.

21 2. Set Cd23= when DC braking is not required. Code No.27 Motor running direction (Settable range -2) Fix motor running direction to prevent mechanical damage. Cd27= Both forward and reverse operations are possible. Cd27=1 Only forward operation is available. Cd27=2 Only reverse operation is available. Code No.28 Restart / Free run start (Settable range -3) Cd28 Restart Free run start No function No function 1 With function No function 2 No function With function 3 With function With function 1. Free run restart function: When power supply failure occurs or voltage loss, there may be a malfunction on PCB control circuit, this function is to return to the original setting of speed and frequency after power recovery. Power Supply Power Failure, Voltage loss External Switch Motor Speed 15msec Time needed for Inverter to detect motor free run speed 2 sec. 2 sec. Note: (1) Free run direction must be the same as setting direction. (2) After power recovery, there is about 2 sec. delay time (motor frequency detect) for start. Restart after power recovery, the inverter will output a frequency signal first to detect if it conforms the frequency of free run, if the two frequencies are equal, the inverter output rated voltage then. The purpose is to prevent over current to happen.

22 2. Restart after instantaneous power failure This function if different from free run restart, the inverter control power is maintained above 5V. Restart after instantaneous power failure: no function Restart after instantaneous power failure: with function Power Supply When it detects low voltage LU, it activates STOP, ALARM, LU. After recovery of voltage, LU and ALARM LED are de-active, STOP remains the same, it will have to switch ON again to restart if you select external control, if you select panel control, just press FWD or REW key to restart. Restart motor under free run. Instantaneous power failure, Voltage loss External Switch Inverter Power 15msec. Motor Speed Note: The inverter will be de-active when control voltage is less than 5V. Apply with free run restart function when it is required. Code No.29 Time (Settable range -9) This function must accommodate Cd47= or Cd48= setting. When motor starts operation, the time counter is active. Code No.3 Stop by panel key (Settable range -1) Cd3= No function Cd3=1 With function Stop function: This function enables the inverter to be stopped by panel key while the inverter is operated by external sequence.

23 Code No.31 Initial factory setting (Settable range,1) The function cannot be modified during revolution. Set data to original factory setting. Cd31= No change Cd31=1 Initial factory setting, refer to function code table. Note: After this function is active, content value returns to, readable value is always. Code No.32, 33, 34, 35 Failure record Record cause of failure, in order to solve failure. Note: 1. Cannot record failure Err, Ero, Erc. 2. Only memorize 4 records. 3. Cannot record inverter stopped by low voltage. 4. Read only Code 32, 33, 34, 35 or delete all (Code 36), cannot put in failure record by operator. Code No.36 Failure record clear (Settable range, 1) Clear the failure record content of Code 32, 33, 34, 35. Cd36= No change Cd36=1 All of the contents of data will be none. Note: After this function is active, content value automatically returns to, thus readable value is always. Code No.37 Frequency gain setting (Settable range 2-2) Select ratio of frequency gain Gain setting for external signals is available using this function. Output Frequency = Set Value Frequency Gain Ex. Under the mode of external voltage (-1V) frequency setting, frequency gain = 1%, set voltage to 2V, Output Frequency = (2V/1V) 12Hz 1% = 24Hz If change frequency gain to 15%, then Output Frequency = (2V/1V) 12Hz 15% = 36Hz

24 2% 1% 2 1 2% V 2 4mA Analog Setting Signal 1V 2mA Note: If the maximum frequency exceeds more than 12Hz, gain setting of larger than 1% is ignored and fixed at 1% and input data of Code 37 will not be changed. Code No.38 Analog output calibration (Settable range 9-11) Set the ratio of frequency graduation calibration then Cd38=99 99% of initial factory Cd38=11 11% of initial factory Set Cd54 to select analog output Code No.39 Frequency command bias (Settable range -25) External analog frequency command bias setting Frequency Output % Settable Range V Frequency Command 1V Code No.4, 41, 42, 43 Multi-speed setting (Settable range.5-24) This function has 8 kinds of speed operation Use external terminal FR (or RR) accommodate 3, 4, 5 to select different speeds. Refer to the following table: Cd4= 5 th speed setting Cd4=1 6 th speed setting Cd4=2 7 th speed setting

25 Cd4=3 8 th speed setting Note: Apply to multi-speed setting, external control is required for operation control mode (e.g. Cd4=1), and it is also required to set Cd59 for activating common terminal 4. External terminal Selective speed Name Terminal 5 Terminal 3 Terminal 4 : stands for external terminal to put in. Code No.44 Stop mode (Settable range -2) Cd44= Deceleration stop Cd44=1 Free run stop Cd44=2 Free run stop, but restart after the deceleration time is reached, Deceleration time is set by Cd11. Code No.45 Frequency detect level (Settable range.5-24) This function is only available when RELAY output terminal Cd47=6 or Cd48=6, and Cd45 is assigned. HZ OUTPUT CD45 TIME FA-FC OPEN CLOSE TIME Code No.46 Speed multiplier (Settable range.1-5) The function shows revolution speed multiplied by a scaling factor on the 7-segment display.

26 1. Hz and A LED de-active. 2. RPM = Frequency Speed multiplier. 3. If the value overflow, it will show Code No.47 Relay 1 output select (Settable range -6) The function sets the mode of relay to activate. Cd47 Specification Remark Time counter Time reached to the content of Cd29 1 Fault 2 Stop 3 Acceleration 4 Speed reached 5 Deceleration 6 Speed pass over Revolution frequency >content of Cd45 Code No.48 Relay 2 output select (Settable range -6) The function sets the mode of relay to activate. Cd48 Specification Remark Time counter Time reached to the content of Cd29 1 Fault 2 Stop 3 Acceleration 4 Speed reached 5 Deceleration 6 Speed pass over Revolution frequency >content of Cd45 Code No.49 Function to lock data (Settable range, 1) To lock data, prevent errors by none operator. Cd49= Data change capable Cd49=1 Data change not capable Code No.5 Software version (Read only) This function is to record software version, read only.

27 Code No.51 Motor rated voltage setting Vr (Settable range 1-45V) This function cannot be modified during revolution. RMS Setting 22V Series 1 38V Series V Series 2 Ex. Power supply voltage 22Vrms, Cd51=22 1, then the inverter Vrate=22Vrms. Power supply voltage 38Vrms, Cd51= , then the inverter Vrate=38Vrms. Power supply voltage 44Vrms, Cd51=22 2, then the inverter Vrate=44Vrms. Voltage Output V Vr (HZ) Frequency Output 1. Vin >Vrate when Fr <Fb Vout = Fr / Fb Vrate when Fr >Fb Vout = Vrate 2. Vin <Vrate when Vout <Vin Vout = Fr / Fb Vrate when Vout >Vin Vout = Vin Vin: Power supply voltage Vout: Inverter output voltage Vrate: Motor rated voltage Fr: Inverter revolution frequency Fb: Bottom frequency Code No.52 Motor no-load current setting (Settable range 5-6) This function cannot be modified during revolution. The function is to compensate motor vibration during a light-load and fixed speed revolution. This function must accommodate the content of Cd3. Ex. Motor: 6Hz, 4-phase, 1 horsepower, 22V, no-load current 1.2Arms Inverter: 1 horsepower, 22V, rated current 4.2Arms, Cd6=1 Cd52 = Motor no-load current / Inverter rated current Motor rated current ratio Cd6 1% = 1.2 / 4.2 1% 1%

28 = 28.5% Code No.53 Motor slip differential compensation (Settable range -1) This function is to compensate speed variation produced by load variation. This function must accommodate the content of Cd52. Setting value -1 in relative slip differential.-1.% Ex. 6HZ, 4-phase 17 rpm Synchronous speed = 18 rpm Full-load speed = 17 rpm Slip differential speed = 18-17=1 rpm Slip differential % = Slip differential speed / Synchronous speed 1% = 1 / 18 1% = 5.5% Slip differential compensation Load variation Time Motor speed Without slip differential compensation Motor speed With slip differential compensation Output frequency With slip differential compensation

29 Code No.56 Overcurrent stall preventive mode (Settable range 1-2%) This function is to prevent when motor current exceeds stall current from stall. There are 2 kinds of acceleration time slopes when motor acceleration current exceeding stall current occurs: Instantaneous load increase during steady operation and current exceeding overcurrent stall, revolution frequency will drop till current dropped to within stall current level. Frequency Normal Status Stall preventive mode Frequency Stall preventive mode Time Time Inverter current During acceleration Stall current level Time Inverter current Stall current level Druing speed reached Time Code No.57 Maximum frequency setting FH (Settable range 1-24) This function cannot be modified during revolution. When Cd5=11, the maximum frequency V/F slope FH Settable range 1Hz-24Hz Please refer to function code table. Code No.58 Bottom frequency setting Fb (Settable range 1-24) This function cannot be modified during revolution. When Cd5=11, the bottom frequency V/F slope Fb Settable range 1Hz-24Hz (Fb FH) Please refer to function code table.

30 Code No.59 Select external terminal 4 / 6 (Settable range -3) This function is to select setting common terminal 4 and 6. CD59 Common input terminal setting External terminal 4=JOG External terminal 6=MBS 1 External terminal 4=JOG External terminal 6=RST 2 External terminal 4=5DF External terminal 6=MBS 3 External terminal 4=5DF External terminal 6=RST Terminal specification: JOG: Jogging operation 5DF: Multi-speed MBS: Free run stop, operates both panel key and external signal. RST: Reset, operates both panel key and external signal. Code No.6 V / F frequency FC (Settable range.5-24) This function cannot be modified during revolution. To set V/F slope frequency FC when Cd5=11. Settable range 1Hz-24Hz (FC Fb) Output Voltage 15% 15 Cd7 VB % FC Fb FH Cd6 Cd58 Cd57 (HZ) Output Frequency Code No.61 PWN frequency This function is to set PWN frequency Cd61 PWM Frequency 1 4 KHZ 2 6 KHZ 3 8 KHZ 4 1 KHZ 5 12 KHZ 6 14 KHZ Note: The maximum PWM frequency setting value is 8 KHZ for inverter above 2HP (including 2HP).

31 7. Description of alarm display indications Error indication Description of fault operation Item for inspection Processing Err Operation error Was the unit operated as Use the correct procedure indicated in the manual ErO Operation error of internal Switch off the power and then Replace the unit ROM, RAM apply again ErC Error of internal CPU Is there a large amount of Check the contact absorber. Install external noise a noise filter OCPA Overcurrent (18% rated Was there rapid acceleration Lengthen the acceleration time current) OCPd Overcurrent (18% rated Was there rapid deceleration Lengthen the deceleration time current) OCPn Overcurrent (18% rated Was there any variation in the Lengthen the time for the load current) load variations OC Overcurrent (2% rated Was there rapid acceleration / Lengthen the acceleration and current) deceleration and variation in the deceleration time and reduce the load load OCS Output short circuit or ground Is there a short circuit for the Perform a megger check for the detected output or grounding for the motor motor OU DC link overvoltage Was there fast deceleration, or fast voltage Lengthen the deceleration time. Investigate the use of the optional DBR LU Insufficient voltage detected Is there a low voltage at power, Improve the voltage condition and due to power failure or or internal inverter wiring error confirm inverter model instantaneous power loss. OH Overheating of the cooling 1. Cooling fan stops 1. Exchange the cooling fan fan detected 2. Ambient temperature too 2. Lower the ambient hot temperature 3. Motor being overload 3. Check the load conditions OL Overload detected for more Is the motor being overloaded Increase the capacity of the than one minute inverter and motor buoh DBR overheat detected Is the braking ratio appropriate Reduce GD 2 of load or lengthen deceleration time Fb Blown fuse Is the fuse blown Change a fuse PLU Power voltage too low Is power voltage too low Improve power supply condition

32 8. Troubleshooting Description of trouble Possible cause Solution The motor does not run at all OCPA is indicated as soon as the motor is started. (Overcurrent protect operation during acceleration.) OCPd is indicated as the motor is decelerating. (Overcurrent protect operation during deceleration). OC or OCS is indicated during operation. (Overcurrent) 1. Wiring error Refer to the wiring diagram 1. Check the power input wiring 2. Is there a voltage for U.V.W output 2. Wrong settings at operator panel The function code No.4 is as follows : Panel key operation 1: External signals 3. Inverter displays fault indication Refer to Protect Function 4. Motor cannot start due Exchange a higher capacity one to overload 5. Motor breaks down Repair motor 6. Inverter breaks down Please contact us 1. Motor wiring error Refer to the wiring diagram 2. Overload Reduce the load or increase inverter capacity 3. Is V/F slope appropriate Check Code 5 V/F slope is appropriate with motor specification 4. Is start torque appropriate Adjust Code 7 torque boost to over come steady friction but not over current trip. 5. Is the acceleration time too short when compared to load GD 2 Lengthen acceleration time by apply Code 8 and Code 1 or increase inverter capacity 6. The inverter is starting Refers to Code 28, change the value from during motor free-run to 1 1. Deceleration time too Apply Code 9 and Code 11 to lengthen short, unable to be deceleration time or increase inverter loaded capacity 1. Short circuit on U.V.W Exclude short circuit or grounding or grounding for motor 2. Instantaneously Reduce load or increase inverter capacity mechanical load on motor 3. Motor breaks down Repair motor

33 4. Inverter breaks down Please contact us OU is displayed 1. Is power voltage with Improve power voltage condition during inverter operation 2. the specification Braking resistor not Apply braking resistor, increase braking applied ratio 3. Deceleration time too short, unable to be Apply Code 9 and Code 11 to lengthen deceleration time loaded LU is displayed 1. Is power voltage with Improve power voltage condition during inverter operation 2. the specification Instantaneous power Check the capacity of the power facilities voltage failure 3. Power dropped and Check the capacity of the power facilities the protector function has operated OL is displayed 1. Overload Reduce load or increase inverter capacity during inverter 2. Is inverter overcurrent Apply Code 6 to re-set motor rated operation limiter appropriate current OH is displayed during inverter operation Check if the cooling fan is still working Is ambient temperature too hot Change cooling fan and clean dirt Improve ambient temperature condition No any indication, the 1. Power failure Check the capacity of the power facilities output frequency displayed 2. Is there loosen part on Check external control terminal external control terminal

34 9. Maintenance and Inspection Maintenance and inspection must be taken under power off. Cautions on maintenance and inspection: (1) Capacitor is charged at high voltage for a while after turning off the power. (Accordingly, start the inspection work at least 5 minutes after turning off the power) (2) Do the work with operator. Inspection items: (1) Please check the following items A. Motor runs as expected. B. Avoid installing on circumstances like acid, alkaloid. C. No trouble is recognized in the cooling system and irregular vibration or noise. D. No parts is overheated or burned. (2) Periodic inspection Interval Inspection item Every 6 months 1. Terminal plates and mounting bolts. 2. Corrosion and breaks in the terminal clips for the wiring. 3. Condition for the connector fixing. Once a year 1. Use clean, dry air to remove dust buildup from the guards, the stack and the cooling fan. 2. Check for parts burns or damage and make any exchanges necessary.

35 1. Function Code Table Code No. Function Detail of Data Initial factory setting Set frequency -24Hz 1 1 Frequency setting procedure : Operation panel Cd 1: External IN2 (-1V) 2: External IN1 (4-2mA) 2 Select monitor display : Frequency (HZ) data 1: Current (A) 2: r.p.m 3: DC Voltage 4: Output AC Voltage 5: External I/O status 3 Torque mode : Without auto boost 1 1: With auto boost 4 Operation command : Operation panel 1: External signal 5 V/F pattern 1-1 fixed Modes 2 11: Set by CD57, CD58 6 Motor rated current 25-1% 1 7 Torque boost -15 (-15.%) st acceleration time (S/5HZ) st deceleration time (S/5HZ) nd acceleration time (S/5HZ) nd deceleration time (S/5HZ) 1 12 No.2 frequency HZ 2 13 No.3 frequency HZ 3 14 No.4 frequency HZ 4 15 Jogging frequency.5hz-3hz 5 16 Start frequency.5hz-3hz 1 17 Upper limit frequency 1-4HZ 6 18 Lower limit frequency -1HZ 19 Jogging acceleration /.1-1 (S/5HZ) 1 deceleration time 2 Jump frequency 1 HZ 21 Jump frequency 2 HZ 22 Jump frequency width -6HZ 1 23 Braking mode : de-active

36 1: Active when stop 2: Active when start 3: Active both stop and start 24 DC braking frequency 1-1HZ 1 25 DC braking rate DC braking time 1-6 Sec Operation direction : Both forward and reverse setting 1: Forward only 2: Reverse only 28 Restart in : Without / Without instantaneous power failure / Free run start 1: With / Without 2: Without / With 3: With / With 29 Time 1-9 (Sec.) 5 3 Stop function at : Impossible 1 panel key under the operation of external sequence 1: Possible 31 Initialize data : No change 1: Data at the time of shipment 32 Fault annunciation OCPA OCPN OCPD none (The last) 33 Fault annunciation OCS OC OL none (Before the last) 34 Fault annunciation OU PLU LU none (The 2 nd before the last) 35 Fault annunciation Fb Erc none none (The 3 rd before the last) 36 Memory clear for fault annunciation 1: Memory clear 37 Frequency gain setting 2-2% 1 38 Analog output calibrate 9-11% 1 39 Frequency command bias 4 No.5 Frequency HZ No.6 Frequency HZ 5

37 42 No.7 Frequency HZ No.8 Frequency HZ 6 44 Stop mode : Decelerate stop 1: Free run stop 2: Free run stop after deceleration time is reached 45 Detect frequency level.5-24hz.5 46 Speed multiplier Relay 1 output select Relay 2 output select Lock data : Data change capable 1: Data change not capable 5 Software version Read only 1 51 Motor rated voltage V Series 1 38V Series V Series 2 52 Motor no-load current 5-6% 3 53 Motor slip differential boost % 54 External analog output : Display output frequency select 1: Display output current Current stall preventive 57 Max. frequency FH setting 58 Motor rated frequency Fb 59 MBS / RST JOG / 5DF 1-2% HZ (FH) HZ (Fb) FH Fb : Terminal 4=JOG, 6=MBS 1: Terminal 4=JOG, 6=RST 2: Terminal 4=5DF, 6=MBS 3: Terminal 4=5DF, 6=RST 6 V/F Frequency FC.5-24HZ.5 61 P.W.M. Frequency 1: 4KHZ 4: 1KHZ 2: 6KHZ 5: 12KHZ 3: 8KHZ : 14KHZ 6 3

8. Troubleshooting Maintenance and Inspection.. 45

8. Troubleshooting Maintenance and Inspection.. 45 Introduction Thank you for choosing the CT-2000ES inverter unit, this inverter unit is suitable for operating squirrel cage induction motors. Please read this instruction manual carefully before actual

More information

CHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3

CHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3 CHAPTER MAINTENANCE AND 6 TROUBLESHOOTING In This Chapter... Maintenance and Inspection.................6 2 Monthly Inspection:..................................6 2 Annual Inspection....................................6

More information

VFD - D700 Series Specifications. The latest low-cost variable speed control solution for centrifugal pumps.

VFD - D700 Series Specifications. The latest low-cost variable speed control solution for centrifugal pumps. VFD - D700 Series Specifications The latest low-cost variable speed control solution for centrifugal pumps. Built-in PID Control to maintain pressure, flow, measured value, and much more 125% overload

More information

AV-300i Specifications. Saftronics Inc. PC10 Product Specifications PC10. Mini Vector AC Drive

AV-300i Specifications. Saftronics Inc.  PC10 Product Specifications PC10. Mini Vector AC Drive Saftronics Inc. www.saftronics.com TM AV-300i Specifications PC10 Product Specifications PC10 Mini Vector AC Drive 1 (1) T hree-phas e 230V input Drive Hp 1/8 1/4 1/2 1 2 3 5 7.5 10 Nominal applicable

More information

13. Before making a service call Trip information and remedies

13. Before making a service call Trip information and remedies . Before making a service call Trip information and remedies.1 Trip causes/warnings and remedies When a problem arises, diagnose it in accordance with the following table. If it is found that replacement

More information

S11 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3- phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC. 1.1 References A. National

More information

Fan and Pump AC Inverter

Fan and Pump AC Inverter Fan and Pump AC Inverter Key Features for Fan and Pump Applications PID and Auto Energy Saving Functions. Input Phase Loss and Output Phase Loss Protection. LCD Keypad can be used to copy parameter settings

More information

General Specifications FECA-TE /2010. Phone: Fax: Web:

General Specifications FECA-TE /2010. Phone: Fax: Web: General Specifications FECA-TE-117 06/2010 1. Standard Specifications 1) Three-phase 230V series Output ratings Input ratings Braking Item Specifications Type (FRN C1S-2U) F12 F25 F50 001 002 003 005 Nominal

More information

VF-nC1 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba VF-nC1 AC Variable Frequency Drives, 6 pulse for 100V single-phase 0.1 to 0.75kW, 200V single-phase 0.2 to 2.2kW and 200V threephase 0.1

More information

GS1 Parameter Summary Detailed Parameter Listings...4 9

GS1 Parameter Summary Detailed Parameter Listings...4 9 CHAPTER AC DRIVE 4 PARAMETERS Contents of this Chapter... GS1 Parameter Summary...............................4 2 Detailed Parameter Listings..............................4 9 Motor Parameters.........................................4

More information

Warning!! 2. The drive contains high voltage that can cause electric shock resulting in personal injury or loss of life.

Warning!! 2. The drive contains high voltage that can cause electric shock resulting in personal injury or loss of life. ! Warning!! 1. Please read this manual completely before installing the drive. 2. The drive contains high voltage that can cause electric shock resulting in personal injury or loss of life. 3. Be sure

More information

6.9 Jump frequency - Avoiding frequency resonance

6.9 Jump frequency - Avoiding frequency resonance E581595.9 Jump frequency - Avoiding frequency resonance : Jump frequency : Jumping width Function Resonance due to the natural frequency of the mechanical system can be avoided by jumping the resonant

More information

E3 Adjustable Speed Drive Engineering Specification

E3 Adjustable Speed Drive Engineering Specification E3 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba E3 AC Variable Frequency Drives, 6 pulse for 230V and 460V. 1.1 References A. National

More information

CHAPTER 8 PARAMETER SUMMARY

CHAPTER 8 PARAMETER SUMMARY CHAPTER PARAMETER SUMMARY Group 0: System Parameter VFD-V Series 00-00 Identity Code Based on the model type 00-01 Rated Current Display 00-02 Parameter Reset 00-03 00-04 Star-up Display of the Drive Definitions

More information

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

CHAPTER AC DRIVE PARAMETERS. In This Chapter... CHAPTER AC DRIVE 4 PARAMETERS In This Chapter... GS2 Parameter Summary....................4 2 Detailed Parameter Listings.................4 11 Motor Parameters........................4 11 Ramp Parameters.........................4

More information

FUJI Inverter. Standard Specifications

FUJI Inverter. Standard Specifications FUJI Inverter o Standard Specifications Norminal applied motor The rated output of a general-purpose motor, stated in kw. That is used as a standard motor. Rated capacity The rating of an output capacity,

More information

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13 Index A A Group functions 3 9 AC reactors 5 3 Acceleration 1 15, 3 8 characteristic curves 3 26 second function 3 24 two-stage 4 19 Acceleration stop function 3 21 Access levels 3 5, 3 36, 4 25 Access

More information

Variable Frequency Drive / Inverter (0.4 ~ 280kW)

Variable Frequency Drive / Inverter (0.4 ~ 280kW) Variable Frequency Drive / Inverter (0.4 ~ 280kW) & Standard Features Configuration Comparison Comparison Table Enclosure IP00 IP20 NEMA 1 Rating Single phase 0.4 2.2kW 0.4 1.5kW Three phase 0.4 4kW Constant

More information

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE 1 2 SERIES 1 2 pag. 4 pag. 5 Applications Model identification 3 pag. 5 4 pag. 6 Capacity

More information

RHYMEBUS INVERTER AC MOTOR CONTROLLER RM5G. Series

RHYMEBUS INVERTER AC MOTOR CONTROLLER RM5G. Series RHYMEBUS INVERTER AC MOTOR CONTROLLER RM5G Series Pre-quality Satisfied Service Analog Keypad (KP-202C) Digital Keypad (KP-201C) RHYMEBUS CORPORATION FOR FOREWORD Thank you for choosing the RHYMEBUS "

More information

Manual Overview...1 2

Manual Overview...1 2 GETTING STARTED CHAPTER 1 Contents of this Chapter... Manual Overview.....................................1 2 Overview of this Publication..................................1 2 Who Should Read This Manual...............................1

More information

CTi Automation - Phone: Fax: Web: -

CTi Automation - Phone: Fax: Web:  - CONTENTS Chapter 1 Specifications 1. Standard Specifications... 1-2 1.1 Three-phase 230V FRENIC5000G11S Series... 1-2 1.2 Three-phase 460V FRENIC5000G11S Series... 1-3 1.3 Three-phase 230V FRENIC5000P11S

More information

Multi-function, Compact Inverters. 3G3MV Series

Multi-function, Compact Inverters. 3G3MV Series Multi-function, Compact Inverters 3G3MV Series There has been a great demand for inverters with more functions and easier motor control than conventional i OMRON's powerful, compact 3G3MV Series with versat

More information

AV-300i Specifications. Saftronics Inc. VG10 Product Specifications VG10. Dynamic Vector Drive

AV-300i Specifications. Saftronics Inc.   VG10 Product Specifications VG10. Dynamic Vector Drive Saftronics Inc. www.saftronics.com TM AV-300i Specifications VG10 Product Specifications VG10 Dynamic Vector Drive 1 Category Item Description Nominal Motor 230 VAC, 3 Phase 1/4 Hp to 125 Hp 460 VAC, 3

More information

Rexroth Frequency Converter Fe 0.75 kw to 7.5 kw / 400 VAC

Rexroth Frequency Converter Fe 0.75 kw to 7.5 kw / 400 VAC Electric Drives and Controls Hydraulics Linear Motion and Assembly Technologies Pneumatics Rexroth Frequency Converter Fe 0.75 kw to 7.5 kw / 400 VAC Simple, scalable and economical Service Bosch Rexroth

More information

SAFETY INSTRUCTIONS WARNING

SAFETY INSTRUCTIONS WARNING Important User Information Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this

More information

LG Variable Frequency Drive

LG Variable Frequency Drive LG Variable Frequency Drive ig5 Series 0.5-5.4HP (200/400V) Installation, Operation and Maintenance Instruction Read this manual carefully before installing, wiring, operating, servicing or inspecting

More information

VLT MICRO Series Adjustable Frequency Drive Instruction Manual

VLT MICRO Series Adjustable Frequency Drive Instruction Manual VLT MICRO Series Adjustable Frequency Drive Instruction Manual 1/00 23-6127-00 Revision DR 2 Table of Contents Chapter 1 Chapter 2 Chapter 3 Introduction Getting Started... 5 Receiving, Inspection, and

More information

Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts

Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts Inverter STARVERT ig5a LS Starvert ig5a is very competitive in its price

More information

This operation manual is intended for users with basic knowledge of electricity and electric devices.

This operation manual is intended for users with basic knowledge of electricity and electric devices. This operation manual is intended for users with basic knowledge of electricity and electric devices. Safety Information Safety Information Read and follow all safety instructions in this manual precisely

More information

VS-616PC5/P5 Series User s Manual

VS-616PC5/P5 Series User s Manual VS-616PC5/P5 Series User s Manual Variable Torque Inverter PRECAUTIONS! WARNING 1) Read this manual in its entirety before installing or operating the VS- 616PC5/P5 inverter. 2) Do not connect or disconnect

More information

GS S. Compact Space Ve VFD. Frequency and .5 5

GS S. Compact Space Ve VFD. Frequency and .5 5 GS S Compact Space Ve VFD Frequency and.55.55 8 Thank you for purchasing CERUS Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards

More information

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class HITACHI SJ1 Series Inverter Quick Reference Guide Single-phase Input 2V Class Three-phase Input 2V Class Three-phase Input 4V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB5821XD Dec.

More information

[ 4 ] Using pulse train input (F01 = 12)

[ 4 ] Using pulse train input (F01 = 12) [ 4 ] Using pulse train input (F01 = 12) Selecting the pulse train input format (d59) A pulse train in the format selected by the function code d59 can give a frequency command to the inverter. Three types

More information

Before you operate the inverter, the parameters that you must first program are the basic parameters.

Before you operate the inverter, the parameters that you must first program are the basic parameters. . Main parameters Before you operate the inverter, the parameters that you must first program are the basic parameters..1 Searching for changes using the history function () : History function History

More information

SAFETY INSTRUCTIONS. After reading this manual, keep it in the place that the user always can contact easily.

SAFETY INSTRUCTIONS. After reading this manual, keep it in the place that the user always can contact easily. Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS To prevent injury and property damage, follow these instructions. Incorrect operation due to ignoring instructions will cause

More information

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3 CHAPTER INSTALLATION 2 AND WIRING Contents of this Chapter... Ambient Conditions..............................2 2 Storage Conditions...............................2 2 Installation.....................................2

More information

FREQUENCY INVERTER VFR-013 QUICK START GUIDE

FREQUENCY INVERTER VFR-013 QUICK START GUIDE FREQUENCY INVERTER VFR-013 QUICK START GUIDE Inoréa Automation & Industry 9 rue du Lugan 33130 BEGLES www.inorea.com Table of contents 1. PEOPLE SAFETY... 3 2. MATERIAL SAFETY... 3 3. NAME PLATE... 4 a.

More information

TECHNICAL SPECIFICATION INVERTER VEGA DRIVE

TECHNICAL SPECIFICATION INVERTER VEGA DRIVE TECHNICAL SPECIFICATION INVERTER VEGA DRIVE ELETTRONICA SANTERNO Contents Overview 3 Features & selection guide 4/5 Data sheet 6/7 Wiring & connection terminals 8/9 Keypad & parameters navigation 10/11

More information

TOSVERT TM VF-nC3 Parameter List

TOSVERT TM VF-nC3 Parameter List TOSVERT TM VF-nC Parameter List E658664 - Setting information * Please fill it in if necessary. Item Content Item Content Setting date / person Customer Application Application model Motor manufacturer

More information

Operating Instructions

Operating Instructions 4XH35QB151210 Small General Frequency Converter Operating Instructions 220V 0.75KW 5.5KW 400V 0.75KW 15KW Please read the instruction carefully and understand the contents so that it can be installed and

More information

High performance multifunction quiet inverter INSTRUCTION MANUAL. SBT-0.75K/1.5K to SBT 22K/30K for general industry, fan and pump SBT-30K to 55K

High performance multifunction quiet inverter INSTRUCTION MANUAL. SBT-0.75K/1.5K to SBT 22K/30K for general industry, fan and pump SBT-30K to 55K High performance multifunction quiet inverter VVVF Inverter INSTRUCTION MANUAL 200 V systems SBT-0.75K/1.5K to SBT 22K/30K for general industry, fan and pump SBT-30K to 55K 400 V systems SHF-1.5K to SHF-250K

More information

THYFREC-VT230S 200V System 0.4 to 90kW 400V System 0.4 to 370kW INSTRUCTION MANUAL

THYFREC-VT230S 200V System 0.4 to 90kW 400V System 0.4 to 370kW INSTRUCTION MANUAL MEIDEN AC SPEED CONTROL EQUIPMENT THYFREC-VT230S 200V System 0.4 to 90kW 400V System 0.4 to 370kW INSTRUCTION MANUAL NOTICE 1. Read this manual thoroughly before using the VT230S, and store in a safe place

More information

9. RS485 Communication

9. RS485 Communication 9. RS485 The communication between inverter and external controller is doing by RS485 using modular connector in cling to inverter controller. Function Initial Minimum Maximum code Value Unit Description

More information

WARNING CAUTION. Fire Prevention. Electrical Shock Prevention. Damage Prevention

WARNING CAUTION. Fire Prevention. Electrical Shock Prevention. Damage Prevention ! WARNING! CAUTI Electrical Shock Prevention 1. Do not remove the front cover when input power is applied. Doing so can result in electric shock. 2. Do not operate the inverter with the front cover removed.

More information

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS CHAPTER 8 SUMMARY OF PARAMETER SETTINGS VFD-S Series!: The parameter can be set during operation, *: Twice the value for 460V class. Group 0 User Parameters Parameters Explanation s 0-00 Identity Code

More information

Troubleshooting Alarm Displays Warning Displays

Troubleshooting Alarm Displays Warning Displays 10 10.1 Alarm Displays............................................10-2 10.1.1 List of Alarms...................................................... 10-2 10.1.2 of Alarms............................................

More information

α α Retry count clear Alarm reset Active End of retry S-curve time during accelerati on H04: (Count) setting S curve time during decelerati on

α α Retry count clear Alarm reset Active End of retry S-curve time during accelerati on H04: (Count) setting S curve time during decelerati on Upon success of retry Alarm Occurrence Disappearance Time S-curve acceleration/deceleration To reduce the shock of the mechanical system, the change in the output frequency is made smooth when the frequency

More information

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS CHAPTER DESCRIPTION OF PARAMETER SETTINGS.1 Group 0: User Parameters 0-00 Identity Code of AC Drive Factory setting: d# Settings None V HP 1/4 1/2 1 2 3 11V/230V d0 d2 d4 d6 d8 460V -- -- -- d3 d d7 d9

More information

SYSDRIVE 3G3XV Inverter 3G3XV- -EV2 Operation Manual

SYSDRIVE 3G3XV Inverter 3G3XV- -EV2 Operation Manual SYSDRIVE 3G3XV Inverter 3G3XV- -EV2 Operation Manual Revised November 1997 iv Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes

More information

9. RS485 Communication (Option)

9. RS485 Communication (Option) 9. RS485 (Option) The communication between inverter and external controller is doing by RS485 using modular connector in cling to inverter controller. Function Initial Minimum Maximum code Value Unit

More information

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control NEW FIRMWARE MAKES SETUP A SNAP Application based commissioning allows parameters

More information

ADJUSTABLE SPEED DRIVES VF-S11 Sords Electric

ADJUSTABLE SPEED DRIVES VF-S11 Sords Electric ADJUSTABLE SPEED DRIVES VF-S11 The Next Generation of Micro Inverters is Here. The S11 provides maximum torque with precise speed control. It features an easy-to-use, quiet and compact design. In addition,

More information

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB DF5-... Frequency Inverters 1 st published 22, edition 02/02 Moeller GmbH, 53105 Bonn Author: Holger Friedrich Editor: Michael Kämper Translator: Dominik Kreuzer All brand and product names are trademarks

More information

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R INVERTER ROLL TO ROLL FUNCTION MANUAL FR-A820-00046(0.4K)-04750(90K)-R2R FR-A840-00023(0.4K)-06830(280K)-R2R FR-A842-07700(315K)-12120(500K)-R2R Roll to Roll Function The FR-A800-R2R inverter has dedicated

More information

ig5a Compact AC Drive 0.4~1.5kW(0.5~2HP) 1-phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 380~480Volts

ig5a Compact AC Drive 0.4~1.5kW(0.5~2HP) 1-phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 380~480Volts iga Compact AC Drive ~1.kW(0.~2HP) 1-phase 200~230Volts ~22kW(0.~30HP) 3-Phase 200~230Volts ~22kW(0.~30HP) 3-Phase 380~480Volts Drive STARVERT iga LS Starvert iga is very competitive in its price and shows

More information

SV9000 SVReady USER MANUAL CONTENTS OPEN SV9000 USER MANUAL. SV9000 Page 0-1

SV9000 SVReady USER MANUAL CONTENTS OPEN SV9000 USER MANUAL. SV9000 Page 0-1 SV9000 Page 0-1 SV9000 SVReady USER MANUAL CNTENTS A General...0-2 B Application selection...0-2 C Restoring default values of application parameters...0-2 D Language selection...0-2 1 Standard Control

More information

AF-3100α SERIES General-purpose High-performance Inverter Maintenance Manual

AF-3100α SERIES General-purpose High-performance Inverter Maintenance Manual AF-3100α SERIES General-purpose High-performance Inverter Maintenance Manual THE AVAILABLE SOLUTION, WORLDWIDE. AF-3100α SERIES Manual 00.000.00.000 INTRODUCTION Thank you for purchasing the SUMITOMO highperformance

More information

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz TAC ATV8, IP55 Variable Speed Drives for Asynchronous Motors. -phase. 80/460 V, 50-60 Hz E-60-24 24 May 2004 ATV 8 IP55 drives are specifically designed for pump and fan applications powered by a three-phase

More information

Foreword Thank you for purchasing the general-purpose VF series inverter produced by Panasonic Electric Works Automation Controls (Shanghai) Co., Ltd.

Foreword Thank you for purchasing the general-purpose VF series inverter produced by Panasonic Electric Works Automation Controls (Shanghai) Co., Ltd. Inverter VF Instruction Manual [Support model] Three phase 4V (.75kW3.7kW) Read this manual carefully before attempting to operate the inverter and store it for further reference. 8A3 645 7 2 Foreword

More information

ADVANCED AND EVER ADVANCING FR-V200. FR-V200 series

ADVANCED AND EVER ADVANCING FR-V200. FR-V200 series ADVANCED AND EVER ADVANCING FR-V200 FR-V200 series CONTENTS 1 SPECIFICATIONS 1 1.1 OPERATION PRINCIPLE...1 1.1.1 What is vector control?...1 1.2 Instructions for Using the Inverter...3 1.3 Specification

More information

General-Purpose AC Servo. MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING)

General-Purpose AC Servo. MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING) General-Purpose AC Servo MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING) D Safety Instructions Please read the instructions carefully before using the equipment. To use the equipment

More information

INSTRUCTION MANUAL (BASIC)

INSTRUCTION MANUAL (BASIC) TRANSISTORIZED INVERTER FR-S500 INSTRUCTION MANUAL (BASIC) FR-S540E-0.4K to 3.7K-EC FR-S520SE-0.2K to 1.5K-EC Thank you for choosing this Mitsubishi transistorized inverter. If this is the first time for

More information

Elettronica Santerno is responsible for the information contained in the original version of the Italian manual.

Elettronica Santerno is responsible for the information contained in the original version of the Italian manual. 15P0087B5 VEGA DRIVE SPACE VECTOR CONTROL UPD. 09/10/02 R. 01 English This manual is integrant and essential to the product. Carefully read the instructions contained herein as they provide important hints

More information

BACnet- MS/TP COMMUNICATION V

BACnet- MS/TP COMMUNICATION V - MS/TP COMMUNICATION V1.00.08.17 11.1 Introduction The VFD can be controlled and monitored through the BACnet MS/TP protocol over an RS-485 connection. The VFD operates as an MS/TP master device, which

More information

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class HITACHI L1-M Series Inverter Quick Reference Guide Single-phase Input 1V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB5741XD December 23 Caution: Be sure to read the L1 Inverter Manual

More information

About this Manual: Chapter 1 provides a summary of the Servo System and all gains used for the Servo System loops.

About this Manual: Chapter 1 provides a summary of the Servo System and all gains used for the Servo System loops. About this Manual: This guide describes the installation and startup procedures of the Servo System so that it can be efficiently put in actual operation in a short time. This guide provides detailed descriptions

More information

ig5a 0.4~1.5kW (0.5~2HP) 1phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 380~480Volts Compact & Powerful Drive

ig5a 0.4~1.5kW (0.5~2HP) 1phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 380~480Volts Compact & Powerful Drive Compact & Powerful Drive iga ~1.kW (0.~2HP) 1phase 200~230Volts ~22kW (0.~30HP) 3Phase 200~230Volts ~22kW (0.~30HP) 3Phase 380~480Volts Drive Starvert iga LS Starvert iga is very competitive in its price

More information

SAFETY INSTRUCTIONS. To prevent injury and property damage, follow these instructions during the installation and operation of the inverter.

SAFETY INSTRUCTIONS. To prevent injury and property damage, follow these instructions during the installation and operation of the inverter. Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS To prevent injury and property damage, follow these instructions during the installation and operation of the inverter. Incorrect

More information

BOSTON GEAR CONTROLLERS. ACE 20 Series 1/8 through 10 HP Adjustable Frequency AC Motor Controllers. MTY (81)

BOSTON GEAR CONTROLLERS. ACE 20 Series 1/8 through 10 HP Adjustable Frequency AC Motor Controllers. MTY (81) BOSTON GEAR CONTROLLERS ACE 20 Series 1/8 through 10 HP Adjustable Frequency AC Motor Controllers ACE 20 Series Offering full-featured control in high torque, low speed applications from 1/8 to 10 HP,

More information

This section is specifically about safety matters

This section is specifically about safety matters 6 4 ) 1 6 4 1 -, 1 8-4 6-4 1 6 4 7 + 6 1 ) 7 ) 4 ) 6 1-6 6-4. 4. 0 J E? A Thank you for choosing this Mitsubishi transistorized Inverter option. This instruction manual gives handling information and precautions

More information

Inverter Drive /Vector Drive Motors & Controls

Inverter Drive /Vector Drive Motors & Controls H2 Inverter/ Encoderless Vector Inverter Drive /Vector Drive & Controls 3/4 thru 50 180-264 VAC 3 Phase - 50/60 Hz 3/4 thru 60 340-528 VAC 3 Phase - 50/60 Hz 3/4 thru 60 515-660 VAC 3 Phase - 60 Hz HVAC

More information

FRN E1-4LM FRN E1-7LM

FRN E1-4LM FRN E1-7LM Application Elevator Only Special Specification Described Model FRN E1-2LM a FRN E1-4LM FRN E1-7LM a a Specifications for Description in this specification takes priority over catalogues, operation manuals

More information

SYSDRIVE 3G3HV Inverter Models The following 200- and 400-V class 3G3HV Inverter models are available.

SYSDRIVE 3G3HV Inverter Models The following 200- and 400-V class 3G3HV Inverter models are available. Function The 3G3HV High-capacity General-purpose Inverter is an easy-to-use inverter that has advanced features, such as PID control and energy-saving operations. SYSDRIVE 3G3HV Inverter Models The following

More information

INSTRUCTION MANUAL GENERAL-PURPOSE INVERTER R ADLEEPOWER

INSTRUCTION MANUAL GENERAL-PURPOSE INVERTER R ADLEEPOWER R ADLEEPOWER INSTRUCTION MANUAL GENERAL-PURPOSE INVERTER THANK YOU VERY MUCH FOR YOUR PURCHASE OF ADLEE INVERTER AS SERIES. PLEASE READ THIS INSTRUCTION MANUAL BEFORE INSTALLATION OF THE INVERTER. PREFACE

More information

INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+ VFD parameter list. A VFD parameter list is required when replacing a DELTA M+ VFD.

INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+ VFD parameter list. A VFD parameter list is required when replacing a DELTA M+ VFD. RYKO Manufacturing Company 116 N.W. 54th Ave. P.O.Box 38 Grimes, Iowa 5111 Phone (515) 986-37 www.ryko.com Fax (515) 986-3621 sales@ ryko.com INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+

More information

Product description. At a glance. Customer benefits

Product description. At a glance. Customer benefits Product description New series is a general current vector control inverter integrated with the performance and features in a high degree. with industry-leading drive performance and functionality control,

More information

General-Purpose AC Servo. MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING)

General-Purpose AC Servo. MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING) General-Purpose AC Servo MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING) F Safety Instructions Please read the instructions carefully before using the equipment. To use the equipment

More information

Troubleshooting Alarm Displays Warning Displays

Troubleshooting Alarm Displays Warning Displays 9 9.1 Alarm Displays..............................................9-2 9.1.1 List of Alarms........................................................ 9-2 9.1.2 of Alarms..............................................

More information

IC5 Series. LG Variable Frequency Drive 1/2-3 HP (230V) LG Industrial SystemsG. Installation, Operation and Maintenance Instruction

IC5 Series. LG Variable Frequency Drive 1/2-3 HP (230V) LG Industrial SystemsG. Installation, Operation and Maintenance Instruction LG Variable Frequency Drive IC5 Series GGGGGGG G G G G G G G G GGGGGGG 1/2-3 HP (230V) GGGGGGGGGGGGGGGGGGGGGGGG G G G G GGGGGGG G G Installation, Operation and Maintenance Instruction G G G G G G G G G

More information

HPVFP High Performance Full Function Vector Frequency Inverter

HPVFP High Performance Full Function Vector Frequency Inverter Advanced User Manual HPVFP High Performance Full Function Vector Frequency Inverter HP VER 1.00 1. HPVFP Parameter Set Overview...3 1.1. About this section...3 1.2. Parameter Structure Overview...3 1.3.

More information

THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE

THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE MEIDEN AC SPEED CONTROL EQUIPMENT THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE NOTICE 1. Read this manual thoroughly before using the VT110S, and store in

More information

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse ADJUSTABLE SPEED DRIVES W7 Series 18 Pulse Meets or Exceeds Your Specifications Standard Specifications Item Voltage Class 460V Maximum HP 60 75 100 125 150 200 250 300 400 500 600 700 800 Drive Rating

More information

USER MANUAL -Installation and Programming Instructions-

USER MANUAL -Installation and Programming Instructions- 15P0073B1 SERIES M VARIABLE FREQUENCY DRIVE FULL DIGITAL INVERTER USER MANUAL -Installation and Programming Instructions- Issued on 14/05/09 R.02 SW Ver. EU2.2 English This manual is integrant and essential

More information

Users Manual SM5 INVERTER. Subject to changes without notice December, 2001

Users Manual SM5 INVERTER. Subject to changes without notice December, 2001 Users Manual SM5 INVERTER Subject to changes without notice December, 2001 1 SM5 Contents 1. SAFETY... 3 1.1 Warnings...3 1.2 Safety Instructions...3 1.3 Earthing...4 1.4 Running The motor...4 2. RECEIVING...

More information

MagneTek. GPD 503 Technical Manual

MagneTek. GPD 503 Technical Manual MagneTek GPD 503 Technical Manual GPD 503 SIMPLIFIED START-UP PROCEDURE This procedure will quickly get you up and running by Digital Operator keypad or user supplied remote operator control. It assumes

More information

PE Electrical Machine / Power Electronics. Power Electronics Training System. ufeatures. } List of Experiments

PE Electrical Machine / Power Electronics. Power Electronics Training System. ufeatures. } List of Experiments Electrical Machine / Power Electronics PE-5000 Power Electronics Training System The PE-5000 Power Electronics Training System consists of 28 experimental modules, a three-phase squirrel cage motor, load,

More information

AF91 Adjustable Frequency Drives Series B

AF91 Adjustable Frequency Drives Series B Effective: January, 00 Page New Information AF9 Adjustable Model AF9 Description Model AF9 Adjustable Frequency AC Drives are designed to provide adjustable speed control of -phase motors. These microprocessor-based

More information

SAFETY INSTRUCTIONS. Always follow safety instructions to prevent accidents and potential hazards from occurring.

SAFETY INSTRUCTIONS. Always follow safety instructions to prevent accidents and potential hazards from occurring. 1 Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this manual, safety messages

More information

SANKEN ELECTRIC CO., LTD.

SANKEN ELECTRIC CO., LTD. NEW-CONCEPT TOP-CLASS INVERTERS FEATURING COMPACT DESIGN & LIGHT WEIGHT Actual Size SANKEN ELECTRIC CO., LTD. http://www.sanken-ele.co.jp/en/index.html Birth of the new SAMCO-e Series of inverters that

More information

Hitachi P1 Closed Loop Hoist Basic Instruc on Manual

Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Hitachi P1 Closed Loop Hoist Basic Instruc on Manual DH Firmware V.18 DETROIT HOIST AND CRANE LLC, CO. 6650 STERLING DRIVE NORTH STERLING HEIGHTS MICHIGAN 48312 Introduction This manual only applies to

More information

AC SPEED CONTROL EQUIPMENT. VAT2000 3ph 200V-230V System 0.4 to 45kW 3ph 380V-460V System 0.4 to 370kW INSTRUCTION MANUAL

AC SPEED CONTROL EQUIPMENT. VAT2000 3ph 200V-230V System 0.4 to 45kW 3ph 380V-460V System 0.4 to 370kW INSTRUCTION MANUAL GE Power Controls AC SPEED CONTROL EQUIPMENT VAT2000 3ph 200V-230V System 0.4 to 45kW 3ph 380V-460V System 0.4 to 370kW INSTRUCTION MANUAL --------------------------------- NOTICE ------------------------------------------

More information

Inverter. Speed Control Motors. Standard AC Motors A-195. Standard AC Motors Intro duction

Inverter. Speed Control Motors. Standard AC Motors A-195. Standard AC Motors Intro duction Standard AC Speed Control FE1/FE2 Standard AC Intro duction Induction Reversible Electromagnetic Brake Right-Angle Gearheads FE1/FE2 AC Speed Control Brake Pack SB5W US ES2 FE1/FE2 Watertight, Dust-Resistant

More information

WorldDrive General Purpose VFD The WDGP: Operation and Instructional Manual

WorldDrive General Purpose VFD The WDGP: Operation and Instructional Manual WorldDrive General Purpose VFD The WDGP: Operation and Instructional Manual WorldWide Electric Corp. 3540 Winton Place Rochester, NY 14623 Phone: (800) 808-2131 Fax: (800) 711-1616 www.worldwideelectric.net

More information

SAFETY INSTRUCTIONS. Always follow safety instructions to prevent accidents and potential hazards from occurring.

SAFETY INSTRUCTIONS. Always follow safety instructions to prevent accidents and potential hazards from occurring. Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this manual, safety messages are

More information

VFS9 Parameter List for Version110 or later

VFS9 Parameter List for Version110 or later VFS9 Parameter List for Version110 or later Setting Date Customer End user Application Application /Serial Inverter s Type-Form Quantity Inverter s Serial Motor s capacity If user s value is same as shipping

More information

Application Note: Replacing J300 with SJ300 Series Inverters

Application Note: Replacing J300 with SJ300 Series Inverters Application Note: Replacing J300 with SJ300 Series Inverters Please refer also to the SJ300 Inverter Instruction Manual AN101001-1 Hitachi America, Ltd. 2002 Hitachi America, Ltd. Chapter 1 Introduction

More information

AF-300 G11 Specifications. GE Industrial Systems. Product Specifications AF-300 G11

AF-300 G11 Specifications. GE Industrial Systems. Product Specifications AF-300 G11 apple GE Industrial Systems Product Specifications AF-300 G11 TM 1 Category Item Description Nominal Motor 230 VAC, 3 Phase 1/4 Hp to 125 Hp 460 VAC, 3 Phase 1/2 Hp to 450 Hp Braking Torque (Standard)

More information

SUPPLEMENTAL MANUAL COMPACT GENERAL-PURPOSE INVERTER (VOLTAGE VECTOR CONTROL)

SUPPLEMENTAL MANUAL COMPACT GENERAL-PURPOSE INVERTER (VOLTAGE VECTOR CONTROL) VS-66V7 Series SUPPLEMENTAL MANUAL COMPACT GENERAL-PURPOSE INVERTER (VOLTAGE VECTOR CONTROL) Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for

More information

General-Purpose AC Servo. MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING)

General-Purpose AC Servo. MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING) General-Purpose AC Servo MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING) B Safety Instructions Please read the instructions carefully before using the equipment. To use the equipment

More information