1 & ZONE CONTROLS Adjustable Constant Airflow Regulator PRODUCT SPECIFICATIONS & TECHNICAL DATA Construction GENERAL The model Adjustable Constant Airflow Regulator is a modulating orifice that automatically regulates airflows in duct systems to constant levels. The passive control element responds to duct pressure and requires no electric or pneumatic sensors or controls. The compensates for changes in duct pressure caused by thermal stack effect, building pressure, dustclogged filters, etc. The also provides a quiet, low-cost solution to balancing forced-air systems for heating, air conditioning and ventilation, eliminating the need for onsite balancing. The will regulate airflow in supply, return, or exhaust duct systems. It can be mounted horizontally or vertically, and can be fitted in ductwork and accessories. The active control element of the is a flexible bulb that inflates and deflates in response to the static pressure difference across the control. This operation regulates the freearea opening through the control, resulting in maintenance of velocity and specific airflow set points. Each is designed and produced for control of air in temperatures ranging from 14 to 14 F (-1 to 6 C). CONSTRUCTION The is constructed of UL94V- ABS plastic, and it is UL 243 safety classified and labeled for flame and smoke generation. The assembly is sized to fit inside standard rigid round ducting, as well as fittings such as take-offs, tees, etc. A double-lip gasket around the circumference ensures a tight, no-leak fit. PERFORMANCE The airflow regulators control airflow accurately to within ± 3 (5 ) for nominal airflow 3 (5 ) and ± 1% for nominal airflow > 3 (5 throughout the target operating pressure range of.2 to 1. in. w.g. (5 to 25 Pa). Each diameter of regulator is available in multiple factory-calibrated set points (see performance curves). Field adjustment of airflow set points is achieved by twisting the integral rotating ring to the desired set point. No tools are required. INSTALLATION The will push-fit into circular ducts in close proximity to a take-off or a terminal. Mounting can be horizontal or vertical. The orientation must correspond to the airflow direction indicated on the device. 1. Removable clip 2. Regulating silicon membrane 3. Double-lip airtightness seal 4. Housing 5. Rotating airflow adjustment ring Information indicated directly on the product: Flow direction, diameter, operating differential pressure range, part number, and date of manufacture Airlow setting range correlation table in and Typical Applications Supply and exhaust air for offices Balancing exhaust and supply airflows in high-rise building duct risers Bathroom exhaust in nursing homes, hotels, motels, dormitories, apartment buildings, offices, etc. Clean room air supply balancing for ceiling filter modules. Maintains constant airflow, even as filter resistance increases Regulation of make-up air Balancing supply airflow from packaged roof-top A/C units Balancing supply and exhaust of heat recovery ventilation systems Regulating outdoor air injection from central supply fan into individual room fan coil units or heat pumps Balancing airflows on series-fan-powered terminal unit systems Supply air to sleeping quarters in military facilities, etc. MAINTENANCE The needs no maintenance when used in normal conditions. There is no risk of dust deposits or obstruction because the has no airways subject to clogging. If the intended application includes air heavily loaded with grease or dust, a fitting with an access panel or door, such as that used for flame dampers, should be provided. WARRANTY Guaranteed for five (5) years, from date of shipment, against all defects in material or workmanship, provided that the material has been installed and used under normal conditions. This warranty is limited to the repair or replacement of the material. 3 2
2 2 How the Works Constant airflow is achieved by the inflating action of the 's bulb. At minimum static air pressure, the bulb is deflated and has a shape similar to an hourglass. As the static pressure increases across the bulb, it inflates, thereby reducing the free area around the bulb. At the same time, the higher static pressure increases the air velocity, resulting in CONSTANT. This occurs regardless of pressure differences in the range of.2 to 1. in. w.g. (5 to 25 Pa). The air velocity in the duct is in the range of 6 to 7 ft/min. (.3 to 3.5 m/s). ΔP 1. (25) Dimensions Ø Duct Diameter 4" (1 mm) ØN ØB E F A Weight 3.62" (92 mm) 4.13" (15 mm).55".51" (13 mm) 2.76" (7 mm).26 lbs (.12 kg) Ø N 5" (125 mm) 1-5 5" (125 mm) " (116 mm) 4.57" (116 mm) 5.2" (132 mm) 5.2" (132 mm).55".55".51" (13 mm).67" (17 mm) 2.76" (7 mm) 4.33" (11 mm).33 lbs (.15 kg).37 lbs (.17 kg) 6" (15 mm) 5.79" (147 mm) 6.2" (153 mm).55".75" (19 mm) 4.65" (118 mm).82 lbs (.37 kg) Ø B FRONT F A SIDE E 8" (2 mm) 1" (25 mm) 7.48" (19 mm) 9.37" (238 mm) 8.27" (21 mm) 1.32" (262 mm).79" (2 mm).79" (2 mm).91" (23 mm) 1.2" (26 mm) 5.67" (144 mm) 7.5" (179 mm) 1.31 lbs (.59 kg) 2.25 lbs (1.2 kg) Typical Specification Model Adjustable Constant Airflow Regulators by American ALDES Ventilation Corporation, Bradenton, Florida, shall solely operate on duct pressure and require no external power supply. Each regulator shall be capable of being field adjusted to the required airflow set-point, as indicated on the schedule, by twisting the rotating ring to the corresponding airflow set value. The device shall be rated for use in air temperatures ranging from 14 to 14 F (-1 to 6 C). Constant Airflow Regulators shall be capable of maintaining constant airflow within ± 3 (5 ) for nominal airflow 3 (5 ) and ± 1% for nominal airflow > 3 (5 throughout the target operating pressure range of.2 to 1. in. w.g. (5 to 25 Pa) differential pressure. Sound power levels shall not exceed those for each size and rating as scheduled. Regulators shall be provided as an assembly consisting of a PC/ABS plastic housing and regulating silicon membrane. A rotating adjustment ring shall allow for setting of airflow to calibrated set-points. No tools shall be needed to set airflow. Each assembly shall be fitted with a double-lip airtightness seal in elastomer. All regulators must be classified per UL 243 and carry the UL mark indicating compliance. All Adjustable Constant Airflow Regulators will require no maintenance and must be warranted for a period of no less than five (5) years. Adjustable Constant Airflow Regulators shall be installed in tight ducting systems in accordance with all applicable codes and manufacturer s instructions.
3 3 Airflow Performance Data Performance charts reflect airflow variation for each size according to the pressure difference between upstream and downstream of the device. The is designed for the differential operating range from.2-1. in. w.g. (5-25 Pa). Airflow measurements taken at 68 F (2 C) at 1 atmosphere pressure. The regulates within the following nominal airflow tolerances: ± 3 (5 ) for nominal airflow 3 (5 ) and ± 1% for nominal airflow > 3 (5 ). Airflows are rounded to the nearest 5 or 5. Sizes are nominal. Product is designed to be inserted into duct of indicated diameter. 4" DIAMETER (1 mm) REGULATING ELEMENT 7 (12) 6 (1) 47 (8) 35 (6) 22 (4) 12 (2).2 (5).4 (1).6 (15).8 (2) 1. (25) 5 (9 ) 45 (75 ) 35 (6 ) 25 (45 ) 2 (35 ) 1 (15 ) (15 ) 15 (25 ) 2 (35 ) 25 (45 ) 35 (6 ) 4 (7 ) 45 (75 ) 5 (9 ) 5" DIAMETER (125 mm) REGULATING ELEMENT 7 (12) 6 (1) 47 (8) 35 (6) 22 (4) 12 (2).2 (5).4 (1).6 (15).8 (2) 1. (25) 5 (9 ) 4 (7 ) 3 (5 ) 18 (3 ) 15 (25 ) (15 ) 15 (25 ) 18 (3 ) 25 (45 ) 3 (5 ) 35 (6 ) 4 (7 ) 45 (75 ) 5 (85 ) 15 (25) 12 (2) 9 (15) 6 (1) 3 (5).2 (5).4 (1).6 (15).8 (2) 1. (25) 11 (19 ) 95 (16 ) 75 (13 ) 65 (11 ) 6 (1 ) (1 ) 65 (11 ) 7 (12 ) 75 (13 ) 8 (14 ) 9 (15 ) 95 (16 ) 11 (19 )
4 4 Airflow Performance Data Performance charts reflect airflow variation for each size according to the pressure difference between upstream and downstream of the device. The is designed for the differential operating range from.2-1. in. w.g. (5-25 Pa). Airflow measurements taken at 68 F (2 C) at 1 atmosphere pressure. The regulates within the following nominal airflow tolerances: ± 3 (5 ) for nominal airflow 3 (5 ) and ± 1% for nominal airflow > 3 (5 ). Airflows are rounded to the nearest 5 or 5. Sizes are nominal. Product is designed to be inserted into duct of indicated diameter. 6" DIAMETER (15 mm) REGULATING ELEMENT 15 (25) 6 (1 ) 12 (2) 11 (19 ) 95 (16 ) 65 (11 ) 7 (12 ) 9 (15) 6 (1) 75 (13 ) 65 (11 ) 6 (1 ) 75 (13 ) 8 (14 ) 9 (15 ) 3 (5) (16 ) 1 (17 ).2 (5).4 (1).6 (15).8 (2) 1. (25) 15 (18 ) 11 (19 ) 12 (2 ) 125 (21 ) 14 (24 ) 8" DIAMETER (2 mm) REGULATING ELEMENT 355 (6) 295 (5) 235 (4) 175 (3) 12 (2) 235 (4 ) 25 (35 ) 19 (325 ) 16 (275 ) 13 (225 ) (225 ) 15 (25 ) 16 (275 ) 175 (3 ) 6 (1).2 (5).4 (1).6 (15).8 (2) 1. (25) 19 (325 ) 25 (35 ) 235 (4 ) 1" DIAMETER (25 mm) REGULATING ELEMENT 47 (8) 41 (7) 355 (6) 295 (5) 235 (4) 175 (3) 12 (2) 6 (1).2 (5).4 (1).6 (15).8 (2) 1. (25) 38 (65 ) 295 (5 ) 235 (4 ) 175 (3 ) (3 ) 25 (355 ) 235 (4 ) 265 (45 ) 295 (5 ) 325 (55 ) 38 (65 )
5 Acoustic Data 5 Sound power levels of noise (Lw) at duct output. The following tables give the sound power levels of noise (Lw) expressed in decibels per octave (db/oct) as well as the global sound power levels in db(a) according to the pressure drop. These sound power levels are results of tests carried out by a Dutch independent laboratory (PEUTZ) and are given at the duct outlet. Measures were carried out in accordance with NF EN ISO 3741 and NF EN ISO 5135 norms, with an fitted into a duct with an upstream and downstream straight length equal to 3 diameters. Ø4" (1 mm) Differential Pressure DP Airflow.2 (5).4 (1).8 (15) 1. (2) 5 Hz Ø5" (125 mm) Differential Pressure DP Airflow.2 (5).4 (1).8 (15) 1. (2) 5 Hz Ø5" (125 mm) Differential Pressure DP Airflow.2 (5).4 (1).8 (15) 1. (2) 5 Hz
6 6 Acoustic Data Sound power levels of noise (Lw) at duct output. The following tables give the sound power levels of noise (Lw) expressed in decibels per octave (db/oct) as well as the global sound power levels in db(a) according to the pressure drop. These sound power levels are results of tests carried out by a Dutch independent laboratory (PEUTZ) and are given at the duct outlet. Measures were carried out in accordance with NF EN ISO 3741 and NF EN ISO 5135 norms, with an fitted into a duct with an upstream and downstream straight length equal to 3 diameters. Ø6" (16 mm) Differential Pressure DP Airflow.2 (5).4 (1).8 (15) 1. (2) 5 Hz Ø8" (2 mm) Differential Pressure DP Airflow.2 (5).4 (1).8 (15) 1. (2) 5 Hz Ø1" (25 mm) Differential Pressure DP Airflow.2 (5).4 (1).8 (15) 1. (2) 5 Hz American ALDES Ventilation Corporation. Reproduction or distribution, in whole or in part, of this document, in any form or by any means, without the express written consent of American ALDES Ventilation Corporation, is strictly prohibited. The information contained within this document is subject to change without prior written notice. American ALDES Ventilation Corporation th Street Court East, Suite 14 Bradenton, FL 3423 USA (fax) info@americanaldes.com mr-modulo_spec_814
Model ABV Pressure Independent Automatic Balancing Valve. Application: Standard Construction: Performance: Configurations Available:
Application: Tag: Project: Location: Date: Engineer: Contractor: Architect: Submitted by: The ABV Automatic maintains a constant airflow volume in HVAC applications. The highly engineered damper blade
More informationNK / NL series. Rectangular VAV and CAV air volume control terminals
NK / NL series Table of contents Description Page Type designation 1 Technical data - General 2 - Specification 3 - Installation instruction 3 Model overview / dimensions 4-5 Sound data NKOAOOB / NLOAOOB
More informationVolumetric flow controller
Volumetric flow controller VRAR Leakage air flow with control damper closed according to DIN EN 1751, up to class 3 Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telephone +49 (0) 74-980 - 0 Fax
More informationDuctwork Controls and Instrumentation Outlets (HVAC) HVAC Control System.
SECTION 15910 DUCT ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15890 - Ductwork. 2. 15900 - Controls and Instrumentation. 3. 15940 - Outlets (HVAC). 4. 15970 - HVAC Control System.
More informationCONNOLS-AIR. AIR TERMINAL UNITS Engineered for Versatile Application and Energy Conservation
CONNOLS-AIR AIR TERMINAL UNITS Engineered for Versatile Application and Energy Conservation Marina Bay Business District is considered the trendiest and most technologically advance area for business in
More informationKitchen exhaust fan GLEB
Kitchen exhaust fan GLEB Contents Kitchen exhaust fan - GLEB...3 Performance Data...4 Dimensions...5 Wiring diagram...6 General description...7 Applications...7 Demand control ventilation...7 Quiet operation...7
More informationRECTANGULAR CAV AND VAV AIR VOLUME CONTROL TERMINALS NK / NL SERIES
RECTANGULAR CAV AND VAV AIR VOLUME CONTROL TERMINALS NK / NL SERIES Table of contents Description Page Type designation 1 Technical data - General 2 - Specification 3 - Installation instruction 3 Model
More informationKCR-R CONSTANT AIR VOLUME FLOW REGULATOR
KCR-R CONSTANT AIR VOLUME FLOW REGULATOR Intended use: The regulator can be used in both intake and exhaust ventilation ducts. Made of M1 class plastic. Operating range up to 60 C Desription: The constant
More informationEXPERIMENTAL INVESTIGATIONS OF DIFFERENT MICROPHONE INSTALLATIONS FOR ACTIVE NOISE CONTROL IN DUCTS
EXPERIMENTAL INVESTIGATIONS OF DIFFERENT MICROPHONE INSTALLATIONS FOR ACTIVE NOISE CONTROL IN DUCTS M. Larsson, S. Johansson, L. Håkansson and I. Claesson Department of Signal Processing Blekinge Institute
More informationFLOW SWITCH 600 Series Velocity Flow Sensor. Instruction Manual
SWITCH 600 Series Velocity Flow Sensor Instruction Manual Ultrasonic Velocity Sensor using Doppler Technology Model: FS-600 Manual Release Date: November, 2009 ECHO Process Instrumentation, Inc. CONTENTS
More informationTechnical Development Program
Technical Development Program COMMERCIAL DISTRIBUTION SYSTEMS PRESENTED BY: Ray Chow Duct Design Level 1 Fundamentals Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Introduction
More informationA. Radius elbows with a construction radius of 1.5 the duct width are preferred to square elbows.
SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insulation shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation
More informationSECTION LOW PRESSURE DUCTWORK
SECTION 15841 LOW PRESSURE DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 15260 - Vibration Isolation. 3. 15280 - Thermal Insulation
More informationDigital flow transmitter for continuous flow measurement
Digital flow transmitter for continuous flow measurement Compact or remote version for DN 06 to 400, PN10 Shows both flow rate and volume (with two totalizers) Automatic-calibration: TEACH-IN Simulation:
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION MECHANICAL SCOPE OF WORK PART 1 - GENERAL
SECTION 23 00 10 - MECHANICAL SCOPE OF WORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01
More informationFST Series HUMIDITY-TEMPERATURE TRANSMITTERS INSTRUCTION MANUAL
FST Series HUMIDITY-TEMPERATURE TRANSMITTERS INSTRUCTION MANUAL 20020628 CONTENTS DESCRIPTION... 3 OPERATION... 4 Power Supply...4 Output Range...4 Temperature Operating Range and Temperature Limits...4
More information1.) Type: VL-F Single compartment rectangular smoke extraction ducts and fittings
1.) Type: VL-F Single compartment rectangular smoke extraction ducts and fittings 2.) Manufacturer / Place of manufacture: AEROPRODUKT Zrt., 6640 Csongrád, Szegedi út 1., HUNGARY 3.) Function: The smoke
More informationRS/2/C/003MR Published August RATING STANDARD for the certification of Rigid Metallic Ductwork Systems with Rectangular Cross-section
RATING STANDARD for the certification of Rigid Metallic Ductwork Systems with Rectangular Cross-section Editing (date): Marie-Clémence DEGALLAIX (30/05/2016) Checking (date): Jean FOURCROY (02/06/2016)
More informationPRESTON HEALTH SERVICES ARCHITECT S NO. 2700
SECTION 23 3113 - LOW PRESSURE DUCTWORK PART 1 - GENERAL 1.1 SCOPE OF WORK: A. The work required under this section includes all work necessary for a complete installation of ductwork and accessories.
More informationDigital flow ELEMENT transmitter for continuous flow measurement
Digital flow ELEMENT transmitter for continuous flow measurement Type 8036 can be combined with... DN06 to DN65 fluidic process connection Programmable outputs : one or two transistor output(s) and single
More informationDIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS
DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS PART 1 GENERAL 1.01 Scope of Work A. Provide material, accessories, tools, equipment and labor as required for the complete fabrication
More information*************************************************************************************************************
15890 DUCTWORK ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 23 33 13 *************************************************************************************************************
More informationInstruction Sheet. VRS Series. Vertical Rackmount system for multiple cable/satellite receivers
Instruction Sheet VRS Series Vertical Rackmount system for multiple cable/satellite receivers THANK YOU Thank you for purchasing the VRS Vertical Rackmount System. Please read these instructions thoroughly
More informationSubmittal Transmittal
Submittal Transmittal Standard St. Joe's - Sonntag Pavillion St. Joseph s Hospital 350 W. Thomas Road Phoenix, AZ 85013 Project # 5690A Tel: Fax: Kitchell Contractors Inc of AZ Date: 10/7/2011 Reference
More informationseries SMLD Smoke Evacuation Damper
series SMLD Smoke Evacuation Damper www.koolair.com Series SMLD 1 CONTENTS Description 2 Dimensions 4 Installation 6 Electrical connections 7 Technical data 9 Coding 11 2 Series SMLD Description Multi-blade
More informationWiring ducts Easily allows for organization, pulling and separation of cables
Easily allows for organization, pulling and separation of cables 2 Catalogue Wiring ducts I ABB Index Halogen free wiring ducts with vertical slots 4 Thermoplastic wiring ducts with vertical slots Flexible
More informationModel 5100F. Advanced Test Equipment Rentals ATEC (2832) OWNER S MANUAL RF POWER AMPLIFIER
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) OWNER S MANUAL Model 5100F RF POWER AMPLIFIER 0.8 2.5 GHz, 25 Watts Ophir RF 5300 Beethoven Street Los Angeles, CA 90066
More informationMEC MEC C Wall-mounted air heaters for indoor installation
mod. MEC mod. MEC C Model Heat Input Heat Output Code MEC 25 25,00,90 30120000 3.000,00 MEC 35 300000 3.080,00 MEC 50 50,00 45,30 30270000 4.0,00 MEC 57 30320000 4.710,00 MEC 85 30370000 6.740,00 MEC 35
More informationinter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE
Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 3.8 THE FIRST 1000
More informationVolumetric flow controller
Volumetric flow controller Model VRA Leakage air flow with control damper closed according to DIN EN 1751, up to class 4 Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telephone +49 (0) 74 63-980
More informationREVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty
HOT AISLE CONTAINMENT SYSTEM (HACS) REVISION #1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. C. Drawings and general provisions of the Contract, including General and Supplementary. Conditions apply to
More informationRicochet Alphasonic Level Transmitter Model LA15/20 Owner s Manual
Warranty, Service & Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: Flowline Inc. 500 Humbolt Street Los Alamitos, CA 9. If for
More informationGuide. Installation. Wilson Electronics, Inc. Direct Connection High Power iden Amplifi er 800 MHz Band. Contents:
Amplifier Installation Guide Direct Connection High Power iden Amplifi er 800 MHz Band Contents: Guarantee and Warranty 1 Before Getting Started / How it Works 3 Installing a Wilson Outside Antenna - In-Vehicle
More informationRIGOL. User s Guide. RP1000D Series High Voltage Differential Probe. Feb RIGOL Technologies, Inc
User s Guide RP1000D Series High Voltage Differential Probe Feb. 2013 RIGOL Technologies, Inc Guaranty and Declaration Copyright 2012 RIGOL Technologies, Inc. All Rights Reserved. Trademark Information
More informationSTANDARD MICROWAVE COMBINER MODEL SMC-XX-X-HP-X
SMC-XX-X-HP Standard Microwave Combiner STANDARD MICROWAVE COMBINER MODEL SMC-XX-X-HP-X Installation Manual Please read the manual completely and carefully before installation. Instructions are intended
More informationCOMMERCIAL KITCHEN HOOD WORKSHEET/ CHECKLIST
COMMERCIAL KITCHEN HOOD WORKSHEET/ CHECKLIST Two copies of this worksheet/checklist must accompany plans sets submitted with commercial kitchen application. The applicant is responsible for assuring the
More informationCIS400. Two-Way Ceiling Monitor CIS400 TWO-WAY CEILING MONITOR FEATURES APPLICATIONS
CIS400 TWO-WAY CEILING MONITOR The CIS400 is a complete two-way bassreflex flush-mount loudspeaker assembly designed for fixed installations into typical ceiling plenum spaces. Employing a unique HF waveguide
More informationDifferential pressure sensors
1 912 1912P02 QBM64/ 1912P01 QBM63/ Differential pressure sensors for air and non-aggressive gases, with a diaphragm sensing element QBM63/ QBM64/ With choice of pressure-linear or extracting-the-root
More informationInstallation and Maintenance Manual IM 770-1
Installation and Maintenance Manual IM 770-1 Group: Applied Air Systems Part Number: IM 770 Date: March 2014 Skyline Outdoor Air Handler Roof Curb Table of Contents General Description... 3 Curb-Ready
More informationSolitel Vibrating Rod Level Switch
Solitel Vibrating Rod Level Switch D E S C R I P T I O N Solitel Vibrating Rod Level Switches provide reliable level detection of powders and bulk solids. This compact, integral switch is suitable for
More informationInstallation and Operating Instructions Differential pressure transmitter for potentially explosive areas. MG-1000-EEx USAGE STRUCTURE AND DESIGN
Installation and Operating Instructions Differential pressure transmitter for potentially explosive areas Mimablad: 176GB/1999-10-25 Ersätter: MG-1000-EEx USAGE MG-1000-EEx is suitable for use in measurement
More informationInstallation Guide. Model #400. Corporate Office: 349 Highland Road East Macedonia, Ohio
Installation Guide Model #400 Corporate Office: 349 Highland Road East Macedonia, Ohio 44056 1.866.822.7328 www.ezbreathe.com Copyright 2006, EZ Breathe, LLC WHAT S INSIDE Before installing your EZ Breathe
More informationINSTRUCTION MANUAL For LINE IMPEDANCE STABILIZATION NETWORK. Model LI khz to 10 MHz
Page 1 of 10 INSTRUCTION MANUAL For LINE IMPEDANCE STABILIZATION NETWORK Model LI-4100 10 khz to 10 MHz Page 2 of 10 Table of Contents 1.0 Introduction... 3 2.0 Product Description... 4 3.0 Product Specifications...
More informationINLINE flowmeter for continuous flow measurement
INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection
More informationCOLIBRI Ceiling. Square ceiling diffuser with discs for supply air QUICK FACTS
Square ceiling diffuser with discs for supply air QUICK FACTS Adjustable discs flexible spread pattern Can be used for vertical air diffusion Swirl function Also available in the Extract air version Designed
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017
SECTION 23 0553 - MECHANICAL SYSTEMS IDENTIFICATION GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationCONTROL Room. Room product for Swegon s WISE system for demand-controlled ventilation. Quick facts Room control against temperature, CO 2
Room product for Swegon s WISE system for demand-controlled ventilation Quick facts Room control against temperature, CO 2, content, etc. Static pressure and flow measurement Position-independent Shut-off-capable
More informationGuide. Installation. Wilson Electronics, Inc. In-Building Wireless Amplifi er. Contents:
Amplifier Installation Guide In-Building Wireless Amplifi er Contents: Guarantee and Warranty 1 Antenna Options and Accessories 2 Before Getting Started / How It Works 3 Installation Overview 4 Installing
More information2/2-Way Solenoid Control Valve
2/2-Way Solenoid Control Valve Excellent range (1:200) Very good response Compact valve design Orifice sizes 0.8... 4 mm Port connection 1/8, 1/4 or sub-base Type 2873 can be combined with Type 8605 Digital
More informationM1.0 MECHNANICAL FLOOR PLAN
GENERAL NOTES A. CONTRACTORS AND SUB CONTRACTORS SHALL CAREFULLY REVIEW THE CONSTRUCTION DOCUMENTS. INFORMATION REGARDING THE COMPLETE WORK IS DISPERSED THROUGHOUT THE DOCUMENT SET AND CANNOT BE ACCURATELY
More informationCOLIBRITM. Ceiling. Square ceiling diffuser with discs for supply air. Quick guide
COLIBRITM Ceiling Square ceiling diffuser with discs for supply air Quick facts Adjustable discs flexible spread pattern Can be used for vertical air diffusion Swirl function Also available in the exhaust
More informationWilson. iden 800 MHz. Adjustable Gain In-Building Wireless Smart Technology Signal Booster. Appearance of device and accessories may vary.
iden 800 MHz Adjustable Gain In-Building Wireless Smart Technology Contents: Options & Accessories....................... 1 Quick Install Overview............................... 2 Installation Diagram.................................
More informationLOW PRESSURE STEEL DUCTWORK Mechanical Systems Insulation Outlets (HVAC) Testing and Balancing.
SECTION 15841 LOW PRESSURE STEEL DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15180 - Mechanical Systems Insulation. 2. 15940 - Outlets (HVAC). 3. 15991 - Testing and Balancing. 1.02 SUBMITTALS
More informationVAV Rectangular Terminal Units
RSVQ VAV Rectangular Terminal Units RSVQ Variable Air Volume (VAV) HVAC systems are the best solution to guarantee high levels of comfort and energy effi ciency in civil and industrial applications VAV
More informationWATERFLUX 3000 Quick Start
WATERFLUX 3000 Quick Start Electromagnetic flowmeter The documentation is only complete when used in combination with the relevant documentation for the signal converter. KROHNE CONTENTS WATERFLUX 3000
More informationMANUAL TNS Series Nut Splitter
TNS Series OPERATION AND MAINTENANCE MANUAL TNS Series Nut Splitter MODELS TNS-012, TNS-100, TNS-104, TNS-108, TNS-112, TNS-200, TNS-208, & TNS-300 1025 Conroy Place, Easton, PA. 18040 U.S.A. Phone: +1
More informationSolitel Vibrating Rod Level Switch
Solitel Vibrating Rod Level Switch DESCRIPTION Solitel Vibrating Rod Level Switches provide reliable level detection of powders and bulk solids. This compact, integral switch is suitable for high or low
More informationFacility Services Subgroup Preface for Divisions 21` through 28
Facility Services Subgroup Preface for Divisions 21` through 28 1.1 EXECUTIVE SUMMARY A. This document provides standards for the Consultants and Contractors producing mechanical and electrical design
More informationNon-Submersible Industrial Pressure Transducer
Non-Submersible Industrial Pressure Transducer KPSI Transducers Series 27, 28, 30 FEATURES Custom Pressure Ranges up to 2000 (13,790 kpa) Accuracy to ±0.10% FS Analog Outputs of 4-20 ma or VDC Welded 316
More informationFor Accurate Music and Voice Reproduction from In-Ceiling Locations
INSTALLATION & USER GUIDE For Accurate Music and Voice Reproduction from In-Ceiling Locations 6-1/2" IN-CEILING LOUDSPEAKER LSC-6 /6.5 LSC-6 / 6.5 6-1/2" IN-CEILING LOUDSPEAKER TABLE OF CONTENTS Features...1
More informationHZ301 & HZ321. Standard and Junior Flush Valve Installation Instructions
TABLE OF CONTENTS Product Overview.. 2 How to Order.. 2 Product Specifications.. 2 Tools Required... 2 Safety Instructions. 3 Visual Check.. 3 Flush Pipe Installation 3 Hygihose Installation. 4 Duct Connection.
More informationModel LF2500 Low Frequency Sound Silencer
Model LF Low Frequency Sound Silencer The SEMCO Model LF low frequency sound silencers are specifically designed to solve noise problems in the lower frequency range and will provide excellent low band
More information5G350 Nominal 33W 5G530 Nominal 48W 5G700 Nominal 64W 5G105 Nominal 97W 5G140 Nominal 126W K K. 1 DM or HL only. Cannot be combined.
Project: Type: Qty: BLL _ Series Mounting Optics Light Engine CCT Finish Voltage Options _ Pole Series Height Finish Pole Options Series Mounting Optics Light Engine CCT Finish Voltage Options BLL Beta
More informationAutoSPLITTER STRAIGHT HEAD MODELS
AutoSPLITTER STRAIGHT HEAD MODELS HYDRAULIC NUT SPLITTER OPERATIONS AND MAINTENANCE MANUAL 1 CONTENTS INTRODUCTION... Page 3 WARNINGS AND SAFETY TIPS... Page 4 POWER REQUIREMENTS... Page 5 ASSEMBLY...
More informationHumidity Temperature Sensor TFG80 Duct version with Polyga measuring element
Galltec Mess- und Regeltechnik GmbH MELA Sensortechnik GmbH D-71145 Bondorf. Germany D-07987 Mohlsdorf-Teichwolframsdorf. Germany Tel. +49 (0)7457-9453-0. Fax +49 (0)7457-3758 Tel. +49(0)3661-62704-0.
More informationAutomatic Film Applicator BEVS 1811/2 User Manual
Automatic Film Applicator BEVS 1811/2 User Manual This manual shall be read carefully before starting. Directions included in this operation manual shall be strictly followed. PAGE 1 Content 1 Company
More informationAPPENDIX A, UMC STANDARD 6-5 STANDARD FOR INSTALLATION OF FACTORY-MADE AIR DUCTS
STANDARD FOR INSTALLATION OF FACTORY-MADE AIR DUCTS Sealing of fibrous glass duct board to the sheet metal sleeve must be made with glass fabric and mastic, except where operating pressure is less than
More informationSide. Channel Blower APEX DARGANG MACHINERY CORPORATION
Side Channel Blower APEX DARGANG MACHINERY CORPORATION Side Channel Blower Construction External bearing Cool-running Long life Motor Industrial quality /60Hz Squired-cage motor totally enclosed(ip55 )
More informationDVS 4 / DVS 4t. Features. Product Description. Applications
UL-148, UL3 Product Description Designed for a wide variety of discrete small scale sound reinforcement applications, the Tannoy DVS 4 is an ultra compact surface mount loudspeaker of exceptional value
More informationProduct Data Sheet RER225-63/18/2TDO- 406
Product Data Sheet RER225-63/18/2TDO- 406 The engineer's choice RER225-63/18/2TDO-406 INDEX 1 General... 3 2 Mechanics... 3 2.1 General... 3 2.2 Connections... 3 3 Operating Data... 5 3.1 Operating Data
More informationSIT 849 SIGMA LH M U LT I F U N C T I O N A L C O N T R O L F O R G A S B U R N I N G A P P L I A N C E. w w w. s i t g r o u p.
SIT 89 SIGMA LH M U LT I F U N C T I O N A L C O N T R O L F O R G A S B U R N I N G A P P L I A N C E 9.955.19 Subject to change without notice Application Domestic gas appliances: central heating boilers,
More informationElectromagnetic Flow Transmitter
Electromagnetic Flow Transmitter Sensor in solid state technology Working as a transmitter and/or as an On/Off controller Automatic-calibration of full scale: Teach-In Clean in place (CIP) Type can be
More informationAcoustics. Randy Zimmerman Chief Engineer
Acoustics Randy Zimmerman Chief Engineer Instructor Randy Zimmerman Chief Engineer 972.212.4811 rzimmerman@titus-hvac.com What You Will Learn Sound power vs sound pressure Sound quality AHRI 880/885 NC
More informationWATERFLUX 3000 Quick Start
WATERFLUX 3000 Quick Start Electromagnetic flow sensor The documentation is only complete when used in combination with the relevant documentation for the signal converter. KROHNE CONTENTS WATERFLUX 3000
More informationHLC-1000 High-limit Humidity Control
FANs 216, 1628.3 Product/Technical Bulletin HLC-1000 Issue Date 1197 HLC-1000 High-limit Humidity Control The HLC-1000 is designed to limit duct humidity by comparing a controller s request for humidification
More informationPhase-sequence Phase-loss Relay
Phase-sequence Phase-loss Relay K8AB-PH Three-phase Phase-sequence Phase-loss Relay Using Voltage Detection Method Prevents reverse motor rotation due to incorrect wiring. Distinguishes between positive
More information2-wire level transmitter
Badger Meter Europa GmbH 2-wire level transmitter Model L2xx INSTALLATION AND OPERATION MANUAL July 2002 Version UF-L2xx-07/02-e Contents Contents Page 1. Installation 1 1.1 Mounting the instrument 1 1.2
More informationDATASHEET AND OPERATING GUIDE TCS Series Thermistors
DATASHEET AND OPERATING GUIDE TCS Series Thermistors CYLINDRICAL HEAD CYLINDRICAL HEAD THERMISTOR This ±1% thermistor is encapsulated in a polyimide tube, for assemblies where surface mounting or embedding
More informationCMS601. Product Description. Features. Applications
CMS61 Product Description The Tannoy CMS61 is a full bandwidth; high power and high sensitivity ceiling monitor system. The design comprises a 165mm (6.5") transducer mounted in a vented, injection moulded,
More informationSize : Connection End : Min Temperature : Max Temperature : Materials : Cast iron body
Size : Connection End : Min Temperature : Max Temperature : DN 50 to 200 Flanged R.F. PN10/16 0 C ( for cold water type ) + 90 C (for hot water type ) Max Pressure : 16 Bars Specifications : Horizontal
More informationIntrinsically safe pressure transmitter MBS 4201, MBS 4251, MBS 4701 and MBS 4751
Data sheet Intrinsically safe pressure transmitter MBS 420, MBS 425, MBS 470 and MBS 475 The intrinsically safe pressure transmitter program is designed for use in hazardous environments and offers a reliable
More informationDigital flow ELEMENT transmitter for continuous flow measurement
ELEMENT Transmitter Digital flow ELEMENT transmitter for continuous flow measurement Type can be combined with... PN10, DN15 to DN400 fluidic process connection Programmable outputs : one or two transistor
More informationSplit case double suction centrifugal pump. Technical data Serie: DPAS C
Split case double suction centrifugal pump Technical data Serie: DPAS C Table of Contents 1 Introduction 1.1 Fields of Application... 1. Pumped Liquids... 1.3 Design... 1. Bearings... 1.5 Shaft Seal...
More informationM1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL
M1 Series Humidity - Temperature Transmitter INSTRUCTION MANUAL 20031110 -2- CONTENTS Overview... 3 Operation... 4 Power supply... 4 Operating range and limits... 4 Temperature compensation of the humidity
More informationMODUBLOC MB SE SERIES
The MODUBLOC MB SE series of burners are characterised by a monoblock structure that means all necessary components can be combined in a single unit, making installation easier and faster. The series covers
More informationElectro-Voice S40. Full Range Compact Speaker System 160 Watts Power Handling Available is Black or White
Electro-Voice S40 Full Range Compact Speaker System 160 Watts Power Handling Available is Black or White NOTE: This data sheet refers to several graphs. In order to keep the size of this document reasonable
More informationGT-1050A 2 GHz to 50 GHz Microwave Power Amplifier
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Giga-tronics GT-1050A Microwave Power Amplifier GT-1050A 2 GHz to 50 GHz Microwave Power Amplifier Operation Manual
More informationType PLC Fitting. Valve for Continuous control. Diaphragm valve. Output
Digital Inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
More informationNEBB Instrument Master List (Effective January 1, 2019)
Discipline Function RC Air Pressure 0 in wg 0 Pa to to 10 in wg 2% of reading ± 0.001 2500 Pa 2% of reading ± 0.25 in wg Pa 0.001 in wg < 1 in wg 0.01 in wg > 1 in wg 0.10 Pa < 250 Pa 10 Pa > 250 Pa Air
More informationInstruction manual for STA 1 sectional door operator
Instruction manual for STA 1 sectional door operator Sectional door operator STA 1 / Rev. 0.3 1 GB 1. Contents 3. General safety instructions 1. Contents 2 2. Key to symbols 2 3. General safety instructions
More informationFor Accurate Music and Voice Reproduction from In-Ceiling Locations
INSTALLATION & USER GUIDE For Accurate Music and Voice Reproduction from In-Ceiling Locations 5-1/4 IN-CEILING LOUDSPEAKER LSC-5 /5R LSC-5 / 5R 5-1/4 IN-CEILING SPEAKER TABLE OF CONTENTS Features...1 Product
More informationKRAMER ELECTRONICS LTD. USER MANUAL MODELS: SPK-C612 Closed-back Ceiling Speakers SPK-C412 SPK-C411. P/N: Rev 1
KRAMER ELECTRONICS LTD. USER MANUAL MODELS: SPK-C612 Closed-back Ceiling Speakers SPK-C412 Closed-back Ceiling Speakers SPK-C411 Closed-back Ceiling Speakers P/N: 2900-300113 Rev 1 Contents 1 Introduction
More informationDirectional valves Electrically operated Series 563, 565, 567. Brochure
Directional valves Electrically operated Brochure 2 Directional valves Electrically operated 3/2-directional valve, Series 563 Qn = 1350 l/min plate connection Electr. connection: Plug, Form B, industry
More information25 / 35 / 45. Rectangular Duct Connection System. Strong and Virtually Leak Free. Simple to install No additional sealing required
D U C T M A T E 25 / 35 / 45 Rectangular Duct Connection System Strong and Virtually Leak Free Simple to install No additional sealing required Available in specialty metals Consistent connections 25 /
More informationIntegrate the Window and WRB (1/2)
Window and WRB Installation - Window/WRB. Cut the house wrap flush along all sides of the rough opening.. Slope the sill and flash with flashing tape. Push the tape tight into the corners, being careful
More informationInstall Speakers. 2 Way 3.5" Full Range Ceiling Loudspeaker with Line Transformer for Installation Applications (White)
Compact 2 way full range ceiling loudspeaker for installation applications 30 Watts continuous, 120 Watts peak power High excursion 3.5" low frequency driver with high temperature voice coil 1" ferrofluid
More informationRS /E-EV BLU SERIES
The RS/E and RS/EV series burners are characterised by a modular monoblock structure that means all necessary components can be combined in a single unit thus making installation easier, faster and, above
More informationOne Revolution Tube Cutter
One Revolution Tube Cutter Series 9060 Tube & Pipe Cleaners Tube Testers Tube Plugs Tube Removal Tube Installation Operating and Maintenance Instructions www.elliott-tool.com Table Of Contents Introduction...
More informationASX SERIES PACIFIC OPERATION MANUAL AC POWER SOURCE POWER SOURCE
ASX SERIES AC POWER SOURCE OPERATION MANUAL PACIFIC POWER SOURCE ASX-SERIES OPERATION MANUAL FOR THE MODELS 115-ASX, 120-ASX 140-ASX, 160-ASX 315-ASX, 320-ASX 345-ASX, 360-ASX 390-ASX, 3120-ASX PPS PART
More informationDescription. 175 watts Test Voltages: 34.2 volts rms 68.3 volts peak R SR (1.15 R E. ): 6.67 ohms. Suspending the Xi-1082
Xi-1082 X-Array Install Two-Way, Full-Range, Sound-Reinforcement System 8-inch two-way 90 x 40 horn coverage 175-watts long term power capacity Ring-Mode Decoupling (RMD ) Full-range with internal passive
More information