IBD23 CURTAIN TYPE STATIC FIRE DAMPERS 3 HOUR UL555 RATED FOR USE IN STATIC SYSTEMS
|
|
- Lee Oliver
- 5 years ago
- Views:
Transcription
1 3900 Dr. Greaves Rd. Kansas City, MO (816) FX (816) ID23 CURTIN TYPE STTIC FIRE DMPERS 3 OUR UL555 RTED FOR USE IN STTIC SYSTEMS pplication Ruskin Model ID23 3 hour UL classified static (fans off) curtain style fire damper for use in VC systems that shut down during a fire event. Fire dampers used for the protection of openings in walls, partitions, or masonry floors with fire resistance ratings of 3 hours or more and shall have a 3 hour fire protection rating. The ID23 can be installed vertically in walls or horizontally in masonry floors and is rated for airflow in either direction. STNDRD CONSTRUCTION FRME ND LDES MTERIL Galvanized steel (in gauges required by UL listing R-5531). CLOSURE springs (horizontal mount only) 301 stainless steel constant force type. FUSILE LINK 165 F (74 C) is standard. 212 F (100 C) optional. damper sizes See pages 2-5 for minimum and maximum UL sizes. See page 6-9 for construction details on multiple section assemblies. OPTIONS FM pprovals as Specification Tested Product SP200 Switch Package to allow remote indication of damper blade position PFM ngles factory supplied two-side installation. Other angles of various sizes and gauges for two-side installation Factory s of various lengths and gauges to insure field compliance with UL installation requirements MCP Control panels for monitoring purpose ccess Door factory mounted access door in common sleeve. Models ID23 series meet the requirements for fire dampers established by: National Fire Protection ssociation NFP Stand ards 80, 90, 92, 92, and 101 ICC International uilding Codes CSFM California State Fire Marshal ID23 # :0004 New York City ME M UL CLSSIFIED UL555 Listing R5531 SEE COMPLETE MRKING ON PRODUCT FM pprovals Specification Tested Product (Option) Notes: 1. Dimensions shown in parentheses ( ) indicate millimeters. 2. Single section dampers ordered with either 12" (305), 14" (356) or 16 (406) long sleeve; the ID230, 430 and 630 models may be substituted. Spec ID23-114/New LL STTED SPECIFICTIONS RE SUJECT TO CNGE WITOUT NOTICE OR OLIGTION. Ruskin 2014
2 DMPER STYLES ND SIZES Style Frame and blades in air stream optional 75-85% free area Vertical Installation 4"w x 4"h (102 x 102) orizontal Installation 6"w x 6"h (152 x 152) Vertical Installation 36"w x 36"h (914 x 914) orizontal Installation 30"w x 45 1 /2"h (762 x 1156) Multiple Section ssembly Vertical Installation 90"w x 72"h (2286 x 1829) orizontal Installation 90"w x 9h (2286 x 2311) 4 1 /2" (114) 6" (152) Min. Style w/o Style w/ Style lades out of air stream optional 80-90% free area Vertical Installation 4"w x 4"h (102 x 102) orizontal Installation 6"w x 4"h (152 x 102) Vertical Installation 36"w x 32"h (914 x 813) orizontal Installation 30"w x 40"h (762 x 1016) Multiple Section ssembly Vertical Installation 90"w x 68"h (2286 x 1727) orizontal Installation 90"w x 8h (2286 x 2057) 4 1 /2" (114) 3/4" (19) = Duct Width = Duct eight = Overall Damper eight Style w/o Style w/ C Style lades out of air stream Fully welded sleeve required 80-90% free area Vertical Installation 4"w x 4"h (102 x 102) orizontal Installation 6"w x 4"h (152 x 102) Vertical Installation 36"w x 32"h (914 x 813) orizontal Installation 30"w x 40"h (762 x 1016) Multiple Section ssembly Vertical Installation 90"w x 68"h (2286 x 1727) orizontal Installation 90"w x 8h (2286 x 2057) 10" (254) Min. 2 1 /2" (64) 5" (127) Min. 10" (254) Min. = Duct Width = Duct eight = Overall Damper eight C Style w/
3 DMPER STYLES ND SIZES C and WC Style Square or Rectangle Transition Frame and blades out of air stream required % free area C Style sealed assembly WC Style fully welded Vertical or orizontal Installation 4"w x 4"h (102 x 102) Vertical Installation 34"w x 3h (864 x 787) orizontal Installation 28"w x 39"h (711 x 991) Multiple Section ssembly Vertical Installation 88"w x 67"h (2235 x 1702) orizontal Installation 88"w x 8h (2235 x 2057) + 2" C Style w/ 1 1 /2" (38) = Duct Width = Duct eight = Overall Damper eight + 2" 1. Style C duct connection extends 1 1 /2" (38) beyond the sleeve. 2. Style WC duct connection extends beyond the sleeve. WC Style w/ CR and WR Style Round Transition Frame and blades out of air stream required % free area CR Style sealed assembly WR Style fully welded Vertical or orizontal Installation 4" diameter (102) Vertical or orizontal Installation 3 diameter (787) orizontal Installation 28" diameter (711) Multiple Section ssembly Vertical Installation 67" diameter (1702) orizontal Installation 8 diameter (2057) CR Style 1 1 /2" (38) D = = Overall Damper eight 1. Style CR duct connection extends 1 1 /2" (38) beyond the sleeve. 2. Style WC duct connection extends beyond the sleeve. 3. Transition collars to be sealed (y Others). WR Style
4 DMPER STYLES ND SIZES CO and WO Style Oval Transition Frame and blades out of air stream required % free area CO Style sealed assembly WO Style fully welded Vertical or orizontal Installation 4"w x 4"h (102 x 102) Vertical Installation 34"w x 3h (864 x 787) orizontal Installation 28"w x 39"h (711 x 991) Multiple Section ssembly Vertical Installation 88 w x 67 h (2235 x 1702) orizontal Installation 88"w x 8h (2235 x 2057) = Duct Width = Duct eight = Overall Damper eight 1. Style CO duct connection extends 1 1 /2" (38) beyond the sleeve. 2. Style WO duct connection extends beyond the sleeve. 3. Transition collars to be sealed (y Others). + 2" + 2" CO Style WO Style 1 1 /2" (38) 1 1 /2" (38) LR Style Round Transition Round enclosure - frame and blades out of air stream optional non-sealed assembly % free area Vertical or orizontal Installation 4" diameter (102) Vertical Installation 3 diameter (787) orizontal Installation 28" diameter (711) Multiple Section ssemblies Not available in style LR. See Style CR for larger assemblies D = = Overall Damper eight LR Style Without 1. Style LR without sleeves the duct connection extends beyond the damper. 2. Style LR with sleeves the duct connection extends 1 1 /2" (38) beyond the sleeve. 3. Transitions and collars to be sealed in the field (y Others). 12"(305) Min. 12" (305) Min. LR Style w/ vailable with 12" (305), 14" (356) or 16" (406) long sleeves 1 1 /2" (38)
5 DMPER STYLES ND SIZES LO Style Oval Transition Frame and blades out of air stream optional non-sealed assembly % free area Vertical or orizontal Installation 4"w x 4"h (102 x 102) Vertical Installation 34"w x 3h (864 x 787) orizontal Installation 28"w x 39"h (711 x 991) Multiple Section ssemblies Not available in Style LO. See Style CO for larger assemblies + 2" = Duct Width = Duct eight = Overall Damper eight LO Style Without 1. Style LO without sleeves the duct connection extends beyond the damper. 2. Style LO with sleeves the duct connection extends 1 1 /2" (38) beyond the sleeve. 3. Transitions and collars to be sealed in the field (y Others). + 2" 12" (305) Min. 12" (305) Min. LO Style w/ vailable with 12" (305), 14" (356) or 16" (406) long sleeves 1 1 /2" (38) R Style Round Transition Round enclosure. lades partially in the air stream optional non-sealed assembly 85-95% free area Vertical or orizontal Installation 4" diameter (102) Vertical Installation 34" diameter (864) orizontal Installation 28" diameter (711) Multiple Section ssemblies Not available in Style R. See Style CR for larger assemblies R Style D = = Overall Damper eight 12" (305) Min. 1. Style R without sleeves the duct connection extends beyond the damper. 2. Style R with sleeves the duct connection extends 1 1 /2" (38) beyond the sleeve. 3. Transitions and collars to be sealed in the field (y Others). 12" (305) Min. 1 1 /2" (38) R Style w/ vailable with 12" (305), 14" (356) or 16" (406) long sleeves
6 SSEMLY ND DIMENSIONL INFORMTION Dampers normally fabricated approximately 1 /4" (6) less than given duct dimensions. (width) and (height) dimensions shown describe maximum UL Classified sizes. Multiple section damper assemblies ordered without sleeves are shipped in individual sections, for field assembly. Multiple section dampers ordered with factory furnished sleeves are normally shipped in complete assemblies, ID23 STYLE DMPERS vertical installation 'X' LDE STCK DIMENSION '' Damper eight 14" (102) thru 12" (305) 11/2" (39) 13" (331) thru 16" (407) 17" (432) thru 23" (585) 24" (610) thru 29" (737) 3" (77) 36" Max (914) 72" Max (1829) 30" (762) thru 33" (839) 3 1 /2" (89) 34" (864) thru 38" (966) 4" (102) 37" (940) thru 46" (1168) 47" (1194) thru 58" (1473) 59" (1499) thru 66" (1676) 3" (77) 3 1 /2" (89) 36" Max (914) 67" (1702) thru 72" (1829) 4" (102) 90" Max (2286) 'X' ORIZONTL installation 'X' LDE STCK DIMENSION '' Damper eight 16" (152) thru 12" (305) 1 1 /2" (39) 13" (331) thru 18" (457) 45 1 /2" Max. (1156) 30" Max (762) 19" (483) thru 23" (585) 24" (610) thru 29" (737) 30" (762) thru 33" (839) 34" (864) thru 38" (966) 39" (991) thru 44" (1118) 3" (77) 3 1 /2" (89) 4" (102) 4 1 /2" (115) 45" (1143) 5" (127) Two section high 9 Max (2311) 90" Max (2286) 'X' LDE STCK DIMENSION '' Damper eight 46" (1168) 47" (1194) thru 58" (1473) 59" (1499) thru 66" (1676) 67" (1702) thru 80" (2032) 8 (2057) thru 88" (2235) 5" (127) 6" (153) 7" (178) 8" (203) 9" (228) 89" (2261) thru 9 (2311) 9 1 /2" (241) 'X' dimension is the total for two sections high
7 SSEMLY ND DIMENSIONL INFORMTION and C style dampers vertical installation '' Damper eight 36" Max (914) 33" (76) thru 12" (305) 1 3 /4" (44) 13" (331) thru 22" (559) 23" (585) thru 32" (813) 33" (839) thru 46" (1168) 47" (1194) thru 68" (1727) 32" Max (813) 68" Max (1727) 'X' dim. + '' dim. = '' dim. 90" Max (2286) 'X' ORIZONTL installation '' Damper eight 33" (76) thru 12" (305) 13" (331) thru 22" (559) 23" (585) thru 32" (838) 33" (839) thru 40" (1016) 1 3 /4" (44) 4 3 /4" (121) 40" Max (1016) 30" Max (762) 'X' dim. + '' dim. = '' dim. two section high '' Damper eight 4 (1041) thru 45" (1143) 5 1 /2" (140) 46" (1168) thru 64" (1626) 7 1 /2" (191) 65" (1651) thru 8 (2057) 9 1 /2" (241) 'X' dim. + '' dim. = '' dim. 8 Max (2057) 90" Max (2286)
8 SSEMLY ND DIMENSIONL INFORMTION C, WC, CO, WO and LO style dampers vertical installation '' Damper eight " (76) thru 1 (279) 12" (305) thru 2 (533) 22" (559) thru 3 (787) 32" (838) thru 45" (1143) 4 3 /4" (121) 3 Max (787) 67" Max (1702) 46" (1168) thru 67" (1702) 4 3 /4" (121) 'X' dim. + '' dim. = '' dim. LO Style is limited to single section only. 34" Max (864) Typical Style C and WC 88" Max (2235) + 3 Max (787) 34" Max (864) Typical Style CO, WO and LO Construction '' Damper eight 33" (76) thru 1 (279) 12" (305) thru 2 (533) 22" (559) thru 3 (787) 4 3 /4" (121) 32" (838) thru 39" (991) 5 3 /4" (146) 'X' dim. + '' dim. = '' dim. two section high '' Damper eight 40" (1016) thru 45" (1143) 5 1 /2" (140) 46" (1168) thru 64" (1626) 7 1 /2" (191) 65" (1651) thru 8 (2057) 9 1 /2" (241) 'X' dim. + '' dim. = '' dim. ORIZONTL installation 28" Max (711) + 36" Max (965) 39" Max (991) 8 Max (2057) + Typical Style CO and WO Construction 3 Max (787) 88" Max (2235) + Typical Style CO, WO and LO Construction
9 SSEMLY ND DIMENSIONL INFORMTION CR, WR and LR style dampers vertical installation '' dimension 33" (76) thru 1 (279) 12" (305) thru 2 (533) 22" (559) thru 3 (787) 4 3 /4" (121) 'X' dim. + '' dim. = '' dim. LR Style is limited to single section only. TWO section high '' dimension 332" (838) thru 45" (1143) 46" (1168) thru 67" (1702) 4 3 /4" (121) 'X' dim. + '' dim. = '' dim. Dia. 34" Max (864) Dia. 67" Max (1702) ORIZONTL installation '' dimension 33" (76) thru 1 (279) 12" (305) thru 2 (533) 22" (559) thru 3 (787) 4 3 /4" (121) 32" (838) thru 39" (991) 5 3 /4" (146) 'X' dim. + '' dim. = '' dim. two section high '' dimension 40" (1016) thru 45" (1143) 5 1 /2" (140) 46" (1168) thru 64" (1626) 7 1 /2" (191) 65" (1651) thru 8 (2057) 9 1 /2" (241) 'X' dim. + '' dim. = '' dim. Dia. 8 Max. (2057) Dia. 28" Max. (711)
10 SSEMLY ND DIMENSIONL INFORMTION R style dampers vertical OR ORIZONTL installation Dia. 28" Max. (711) 34" Max (864) Vertical orizontal suggested specification Furnish and install at locations shown on plans, static fire dampers tested, constructed and labeled in accordance with the last edition of UL standard 555. Dampers shall have a fire of 3 hours and shall meet the requirements of the latest edition of NFP90. Curtain type fire dampers suitable for vertical wall or partitions; and horizontal (masonry floor/ceiling) with a fire resistance rating of 3 hours and greater. Fire Dampers shall be produced in an ISO 9001 certified factory. Damper frame and blades shall be galvanized steel in gauges required by UL listing R-5531 installed in a factory mounted sleeve and shipped loose mounting angles. Damper blades shall be steel interlock to provide fire shield in gauges required by UL listing R Closure springs on horizontal mounted dampers shall be of 301 stainless steel and shall be constant force type. Each fire damper shall have a 3 hour fire protection rating and shall be supplied with a 165 F (74 C) or 212 F (100 C) fusible link. Damper shall be installed in static (fan off) systems only. Submittal information shall include the fire protection rating and manufacturer s UL installation instruction. Optional FM pprovals Specification Each fire damper shall be listed in Factory Mutual (FM) pprovals Specification Tested Product and labeled accordingly. Static fire dampers shall be Ruskin model ID23. (Consult for electronic version of this Quick spec as well as for complete 3- part CSI MasterFormat Specifications) Dr. Greaves Rd. Kansas City, MO (816) FX (816) Printed on recycled paper using vegetable based inks
DIBD20, 40, 60 AND DIBD230, 430, 630 CURTAIN TYPE DYNAMIC FIRE DAMPERS
00 Dr. Greaves Rd. Kansas City, MO 00 (1) 1- F (1) - DID, 0, 0 ND DID0, 0, 0 CURTIN TYPE DYNMIC FIRE DMPERS 1 1 / ND OUR UL RTED FOR USE IN DYNMIC ND STTIC SYSTEMS PPLICTION DID, 0, 0 fire dampers can
More informationDIBD2 and DIBD23 CURTAIN TYPE DYNAMIC FIRE DAMPERS 1 1 /2 AND 3 HOUR UL555 RATED FOR USE IN DYNAMIC AND STATIC SYSTEMS
00 r. Greaves Rd. Kansas City, MO 00 (1) 1- F (1) - I and I CURTIN TYPE YNMIC FIRE MPERS 1 1 / N OUR UL RTE FOR USE IN YNMIC N STTIC SYSTEMS PPLICTION I fire dampers can be installed vertically in walls
More informationHALDEMAN, INC. BRAND: RUSKIN. Fire Dampers. IBD20 Deduct 1/4 Inch. Model:
LEMN, INC. REPS v.. RN: RUSKIN Fire ampers Model: FRME: MOUNTING: FUSELINK TEMP: SLEEVE/TRNS: SLEEVE LENGT: SLEEVE GUGE: SLV MTERIL: MOUNTING NGLES: NGLE IM/G: I0 educt / Inch STYLE VERTICL EGREES SLEEVE
More informationModel ABV Pressure Independent Automatic Balancing Valve. Application: Standard Construction: Performance: Configurations Available:
Application: Tag: Project: Location: Date: Engineer: Contractor: Architect: Submitted by: The ABV Automatic maintains a constant airflow volume in HVAC applications. The highly engineered damper blade
More informationDocument Number ODFD-XXX and OFD-XXX Series Installation Drawings for Out of Wall Curtain Fire Dampers
Document Number 481329 ODFD-XXX and OFD-XXX Series Installation Drawings for Out of Wall Curtain Fire s Approved installations for curtain fire dampers 1) Through the grille access and 2) Installation
More informationPart No. Thread Size B Design Load Approx. Wt./100 A in. (mm) Lbs. (kn) Lbs. (kg)
ttachments Fig. 3199R - eiling Flange Fig. 3199RT - eiling Flange ura-opper oated Size Range: 3 /8"-16 & 1 /2"-13 rod Material: Malleable Iron (Stainless Steel Type 304 available) Standard 3199RT is UR-OPPER
More informationB3199R - Ceiling Flange B3199RCT - Ceiling Flange Dura-Copper Coated. TOLCO Fig All Steel Ceiling Plate. 216 Eaton
ttachments 3199R - eiling Flange 3199RT - eiling Flange ura-opper oated Size Range: 3 /8"-16 & 1 /2"-13 rod Material: Malleable Iron (Stainless Steel Type 304 available) Standard 3199RT is UR-OPPER coated
More informationSubmittal Sheet COUNTERSUNK HOLES SDG SPIRAL DUCT GRILLE 1 7/8" (47) + 1 1/4" (32) - 3/4" (19) ( DUCT OPENING ) END GASKET NOM. LENGTH - 3/4" (19) OPTIONAL AIR SCOOP AIR SCOOP (ROD OPERATOR) NOM. LENGTH
More informationDuctwork Controls and Instrumentation Outlets (HVAC) HVAC Control System.
SECTION 15910 DUCT ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15890 - Ductwork. 2. 15900 - Controls and Instrumentation. 3. 15940 - Outlets (HVAC). 4. 15970 - HVAC Control System.
More informationEngineering Services Program
GDR41 1214 Product Evaluation Engineering Services Program The following product has been evaluated for compliance with the wind loads specified in the International Residential Code (IRC) and the International
More informationHVAC Spiral Pipe Component Parts
VC piral Pipe Component Parts Yellow label union manufacturer of VC piral Pipe component parts tamped Fittings VC component parts will save you time and money on your next spiral pipe job. In a market
More informationCOMMERCIAL KITCHEN HOOD WORKSHEET/ CHECKLIST
COMMERCIAL KITCHEN HOOD WORKSHEET/ CHECKLIST Two copies of this worksheet/checklist must accompany plans sets submitted with commercial kitchen application. The applicant is responsible for assuring the
More informationLOW PRESSURE STEEL DUCTWORK Mechanical Systems Insulation Outlets (HVAC) Testing and Balancing.
SECTION 15841 LOW PRESSURE STEEL DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15180 - Mechanical Systems Insulation. 2. 15940 - Outlets (HVAC). 3. 15991 - Testing and Balancing. 1.02 SUBMITTALS
More informationPRESTON HEALTH SERVICES ARCHITECT S NO. 2700
SECTION 23 3113 - LOW PRESSURE DUCTWORK PART 1 - GENERAL 1.1 SCOPE OF WORK: A. The work required under this section includes all work necessary for a complete installation of ductwork and accessories.
More informationMax. Rec. Load. Wt. Per Inch lbs. kn lbs. kn lbs. kg. Wt. Per Inch lbs. kn lbs. kn lbs. kg 750 F (399 C)
FIG. 10 FIG. 15 & 15L Function: Designed for use in pipe hanger assemblies. (Type 304 or 316 Stainless Steel upon request) Ordering: Specify figure number, rod size, length (), material, and finish. 650
More informationLINEAR DIFFUSERS AND BAR GRILLES
Model 49-240 Model 48LL1 Model 49-280 Model 49-480 Model 48LL2 Linear ar Grilles The Nailor 4900 Series provides an extruded aluminum bar grille that offers beautiful styling and efficient performance.
More informationA. Radius elbows with a construction radius of 1.5 the duct width are preferred to square elbows.
SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insulation shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation
More informationFIRE RATED DOOR AND FRAME GENERAL REQUIREMENTS
` FIRE RATED DOOR AND FRAME GENERAL REQUIREMENTS These requirements apply to all fire rated doors, frames, and windows. Requirements for the installation of these assemblies are included in the Standard
More informationB. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.
SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.
More informationROCKFORD PROCESS CONTROL, INC.
esigners and Manufacturers of Institutional asework Hardware ROKFOR PROESS ONTROL, IN. 2020 Seventh Street Rockford, IL 61104 Phone: 815-966-2000 Fax: 815-966-2026 sales@rockfordprocess.com www.rockfordprocess.com
More informationSECTION SWINGING AUTOMATIC ENTRANCES IN-GROUND, AUTOMATIC SWING DOOR OPERATOR CONVERTER ADAPTED TO BROOKFIELD NB-500 EXTREME DUTY OPERATOR
SECTION 084229.33 SWINGING AUTOMATIC ENTRANCES IN-GROUND, AUTOMATIC SWING DOOR OPERATOR CONVERTER ADAPTED TO BROOKFIELD NB-500 EXTREME DUTY OPERATOR PART 1-GENERAL 1.01 DESCRIPTION A. This section describes
More informationSECTION BULLET- RESISTANT DOORS
1 SECTION 08 3950 BULLET- RESISTANT DOORS PART 1- GENERAL 1.01 SUMMARY A. This Section Includes: 1. Bullet- resistant steel door and frame systems. 2. Door hardware for bullet- resistant steel door and
More informationTHIS PAGE INTENTIONALLY LEFT BLANK
THIS PAGE INTENTIONALLY LEFT BLANK Seamed Edge Doors 1000 Series 16 and 18 Gauge Doors Cold Rolled or Galvanized Steel Tight Corner Seam Full Body Polystyrene Core or Honeycomb Core Non-Handed Design 12-Gauge
More informationThe General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.
SECTION 15800! AIR DISTRIBUTION PART 1! GENERAL 1.01 RELATED DOCUMENTS The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this
More informationModel LF2500 Low Frequency Sound Silencer
Model LF Low Frequency Sound Silencer The SEMCO Model LF low frequency sound silencers are specifically designed to solve noise problems in the lower frequency range and will provide excellent low band
More informationModel 30/L/0. Model 30/S/0. Shortl Blades, 0 Deflection 3/4" Spacing. Model 35/S/0 Short Blades, 0 Deflection 1/2" Spacing
model 30 / 35 - Steel Return Grilles & Registers 0 Deflection 0 fixed blade deflection maximizes free area for low pressure loss and sound levels Potential line of sight into duct thru grille is acceptable
More informationFIRE RATED DOOR AND FRAME GENERAL REQUIREMENTS
FIRE RATED DOOR AND FRAME GENERAL REQUIREMENTS These requirements apply to all fire rated doors, frames, and windows. Requirements for the installation of these assemblies are included in the Standard
More informationFLOWLINE LINEAR DIFFUSERS
FLOWLINE LINER DIFFUSERS 1 FLOWLINE LINER DIFFUSERS Contents Overview of FlowLine System Continuous FlowLine Linear FL Series orizontal igh Throw Pattern Controllers FLV Series Vertical Jet Throw Pattern
More informationThe General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.
SECTION 23 31 13 METAL HVAC DUCTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in
More informationTable of Contents F Series Frames
Table of Contents F Series Frames How to Order Frames... F 1 F Series Spec Sheet... F 2 F Series Profiles 1 of 6... F 3 F Series Profiles 2 of 6... F 4 F Series Profiles 3 of 6... F 5 F Series Profiles
More informationB. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.
SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.
More informationREVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty
HOT AISLE CONTAINMENT SYSTEM (HACS) REVISION #1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. C. Drawings and general provisions of the Contract, including General and Supplementary. Conditions apply to
More informationSPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK
SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK PART 1.0 GENERAL 1.1 SCOPE A. This specification contains the minimum requirements for the design, manufacture and testing of a UL listed,
More informationSt. Monica Food Pantry
St. Monica Food Pantry 23 3300-1 HVAC WORK DIVISION 23 SECTION 233300 HVAC AIR DUCT ACCESSORIES PART 1. GENERAL 1.1 WORK INCLUDES A. Gravity Operated Backdraft Dampers B. Volume dampers C. Motor operated
More informationInstallation and Maintenance Manual
Installation and Maintenance Manual IM770 Group: pplied ir Part Number: IM770 Date: pril 2003 Roof Curb for Skyline TM Outdoor ir Handlers 2013 Daikin pplied IM 770 Page 1 Table of Contents General Description...
More informationFLUOROPOLYMER COATED DUCT FOR CAUSTIC ENVIRONMENTS
DIVISION 23 FLUOROPOLYMER COATED DUCT FOR CAUSTIC ENVIRONMENTS Part I General 1.1 Related Documents A. All terms and general provisions of contract, General and Supplementary Conditions, and Specification
More informationCARTRIDGE-STYLE RECOVERY POWDER BOOTH
CARTRIDGE-STYLE RECOVERY POWDER BOOT Environmentally Safe Cartridge-Style Recovery Powder Booths exceed safety and code requirements NFPA-33, IFC to protect those that work in any industrial spray environment,
More informationINSTALLATION INSTRUCTIONS FOR CECO DOOR FLOOD RESISTANT DOOR AND FRAME ASSEMBLIES
INSTLLTION INSTRUCTIONS FOR CECO DOOR FLOOD RESISTNT DOOR ND FRME SSEMBLIES GENERL The installation of flood resistant door and frame assemblies differs significantly from that of standard door and frame
More informationZone Control Unit (ZCU) Solution
Description The Zone Control Unit (ZCU) is a VAV turnkey solution. It is an applied equipment-controls package that is preengineered and factory-fabricated, to dramatically reduce field installed equipment
More informationCompliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)
Typical Specification 1.2kV Class Energy Efficient Dry-Type Distribution Transformers Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016) Canada 595 Southgate Drive Guelph, Ontario N1G
More informationContemporary Collection
HZ5E Gas Fireplace Model HZ5E-NG1 HZ5E-LP1 Fuel Type Natural Gas Propane Gas Minimum Supply Pressure 5 W.C.(1.5 kpa) 1 W.C. (.98 kpa) Manifold Pressure - High 3.5 W.C. (.87 kpa) 1 W.C. (.9 kpa) Manifold
More informationMISCELLANEOUS SIGN CONNECTION DETAILS TYPICAL ROUTE MARKER ASSEMBLIES SIGN TO POST MICHIGAN DEPARTMENT OF TRANSPORTATION
5-4" SEE DETAIL I COUPLING BAR ON 3 2-10" CANTILEVER SIGN SUPPORT TYPICAL ROUTE MARKER ASSEMBLIES 5/1 DIAMETER STAINLESS STEEL BOLT AND NYLON INSERT LOCK NUT SELF-ALIGNING STEEL REINFORCING PLATE ( TYPE
More informationWalz & Krenzer, Inc.
08 39 19/WAL BuyLine 9365 Walz & Krenzer, Inc. Watertight Door and Window Watertight Hatch Removable Lip Seal Flood Barrier System 3 Lip Seal Gasket Flood Barriers Flood Barriers and Watertight Closures
More informationSECTION MECHANICAL IDENTIFICATION
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. B. Related Sections:
More information*************************************************************************************************************
15890 DUCTWORK ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 23 33 13 *************************************************************************************************************
More informationLABEL & RATING OPTIONS
LABEL & RATING OPTIONS FIRE LABELING GUIDELINES APPLICATION MAXIMUM SIZE HOURLY RATING Single Door 4'0" wide x 10'0" high Up to 3 hour 4'3" wide x 10'0" high Up to 1-1/2 hour Pair 8'0" wide x 10'0" high
More informationMichigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE
PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationAPPENDIX A, UMC STANDARD 6-5 STANDARD FOR INSTALLATION OF FACTORY-MADE AIR DUCTS
STANDARD FOR INSTALLATION OF FACTORY-MADE AIR DUCTS Sealing of fibrous glass duct board to the sheet metal sleeve must be made with glass fabric and mastic, except where operating pressure is less than
More informationTECHNICAL DATA SHEET STANDARD STEEL FRAMES SPECIFICATIONS MESKER STANDARD STEEL FRAMES
DS-201-1 STANDARD STEEL FRAMES SPECIFICATIONS STANDARD STEEL FRAMES 1. Frames shall be manufactured by Mesker Door Incorporated and designated as F-416 (16 GA) or F-414 (14 GA) for 1 3/4 doors, F-412 for
More informationSECTION WOOD AND PLASTIC DOORS. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.
SECTION 081416 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting
More informationAMDL - Aluminum Linear Louver Face Diffuser Submittal Sheet OVERALL DIFFUSER = NOM. + 5.750 (146) NECK OVERALL = NOM. -.125 (3) NOM. DCUT OVERALL DIFFUSER = NOM. + 5.750 (146) 2.094 (53) TYPE 1 SURFACE
More informationZone Control Unit (ZCU) VAV Turnkey Solution
Description The Zone Control Unit (ZCU) is a VAV turnkey solution. It is an applied equipment-controls package that is pre-engineered and factory-fabricated, to dramatically reduce field installed equipment
More informationGRILLE AND REGISTER OPTIONS AND ACCESSORIES
GRILLE ND REGISTER OPTIONS ND CCESSORIES PRODUCT OVERVIEW OPTIONS ND CCESSORIES FOR FSTENING ND MOUNTING FRMES Up to four methods of fastening available for most models. Sub-frame available for professionally
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 SUBMITTALS A.
More informationSECTION PANELBOARDS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section
More informationB. Bidders shall acknowledge receipt of this Addendum in writing on his Proposal Form.
McKee and Associates Architecture and Interior Design Addendum No. THREE Date: 12.11.17 Project: A NEW BUILDING FOR THE GREATER LIMESTONE COUNTY CHAMBER OF COMMERCE ATHENS, ALABAMA A3.1 GENERAL PROJECT
More informationWALL HI-OUTPUT. Project. Type. Notes
Project Type Notes PERFORMANCE/LINEAR FT AT 3000K AND 3500K NOMINAL LUMEN OUTPUT INPUT WATTS* EFFICACY* 3 9/16 700 lm/ft 7.3 W/ft 96 lm/w 900 lm/ft 9.8 W/ft 92 lm/w 1100 lm/ft 12.5 W/ft 88 lm/w 1 5/8"
More informationBike Locker Model DBL1 & DBL2
Bike Locker Model DBL1 & DBL2 DBL1 & DBL2 are constructed of 99% recycled steel and is available in 20 standard powder coat colors or a galvanized finish. DBL1 & DBL2 store 1 or 2 bikes effortlessly and
More informationSECTION GARBAGE CHUTE. Wilkinson Chutes Canada Toronto, Ontario, CANADA
Version 00 WILKINSON HUTES ANADA PAGE OF This section is based on a system produced by: Part GENERAL RELATED DOUMENTS - GARAGE HUTE Wilkinson hutes anada Toronto, Ontario, ANADA -- A The general provisions
More informationBrown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS
SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600
More informationInstallation Instructions. 45 and 60-Minute Positive Pressure Fire-Rated Veneered Door Frame UBC & UL-10C
Wood Doors Installation Instructions 45 and 60-Minute Positive Pressure Fire-Rated Veneered Door Frame UBC 7-2-1997 & UL-10C Positive Pressure Category Requirements: Category C The Maiman Company Fire
More informationCEILING HI-OUTPUT. Project. Type. Notes
Project Type Notes PERFORMANCE/LINEAR FT AT 3000K AND 3500K NOMINAL LUMEN OUTPUT INPUT WATTS* EFFICACY* 3 9/16 700 lm/ft 7.9 W/ft 89 lm/w 900 lm/ft 10.6 W/ft 85 lm/w 1100 lm/ft 13.5 W/ft 81 lm/w 1 5/8"
More informationB. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.
SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section includes standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.
More informationGE Monogram 36" Built-In Bottom-freezer Refrigerator
SECTION 1 FLUSH INSET INSTLLTION SECTION 2 STNDRD INSTLLTION 1/4" FRMED PNELS 3/4" OVERLY PNELS OVERLL DIMENSIONS FLUSH INSET INSTLLTION 38" (96.5) 25 7/8" (65.7) 20 5/8" (52.4) 9 5/8" (24.4) * 8 (212.1)
More informationMR Modulo Adjustable Constant Airflow Regulator
& ZONE CONTROLS Adjustable Constant Airflow Regulator PRODUCT SPECIFICATIONS & TECHNICAL DATA Construction 5 4 1 GENERAL The model Adjustable Constant Airflow Regulator is a modulating orifice that automatically
More informationInstruction. MI October I/A Series Models 83.-D and -T Vortex Flowmeter Intrinsic Safety Connection Diagrams
Instruction MI 019-175 October 2000 I/A Series Models 83.-D and -T Vortex Flowmeter Intrinsic Safety Connection Diagrams MI 019-175 October 2000 Intrinsically Safe Connection Diagrams If your Model 83.-D/-T
More informationTransmission Line Support Systems
Antenna Support Bracket for transmission line The Antenna Support Bracket angle mounts directly to a 4-1/2" (114 mm) OD antenna pipe mount or tower leg. This is ideal for supporting transmission line runs
More information300 Series Racks. 19" Wide Opening Stand-Alone Wall Cabinet with Adjustable Rails. Applications. Features. In The Box. Options
300 Series Racks 19" Wide Opening Stand-Alone Wall Cabinet with Adjustable Rails Applications The 300 Series is ideal to house electronic equipment for any type of application, both commercial and residential,
More informationHi Density Card Connector SPECIFICATIONS: STANDARD MATERIALS AND FINISHES
Hi Density ard onnector SPEIFITIONS: The micro-miniature card connector series 106 is designed for a space conscious industry. The hi-density card configuration connector provides an extremely dense and
More informationSECTION WIREWAYS FOR RADIOLOGY EQUIPMENT
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable
More informationDIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS
DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS PART 1 GENERAL 1.01 Scope of Work A. Provide material, accessories, tools, equipment and labor as required for the complete fabrication
More informationMH Series Mitered Frames shall be as manufactured or furnished by Republic Doors and Frames, McKenzie, Tennessee
drywall frames - mh series/mitered SHEET NO. 202 MH Series Mitered Frames shall be as manufactured or furnished by Republic Doors and Frames, McKenzie, Tennessee 38201. Profile - Made for two basic door
More informationMulti-Set II Drop-In Anchors
CONCRETE ANCHORING SPECIALISTS Internally Threaded Heavy- Duty Anchoring Systems DESCRIPTION/SUGGESTED SPECIFICATIONS Drop-In, Shell-Type Anchors SPECIFIED FOR ANCHORAGE INTO CONCRETE Drop-In, shell-type
More information2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations.
General Conditions: 1. Deliver all food service equipment as specified herein, including that which is reasonably inferred, with all related items necessary to complete work shown on contract drawings
More information1. This Section specifies the ethernet Category 5E data cabling system for buildings and structures.
PAGE 271200-1 SECTION 271200 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationEMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL
EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION 05720 METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL EMMEGI ARCHITECTURAL FENCING is a high quality steel fencing system comprised of a hybrid
More information4. Metal roof jacks at penetrations and attachments
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - SECTION 07 61 00 METAL SHINGLE ROOFING - - - - - - - - - - -
More informationTOLL FREE:(888) FAX:(941) ASSEMBLY of ProTEC CONCRETE STRUCTURAL INSULATED PANEL
ASSEMBLY of ProTEC CONCRETE STRUCTURAL INSULATED PANEL The ProTEC panels are manufactured with grooves on all four sides to accept the steel components. This grooving applies to the regular panel whose
More informationHeckmann Building Products Inc. DOVETAIL SLOT AND ANCHORS SPECIFICATION SECTION MASONRY ANCHORS AND ACCESSORIES PART 1 GENERAL
Heckmann Building Products Inc. DOVETAIL SLOT AND ANCHORS SPECIFICATION MASONRY ANCHORS AND ACCESSORIES PART 1 GENERAL SECTION 04085 1.1 SECTION INCLUDES NOTE: Delete items below not required for project.
More informationSymphony II Adaptable Table System
Symphony II Adaptable Table System 1.00 General 1.01 Conditions 1.02 Scope of work 1. This section covers all materials, equipment, tools and labor for the supply and installation of the laboratory Symphony
More informationDoor Hinges Drill-in Hinges
Drill-in hinge StarTec Frame part For timber lining frames For rebated doors Maintenance-free friction bearing To use in combination with receiver Max. door weight: 40 kg Knuckle: Ø15 mm Drilling bit Ø7.2
More informationC. HMMA 863: Guide Specifications for Detention Security Hollow Metal Doors and Frames
SECTION 083463 DETENTION DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationCEILING HI-OUTPUT. Project. Type. Notes
Project Type Notes PERFORMANCE/LINEAR FT AT 3000K AND 3500K NOMINAL LUMEN OUTPUT INPUT WATTS* EFFICACY* 3 9/16 700 lm/ft 7.9 W/ft 89 lm/w 900 lm/ft 10.6 W/ft 85 lm/w 1100 lm/ft 13.5 W/ft 81 lm/w 1 5/8"
More informationDERO BIKE LOCKER 33. Maximum Security
Maximum Security The Dero Bike Locker 33 offers bike parking for a single bicycle per unit, thus providing a narrower footprint when space is limited. This affordable bike locker is a perfect option for
More informationSECTION HOLLOW METAL DOORS AND FRAMES
SECTION 081113 HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: Include construction details, material
More informationInstallation Instructions
Installation Instructions 200 Series Curtainwall 3056 WALKER RIDGE DR. NW, SUITE G WALKER, MI 49544 800-866-2227 dependable@tubeliteinc.com Revised April 2014 dependable@tubeliteinc.com Page 1 TABLE OF
More informationARCHITECTURAL STICK SYSTEMS
ABOUT THE STICK SYSTEMS: The Steelcraft Architectural Stick Systems are designed to fit virtually all construction requirements for commercial building applications. These frame assemblies are fabricated
More informationCHASKA 34, CHASKA 335S, CHASKA 29, CHASKA 25
QUALITY FIREPLACES FOR LIFE. KOZY HEAT FIREPLACES CHASKA 34, CHASKA 335S, CHASKA 29, CHASKA 25 Chaska 34 Log shown with a Rectangle screen front with an Antique Copper overlay, log set, custom 4-sided
More informationAMBICO Limited Section and WOOD BULLET RESISTANT DOORS AND FRAMES Page 1
Page 1 This section includes AMBICO Bullet Resistant, Wood Doors and Bullet Resistant Steel Frames which meet the UL752 Standard for Bullet-Resisting Equipment. This section relies on both the Canadian
More informationGE Monogram. Installation. Instructions. 36" Vent Hood. Model ZV750. Call anywhere in the US and Canada -
at :: rangehoods. com GE Monogram Instructions Model ZV750 GE Monogram at:: rangehoods. com is a division of CAUTION WARNING Before you begin Read these instructions completely and carefully. IMPORTANT:
More informationRemoteTeller SYSTEM - RTS VAT 21 GX CUSTOMER UNIT COMPONENTS CUSTOM DESIGNED CUSTOMER AREA
SEND SEND CLL CLL L " LCD COLOR MONITOR 4-29- COLOR CCD CMER 4-29- 486G VT 2 GX CUSTOMER UNIT CLL -8-999-6 LISTINGS ND PPROVLS CLSSIFIED TO UL 4R SFETY OF INFORMTION TECHNOLOGY EQUIPMENT UL TESTED TO THE
More informationSECTION MECHANICAL IDENTIFICATION
Buebtel/Perlcins Community Learning Center GPD - 2001271.15 SECTION 15075 MECHANICAL IDENTIFICATION PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General
More information2-Spindle Horizontal CNC lathes
2-Spindle Horizontal CNC lathes 2-Spindle Horizontal CNC lathes 2SP series machines are true 2-spindle lathes that boast space savings and high productivity Max turning diameter length: ø0 0 Max turning
More informationHALLOWELL HI-TECH SHELVING
LLOLL I-C SLVING i-ech Industrial grade steel shelving continues a tradition of quality established generations ago with the goal of providing a shelving line with the strength needed to handle most industrial
More informationGeneral Product & Quality Specification
DATE: 29/05/12 VERSION NUMBER: 03 General Product & Quality Specification Exterior FX Range Paint Grade Flush Door Introduction: FX range paint grade flush doors are designed for external use, however
More informationUSER MANUAL RM050A-R3, RM051A-R3 WALLMOUNT RACKS 24/7 TECHNICAL SUPPORT AT OR VISIT BLACKBOX.COM
USER MANUAL RM050A-R3, RM051A-R3 ULTRA WALLMOUNT RACKS 24/7 AT OR VISIT BLACKBOX.COM TABLE OF CONTENTS PREFACE... 3 Safety Symbols Used in this Manual...3 Safety Considerations...3 1. SPECIFICATIONS...
More informationSECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT Henderson Engineers, Inc. PART 1 - GENERAL REQUIREMENTS 1.1 SUMMARY A. Extent of Plumbing work to be identified as required by this Section
More informationSECTION COMMON WORK RESULTS FOR HVAC
SECTION 23 05 00 COMMON WORK RESULTS FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Ball Valve. 2. Hangers and Supports. 3. Identification Tags and Sleeves. 1.2 INCLUDED SECTIONS A. Section
More information***************************************************************************************************************
10800 TOILET ROOM ACCESSORIES SPECIFIER: CSI MasterFormat 2004 number 10 28 13 PART 1 GENERAL 1.1 SUMMARY A. Related Sections: 1. 04220 - Concrete Unit Masonry. 2. 06100 - Carpentry. 3. 09310 - Ceramic
More informationSECTION SWINGING AUTOMATIC ENTRANCES
SECTION 084229.33 SWINGING AUTOMATIC ENTRANCES IN-GROUND, AUTOMATIC SWING DOOR OPERATOR CONVERTER ADAPTED TO IR/DOR-O-MATIC SENIOR SWING & ASTRO SWING OPERATOR PART 1-GENERAL 1.01 DESCRIPTION A. This section
More information